T-Series Climate Changer Air Handler IOM •
CLCH-SVX06A-EN
Installation - Piping
Steam Coil Piping
T-Series air handlers fitted with steam coils have labeled holes for piping penetrations.
Figure 38
and
Figure 39
illustrate typical steam coil piping configurations. See
Table 10
for the codes of system components in these figures.
The coil condensate return line must be piped full size of the condensate trap connection,
except for a short nipple screwed directly into the coil header’s condensate return
tapping. Do not bush or reduce the coil return tapping size.
Table 10. Code of system components for piping figures
Code
System component
FT
Float and thermostatic steam trap
GV
Gate valve
OV
Automatic two-position (ON-OFF) control valve
VB
Vacuum breaker
ST
Strainer
AV
Automatic or manual air vent
MV
Modulating control valve
Figure 38. Typical piping for Type N steam coils and
horizontal tubes for horizontal airflow
Figure 39. Typical piping for Type NS steam coils and
horizontal tubes for horizontal airflow
Pitch down
VB
VB
VB
Pitch down
Pitch down
Steam main
MV or OV
GV
ST
GV
GV
GV
ST
ST
ST
ST
Air
flow
FT
Return main
FT
FT
FT
12-in.
min
12-in.
min
12-in.
min
MV
Pitch down
Steam main
Full size of
coil connection
GV
GV
GV
Air flow
Return main
Full size of
steam trap
connection
ST
VB
VB
Full
size
of
main
12-in.
min.
ST
FT
FT
ST
ST
FT
12-in.
min.