23
Installation (Continued)
Field Installed Control Wiring
Before installing any connecting wiring, refer to Figure 3-2
for the electrical access locations provided on the unit. In-
stall appropriately sized control wiring for the 115 volt elec-
trical components as required by the application.
H A Z A R D O U S V O LTA G E !
DISCONNECT ALL ELECTRIC POWER INCLUDING
REMOTE DISCONNECTS BEFORE SERVICING.
Failure to disconnect power before servicing can
cause severe personal injury or death.
Since the unit-mounted 115V control power transformer
(1T1) is provided on all units, it is not necessary to run a
separate 115 volt control power source to the unit.
Note: 200/230 Volt units are shipped with
transformer 1T1 wired for 200 volt operation. If the
unit is to be operated on a 230 volt power supply,
rewire the transformer as shown on the unit
schematic.
When the 115 volt control circuit is properly connected to
the field provided interlock contacts 5K1 for circuit #1 and
5K2 for circuit #2 (if applicable), proper condenser fan cy-
cling and ambient control for the remaining fans is achieved
with corresponding compressor operation.
Note: All field wiring must conform to NEC
guidelines as well as state and local codes.
CCAD Package Chiller Interface
The Unit Control Module (UCM) within the Trane Model
CCAD package chiller is designed to control the CAUC con-
denser fan operation. To obtain proper condenser fan se-
quencing for the CCAD package chiller, several control wir-
ing modifications must be made to the CAUC units.
Refer to Figure 3-7 and the field wiring diagram in the
CCAD package chiller installation literature. Follow the ap-
propriate procedure below for the operating ambient appli-
cation when installing the 115 volt electrical wiring for the
CAUC unit.
Standard Ambient Operation
(Circuit #1 - 20 through 60 Ton Units)
1. Remove the jumper wire from between terminals 1TB2-3
and 1TB2-4 in the CAUC unit control panel.
2. Install a jumper between terminals 1TB3-3 and 1TB3-4 in
the CAUC control panel.
3. Install interconnecting wiring between the following termi-
nals:
CAUC Unit
CCAD Unit
1TB2-1
to
TB1-3 of 1U1A7
1TB2-4
to
TB1-2 of 1U1A7
1TB2-5
to
TB1-1 of 1U1A7
(Circuit #2 - 40 through 60 Ton Units)
4. Remove the jumper wire from between terminals 1TB2-8
and 1TB2-9 in the CAUC unit control panel.
5. Install a jumper between terminals 1TB3-8 and 1TB3-9 in
the CAUC control panel.
6. Install interconnecting wiring between the following termi-
nals:
CAUC Unit
CCAD Unit
1TB2-1
to
TB1-3 of 1U1A8
1TB2-9
to
TB1-2 of 1U1A8
1TB2-10
to
TB1-1 of 1U1A8
Low Ambient Operation
(Circuit #1 - 20 through 60 Ton Units)
1. Complete steps 1 through 3 of the previous standard am-
bient procedure for Circuit # 1.
2. Install an additional jumper between terminals 1TB3-6
and 1TB3-7 in the CAUC control panel.
(Circuit #2 - 40 through 60 Ton Units)
3. Complete steps 4 through 6 of the previous standard am-
bient procedure for Circuit #2.
4. Install an additional jumper between terminals 1TB3-11
and 1TB3-12 in the CAUC control panel.
5. Follow the low ambient damper adjustment procedure
listed in the "Low Ambient Damper" section before start-
ing the unit.
Содержание CAUC-C20
Страница 5: ...5 General Information Continued Unit Component Layout and Shipwith Locations 60 Ton Unit Illustrated...
Страница 8: ...8 Figure 3 2 CAUC C20 Unit Dimensional Data Recommended Clearances...
Страница 9: ...9 Figure 3 2 Continued CAUC C25 Unit Dimensional Data Recommended Clearances...
Страница 10: ...10 Figure 3 2 Continued CAUC C30 Unit Dimensional Data Recommended Clearances...
Страница 11: ...11 Figure 3 2 Continued CAUC C40 Unit Dimensional Data Recommended Clearances...
Страница 12: ...12 Figure 3 2 Continued CAUC C50 Unit Dimensional Data Recommended Clearances...
Страница 13: ...13 Figure 3 2 Continued CAUC C60 Unit Dimensional Data Recommended Clearances...
Страница 24: ...24 Figure 3 7 Typical Interface Connection Diagram for CCAD 20 through 60 Ton Package Chiller...
Страница 25: ...25...
Страница 33: ...33 Blank...
Страница 34: ...34 Figure 5 2 Typical Wiring Schematic for 20 through 60 Ton Units...
Страница 35: ...35...
Страница 36: ...36 Figure 5 3 Typical Control Panel Connections Diagram for 20 through 60 Ton Units...
Страница 37: ...37...
Страница 42: ...42...
Страница 43: ...43...
Страница 44: ...44...