53
Troubleshooting
25
CN13
Low pressure overrun
78
78
Switch off the compressor
of the system A. If this fault
occurs twice, switch off and
give an alarm.
26
CN14
Low pressure overrun 2
7A
7A
Switch off the compressor
of the system B. If this fault
occurs twice, switch off and
give an alarm.
27
TH4
、
TH9
Coil superheating
98
98
Switch off
2
28
TH7
The ambient temperature exceeds the
working range
87
87
Switch off
29
CN29
Communication fault between control panel
and centralized controller
ED
None
Switch off
3
30
CN4/XP1
Communication fault between single unit
controller and mainboard
EE
None
Switch off
Fault Code Table for Main Control Panel
Note: the faults in this table are only displayed on the single unit controller and the centralized
controller.
Note 1: when this fault occurs, switch off all compressors. The water pump will continuously
operate. Lock
“
antifreezing locking time of plate type heat exchanger for refrigeration
unit
”
. the fault is permitted to be manually reset only when the water outlet
temperature or the suction temperature is recovered to the normal state,
Note 2: for CXAJ065/045 unit, there are no TH8, TH9, TH10, TH11, CN14, IND3 and IND9 inputs
and relevant alarm codes.
Note 3: this alarm code will be displayed only when
“
module control
”
is selected.
Note 4: this alarm code will be displayed only when
“
module control
”
is selected and it is a
modular host unit.