Troubleshooting
SS-SVX002B-EN
45
Water- Water/Glycol Valve Fails to Open or Close
(cont.)
c. Actuator failed.
Replace actuator.
Electric Heater Inoperable
a. Circuit breaker tripped.
Check for short circuit; reset circuit breaker.
b. Temperature set point too low.
Increase temperature set point.
c. Overheat switch open.
Insufficient air flow across heater elements.
Check for dirty filters or obstructions that may
reduce air flow. Correct or replace as needed.
d. Manual reset overheat safety switch tripped.
Reset manual overheat safety switch (see item
immediately above).
e. Heater element burned out.
Check continuity with an ohmmeter Replace
heater element.
Hot Water Heater Inoperable
a. Low hot water flow.
Check hot water flow at supply source. Inspect
piping for leaks or obstructions.
b. Hot water supply temperature too low
Check hot water supply
c. Temperature set point too low
Increase temperature set point
d. Control power interrupted
Check for loose or broken wires
Table 7.
Troubleshooting (continued)
SYMPTOM
PROBABLE CAUSE
RECOMMENDATION