T-Series Climate Changer Air Handler IOM •
CLCH-SVX06A-EN
Installation - Electrical
To provide field-wiring to units with DDC or low limit controls:
•
If VFD or starter is not factory-mounted, provide 120 Vac power to a transformer in
the valve jack when a separate circuit is recommended (see
Figure 54
).
•
Install outside-air sensor and space sensor, if ordered.
•
For valve jack mounting and wiring detail, see
Figure 56
.
Quick Connects
The actuators, factory-mounted or field-supplied, are separately wired and controlled by
a direct-digital controller or other building logic.
Figure 57
illustrates the typical quick
connect scheme.
Figure 56.
Valve jack wiring details
Valve quick
connect
Conduit
assembly
Figure 57.
Typical quick connects with wiring identification
Actuator
Power 24 Vac
Sig. 0-10 Vdc
Signal to
slave actuator
Wire from
homerun cable