SS-SVX002B-EN
7
Introduction
General
The CyberAir floor mounted, precision air conditioning
system unit will provide years of trouble-free service if
installed and maintained in accordance with this manual.
Damage to the unit from improper installation, operation
or maintenance is not covered by the warranty.
CyberAir systems are designed to be installed indoors
unless otherwise noted on the equipment.
Product Description
CyberAir systems are designed to be the most versatile
and flexible floor mounted air conditioning systems in the
industry. The unit is available in air-cooled, water-cooled or
glycol-cooled configurations and have up-flow or down
flow air patterns utilizing highly efficient, electronically
commutated (EC) fans. CyberAir systems are designed to
supply air to only one room.
CyberAir systems incorporate two cooling circuits with
highly reliable scroll compressors. They are designed to
operate with R-410A refrigerant. The cooling capacity, in
kW, will depend on the unit size which can range from 21
to 105 kW (1 kW = 3415 Btu/ h). Refer to the unit nameplate
to identify the model number and cooling capacity of your
unit.
Note:
CyberAir systems are strictly for non- residential
applications.
The functional modes of operation, in addition to cooling,
are heating, humidification, dehumidification which
provide complete environmental control of a conditioned
space.
There are two air flow pattern configurations, up-flow and
down-flow, and several cabinet sizes based on the type of
system and capacity. Regardless of configuration,
CyberAir systems are compact and versatile. See the
Installation drawing provided with your unit for the layout
and dimensions of the cabinet.
The CyberAir unit is provided with a factory mounted,
main power disconnect switch with a lockable handle. The
disconnect switch electrically isolates the unit during
routine maintenance. The system incorporates state of the
art component protection with the use of motor start
protectors or circuit breakers.
The advanced microprocessor controller is provided as a
standard for CyberAir systems. This controller provides
superior features for more comprehensive control of the
unit. These features include: full alarm system; input/
output monitoring status; full integrated control of
heating, cooling, humidification, and dehumidification;
multi-A/C unit control and remote communication with
building management systems.
The controller user interface display panel is typically
mounted on the front door of the A/C unit. It features a high
resolution touch screen display offering enhanced
graphical display capabilities and a round membrane type
keypad to navigate through the controller menus and
adjust operating parameters.
An operating manual for the controller is provided under
separate cover. Refer to that manual for detailed
instructions on operating the system controller.
Figure 1.
Touch Screen Display