background image

6

18-CD19D7-22

Installer’s Guide

UPFLOW INSTALLATION

Standoffs and screws (See Figure 1) are included with the
cased coils for attachment to the furnace.  There are clear-
ance alignment holes near the bottom of the coil wrapper and
drill screws are used to engage the furnace top flange.  The
standoff is inserted into the cabinet alignment hole. The drill
screws are inserted through the standoffs then screwed into
the furnace flange.  The coil is always placed downstream of
the furnace airflow.  These instructions apply only if the coil
is on top of an upflow furnace.

DOWNFLOW INSTALLATION

WARNING

!

Do not install the furnace directly on carpeting, tile or other
combustible material other than wood flooring.  For vertical
downflow application, subbase (BAYBASE205) must be
used between the furnace and combustible flooring.  When
the downflow furnace is installed vertically with a cased
coil, a subbase is not required.

REQUIRED FLOOR OPENING:  (DOWNFLOW)

See Figure 2 and Table 1

TABLE 1

CABINET

WIDTH

RETURN

DUCT WIDTH

FLOOR OPENING PLENUM OPENING

"A"

"B"

"C"

"D"

14-1/2"

13-1/4"

13-5/8"

20-1/8"

12-5/8"

19-3/8"

17-1/2"

16-1/4"

16-5/8"

20-1/8"

15-5/8"

19-3/8"

21"

19-3/4"

20-1/8"

20-1/8"

19-1/8"

19-3/8"

24-1/2"

23-1/4"

23-5/8"

20-1/8"

22-5/8"

19-3/8"

HORIZONTAL INSTALLATION

The coil and furnace must be fully supported when used in the
horizontal position.

Three brackets (with screws) are included with downflow
furnaces for installation to stabilize and secure the furnace
and TXC cased coil in the 

horizontal position

. See Figure 4.

IMPORTANT:
The 2/4TXC cased coil must be placed downstream of the
furnace.  In horizontal installations, the apex of the coil
may point either toward or away from the furnace.  See
the 2/4TXC coil Installer's Guide for more details.

The cased coil is secured to the furnace and both the furnace

and

 the cased coil must be properly supported. The brackets

mount using the rear screws on the coil case and use the
screws provided to secure the bracket to the furnace. The

123456789012345678901234567890121234567890123456

123456789012345678901234567890121234567890123456

123456789012345678901234567890121234567890123456

123456789012345678901234567890121234567890123456

123456789012345678901234567890121234567890123456

123456789012345678901234567890121234567890123456

123456789012345678901234567890121234567890123456

123456789012345678901234567890121234567890123456

123456789012345678901234567890121234567890123456

123456789012345678901234567890121234567890123456

123456789012345678901234567890121234567890123456

123456789012345678901234567890121234567890123456

123456789012345678901234567890121234567890123456

123456789012345678901234567890121234567890123456

123456789012345678901234567890121234567890123456

123456789012345678901234567890121234567890123456

123456789012345678901234567890121234567890123456

123456789012345678901234567890121234567890123456

123456789012345678901234567890121234567890123456

123456789012345678901234567890121234567890123456

FURNACE

FRONT

A (width)

B (depth)

C

D

3

UPFLO

W

FURNA

CE

CASED

COIL

SCREWS

(BOTH SIDES)

STANDOFFS

(BOTH SIDES)

STANDOFFS (4)

DRILL SCREWS (4)

FOR VERTICAL

INSTALLATIONS

1

2

CASED COIL CONNECTION

BRACKET FOR DOWNFLOW

FURNACE IN HORIZONTAL

DOWNFLOW ONLY

4

5

remaining bracket is placed as close to center as possible
(horizontally) between the coil case front and the furnace
bottom channel (for downflow/horizontal furnace). Use four of
the screws provided to secure the bracket.

This furnace may be installed in an attic or crawl space in the
horizontal position by placing the furnace on the left or right
side (as viewed from the front in the upright position).  The
horizontal furnace installation in an attic should be on a
service platform large enough to allow for proper clearances
on all sides and service access to the front of the furnace (See
Clearance Table on Outline Drawings, pages 4&5, and
Figure 5 below).

If the furnace is suspended using perforated steel strap
(plumber’s strap), it must be supported at all four corners
and in the middle at the front of the furnace. The forward
most screw on the side of the furnace may be used to connect
the strapping (See Figure 6 on page 7).

TYPICAL ATTIC PLATFORM INSTALLATION

(UPFLOW/HORIZONTAL FURNACE SHOWN)

Содержание DD1A040A9241A Series

Страница 1: ...rotation ALL phases of this installation must comply with NATIONAL STATE AND LOCAL CODES IMPORTANT This Document is customer property and is to remain with this unit Please return to service informati...

Страница 2: ...g ignition input rate temperature rise and venting according to the manufacturer s instructions 10 This product must be piped by a Licensed Plumber or Gas Fitter in the Commonwealth of Massachusetts S...

Страница 3: ...drops or ducts with equivalent lengths and sizes See Field Wiring Diagrams for Twinning on page 16 for proper hookup CAUTION To prevent shortening its service life the furnace should not be used as a...

Страница 4: ...4 18 CD19D7 22 Installer s Guide From Dwg 21C341699 Rev 7 UD A 1A OUTLINE DRAWING ALL DIMENSIONS ARE IN INCHES...

Страница 5: ...18 CD19D7 22 5 Installer s Guide From Dwg 21C341700 Sh 1 Rev 3 DD A 1A OUTLINE DRAWING ALL DIMENSIONS ARE IN INCHES...

Страница 6: ...234567890123456 123456789012345678901234567890121234567890123456 123456789012345678901234567890121234567890123456 123456789012345678901234567890121234567890123456 1234567890123456789012345678901212345...

Страница 7: ...FURNACE SHOWN Confined spaces are installations with less than 50 cu ft of space per 1000 BTU hr input from all equipment installed Air for combustion and ventilation requirements can be supplied fro...

Страница 8: ...he furnace is located in a utility room adjacent to the living area the system should be carefully designed with returns which minimize noise transmission through the return air grille Although these...

Страница 9: ...n Flexible duct connectors are recommended to connect both supply and return air ducts to the furnace If only the front of the furnace is accessible it is recommended that both supply and return air p...

Страница 10: ...inserted into the bottom of the furnace The retaining screw pin on each side inserts into engagement holes at the bottom of the furnace cabinet side See Figures 13 14 16 NOTE Remove the bottom front...

Страница 11: ...e side of the furnace Confirm that the upper retaining pin screw locks into the engagement hole in the blower deck and the lower pin screw rests against the side of the bottom panel See Figures 14 15...

Страница 12: ...1 2 DO NOT CUT CUT ON LINE Airflow Airflow d TABLE 7 CABINET WIDTH FILTER SIZE FILTER BRACKET LOCATION 14 1 2 2 14X20X1 12 7 8 17 1 2 2 16X20X1 14 3 8 21 2 16X20X1 13 1 8 24 1 2 2 16X20X1 11 5 8 Locat...

Страница 13: ...ercent NOTE If desired a side wall termination can be accom plished through the use of an add on draft inducer The inducer must be installed according to the inducer manufacturer s instructions Set th...

Страница 14: ...before servicing the unit Failure to follow this warning could result in electrical shock personal injury or death D 2 4 X 7 g GAS VENT TERMINATION ROOF PITCH MINIMUM HEIGHT FLAT TO 7 12 OVER 7 12 TO...

Страница 15: ...m As with all gas appliances using electrical power this furnace shall be connected into a permanently live electric circuit It is recommended that it be provided with a separate circuit protection de...

Страница 16: ...3 Rev 2 TWIN TWIN R1 R1 TWINNING CONNECTION DIAGRAM FOR TWINNING 1 STAGE FURNACES WITH SINGLE WIRE TWINNING FEATURE 1 STAGE HEATING ONLY THERMOSTAT 1 STAGE HEAT ONLY THERMOSTAT WITH FAN SWITCH FURNACE...

Страница 17: ...he gas valve for propane is 13 8 W C Mini mum pressure is 11 0 W C All gas fittings must be checked for leaks using a soapy solution before lighting the furnace DO NOT CHECK WITH AN OPEN FLAME The fol...

Страница 18: ...em 2 Attach a manifold pressure gauge with flexible tubing to the outlet pressure boss marked OUT P on White Rodgers gas valve model 36G or 36J See Figure 28 for White Rodgers gas valve model 36J See...

Страница 19: ...if orifice change is required Furnace input rate and temperature rise should be checked again after changing orifices to confirm the proper rate for the altitude Installations above 4 000 feet may req...

Страница 20: ...ty of the unit it must be checked out on initial start up by the installer To check for proper operation of the limit switches set the thermostat to a temperature higher than the indicated temperature...

Страница 21: ...ignition is not achieved it will lockout the furnace 3 POWER FAILURE If there is a power failure during a heating cycle the system will restart the ignition sequence automatically when power is resto...

Страница 22: ...22 18 CD19D7 22 Installer s Guide NOTES...

Страница 23: ...18 CD19D7 22 23 Installer s Guide NOTES...

Страница 24: ...distributor P I 08 02 Since the manufacturer has a policy of continuous product and product data improvement it reserves the right to change design and specifications without notice Literature Order N...

Отзывы: