SSC-SVN001H-EN
9
Refrigerant Piping
Units should be interconnected pre-
ferably by copper pipes.
The Table 04 presents connection
sizes for Onix units and remote
TRCE/TRAE condensing units, as
well as liquid and suction piping si-
zes recommended for the intercon-
nection.
The equivalent lengths indicated al-
ready include losses due to valves,
curves, elbows, reductions, etc.
Maximum Distances
(Recommended)*
Distance between units:
46m
Difference between unit levels:
18m
(*) – Calculated distance, considering equivalent
length of connection elements.
Contact
Trane
for distances above
the recommended ones.
Refrigeration Piping
(Interconnection)
Instructions for Fixing the Expan
-
sion Valve Thermostatic Bulb
- In the suction line, as closest as
possible to the evaporator outlet.
- Before external equalization, in an
horizontal line run.
Tab. 04 - Connection and Pipe Sizes Recommended by Circuit.
Note: For equivalent lengths above the values indicated, please contact Trane or an authorized installer.
- The copper tube must be comple-
tely clean.
- At the 12h position for pipes smal-
ler than 7/8”, and 4h or 8h position
for 7/8” or larger pipes.
- Then insulate the pipes using ther-
mal sheets.
MOUNTING DIAGRAM
DRIER FILTER AND LIQUID SIGHT GLASS
CAUTION:
!
Do not operate the unit without
air filters.
MOUNTING DIAGRAM
DRIER FILTER
DRIER FILTER -
Ø1/2” AND Ø5/8” THREAD
WELDED DRIER FILTER
Ø5/8” Ø7/8” Ø1.1/8”
Welded filter Ø5/8”
only for CXPA 25
DRIER FILTER -
Ø1/2” AND 5/8” THREAD
LIQUID SIGHT GLASS
WITH HUMIDITY INDICATOR
WELDED DRIER FILTER
Ø5/8”Ø7/8”Ø1.1/8”
Welded filter Ø5/8”
only for CXPA 25
Connection Size (in.)
Equivalent Pipe Length
CXS Mod.
TRCE/TRAE
<12m
12~18m
18~24m
24~30m
30~36m
36~46m
Line(Ton)
Liq.
Suct.
Liq.
Suct.
Liq. Suct.
Liq.
Suct.
Liq.
Suct.
Liq.
Suct.
Liq.
Suct.
Liq.
Suct.
5
1/2
7/8
1/2
7/8
1/2
7/8
1/2
7/8
1/2
7/8
1/2
1-1/8
5/8
1-1/8
5/8
1-1/8
7,5
5/8
1-1/8
1/2
1-1/8
1/2
7/8
1/2
1-1/8
5/8
1-1/8
5/8
1-1/8
5/8
1-1/8
7/8
1-3/8
10
5/8
1-3/8
5/8
1-3/8
5/8
1-1/8
5/8
1-1/8
5/8
1-1/8
7/8
1-3/8
7/8
1-3/8
7/8
1-3/8
12,5
5/8
1-3/8
5/8
1-3/8
5/8
1-1/8
7/8
1-3/8
5/8
1-5/8
7/8
1-5/8
7/8
1-5/8
7/8
1-5/8
15
5/8
1-5/8
7/8
1-3/8
5/8
1-3/8
7/8
1-3/8
7/8
1-3/8
7/8
1-5/8
7/8
1-5/8
7/8
1-5/8
20
5/8
1-5/8
1 1/8
1-5/8
7/8
1-3/8
7/8
1-5/8
7/8
1-5/8
7/8
1-5/8
7/8
1-5/8
1-1/8
2-1/8
25
7/8
2-1/8
1 1/8
1-5/8
7/8
1-3/8
7/8
1-5/8
7/8
1-5/8
1-1/8
2-1/8
1-1/8
2-1/8
1-1/8
2-1/8
EXPANSION VALVE
EQUALIZATION
SUCTIONPIPE
ORSUCTIONHEADER
THERMAL BULB
INSULATION
BULB
EVAPORATOR
COIL
BULB FIXED AT 12H POSITION
FOR PIPES UP TO DIA. 3/4”
AND 4H POSITION OR 8H POSITION
FOR 7/8”-DIA. PIPES AND LARGER
12H
8H
4H
Содержание CXPA 050
Страница 27: ...SSC SVN001H EN 27 Fig 35 Dimensions Condensing Units TRAE 150 1 circuit TRAE Dimensional Data...
Страница 28: ...28 SSC SVN001H EN Fig 36 Dimensions Condensing Units TRAE 150 2 circuits TRAE Dimensional Data...
Страница 29: ...SSC SVN001H EN 29 Fig 37 Dimensions Condensing Units TRAE 200 1 Circuit TRAE Dimensional Data...
Страница 30: ...30 SSC SVN001H EN TRAE Dimensional Data Fig 38 Dimensions Condensing Units TRAE 200 2 Circuits...
Страница 31: ...SSC SVN001H EN 31 TRAE Dimensional Data Fig 39 Dimensions Condensing Units TRAE 250 1 Circuit...
Страница 32: ...32 SSC SVN001H EN TRAE Dimensional Data Fig 40 Dimensions Condensing Units TRAE 250 2 Circuits...