Installation (Continued)
Table 3-3
Customer Connection Wire Range
Table 3-4
Unit Electrical Data
Allowable
Minimum
Maximum
Dual
Condenser Fan Motors
Unit
Rated
Voltage
Circuit
Fuse
Element
HP
FLA
LRA
KW
Size
Voltage
Range
Ampacity
Size
Fuse
Qty.
(Each) (Each) (Each) (Each)
200/230/60/3
180-220/208-254
9.2
15
15
2
1.0
4.1
20.7
0.9
C20
460/60/3
416-508
4.1
15
15
2
1.0
1.8
9.0
0.9
575/60/3
520-635
3.2
15
15
2
1.0
1.4
7.2
0.9
200/230/60/3
180-220/208-254
13.3
20
15
3
1.0
4.1
20.7
0.9
C25
460/60/3
416-508
5.9
15
15
3
1.0
1.8
9.0
0.9
575/60/3
520-635
4.6
15
15
3
1.0
1.4
7.2
0.9
200/230/60/3
180-220/208-254
13.3
20
15
3
1.0
4.1
20.7
0.9
C30
460/60/3
416-508
5.9
15
15
3
1.0
1.8
9.0
0.9
575/60/3
520-635
4.6
15
15
3
1.0
1.4
7.2
0.9
200/230/60/3
180-220/208-254
17.4
20
20
4
1.0
4.1
20.7
0.9
C40
460/60/3
416-508
7.7
15
15
4
1.0
1.8
9.0
0.9
575/60/3
520-635
6
15
15
4
1.0
1.4
7.2
0.9
200/230/60/3
180-220/208-254
25.6
30
30
6
1.0
4.1
20.7
0.9
C50
460/60/3
416-508
11.3
15
15
6
1.0
1.8
9.0
0.9
575/60/3
520-635
8.8
15
15
6
1.0
1.4
7.2
0.9
200/230/60/3
180-220/208-254
25.6
30
30
6
1.0
4.1
20.7
0.9
C60
460/60/3
416-508
11.3
15
15
6
1.0
1.8
9.0
0.9
575/60/3
520-635
8.8
15
15
6
1.0
1.4
7.2
0.9
Notes:
1. Electric information is for each individual motor.
2. Minimum Circuit Ampacity is 125% of the RLA of one motor plus the RLA of the remaining motors.
3. Maximum Fuse Size is 300% of the RLA of one motor plus the RLA of the remaining motors.
4. Recommended Dual Element Fuse Size is 225% of the RLA of one motor plus the RLA of the remaining motors.
5. RLA is rated in accordance with UL Standard 465.
6. Local codes may take precedence.
Содержание CAUC-C20
Страница 5: ...5 General Information Continued Unit Component Layout and Shipwith Locations 60 Ton Unit Illustrated...
Страница 8: ...8 Figure 3 2 CAUC C20 Unit Dimensional Data Recommended Clearances...
Страница 9: ...9 Figure 3 2 Continued CAUC C25 Unit Dimensional Data Recommended Clearances...
Страница 10: ...10 Figure 3 2 Continued CAUC C30 Unit Dimensional Data Recommended Clearances...
Страница 11: ...11 Figure 3 2 Continued CAUC C40 Unit Dimensional Data Recommended Clearances...
Страница 12: ...12 Figure 3 2 Continued CAUC C50 Unit Dimensional Data Recommended Clearances...
Страница 13: ...13 Figure 3 2 Continued CAUC C60 Unit Dimensional Data Recommended Clearances...
Страница 24: ...24 Figure 3 7 Typical Interface Connection Diagram for CCAD 20 through 60 Ton Package Chiller...
Страница 25: ...25...
Страница 33: ...33 Blank...
Страница 34: ...34 Figure 5 2 Typical Wiring Schematic for 20 through 60 Ton Units...
Страница 35: ...35...
Страница 36: ...36 Figure 5 3 Typical Control Panel Connections Diagram for 20 through 60 Ton Units...
Страница 37: ...37...
Страница 42: ...42...
Страница 43: ...43...
Страница 44: ...44...