BAYSTAT253A HUMIDITY CONTROL

69-1698

6

Pub.No.: 22-5203-01

Fig. 11. Wiring for variable-speed, 2-stage furnace (2H/1C) using 1H/1C thermostat.

OPERATION AND CHECKOUT

Place the system in operation and observe through at 
least one complete cycle to make certain that all 
components are functioning correctly.

FIELD WIRING DIAGRAM FOR VARIABLE SPEED 2 STAGE FURNACE

2 STAGE HEATING, 1 STAGE COOLING 

USING A 1 STAGE HEATING, 1 STAGE COOLING THERMOSTAT

(OUTDOOR SECTION WITHOUT TRANSFORMER)

7

6

9

5

5

THERMOSTAT

VARIABLE SPEED

2-STAGE FURNACE

W

G

B

Y

Y

Y/Y2

R

W2

BK

B/C

W1

G

O

B/C

R

W14

JUMPER 

M19853

YI/YLo

BK/2

BK/3

WH/1

BK

LH

BK

BK

FURNACE
JUNCTION
BOX

GROUND
SCREW

LN

WH

WH

HUM

TO 115 V 1 PH.,
60 HZ., POWER

SUPPLY PER

LOCAL CODES

FIELD ADDED JUMPER
W1 TO W2
2ND STAGE WILL FIRE
10 MINUTES AFTER 1ST.

EAC

1

BE SURE POWER AGREES WITH EQUIPMENT NAMEPLATE(S).

6

THIS WIRE IS ONLY FOR THERMOSTATS REQUIRING CONNECTION TO TRANSFORMER COMMON TERMINAL.

7

THE "Y" TERMINAL FROM THE THERMOSTAT MST BE WIRED TO THE "Y" TERMINAL OF THE FURNACE
CONTROL FOR PROPER BLOWER OPERATION DURING COOLING.

2

LOW VOLTAGE (24 V WIRING) TO BE NO. 18 A.W.G. MINIMUM.

3

GROUNDING OF EQUIPMENT MUST COMPLY WITH LOCAL CODES.

4

SET THERMOSTAT HEAT ANTICIPATOR PER UNIT WIRING DIAGRAM.

5

THESE LEADS PROVIDE 115 V POWER FOR CONNECTION OF ELECTRONIC AIR CLEANER AND HUMIDIFIER 
MAXIMUM LOAD 1.0 AMPS EACH.

8

SET DIP SWITCHES WITH POWER OFF PER INSTALLATION INSTRUCTIONS TO SET AIRFLOW AND 
INDOOR FAN OFF DELAYS.

9

OPTIONAL HUMIDITY CONTROL IS TO BE CONNECTED BETWEEN R AND BK. FACTORY INSTALLED JUMPER R TO BK
ON THE CIRCUIT  BOARD MUST BE CUT IF OPTIONAL HUMIDISTAT IS USED. THE JUMPER MUST ALSO BE
CUT WHEN APPLYING AN AIRFLOW COMMAND SIGNAL TO THE BK INPUT SUCH AS WITH THE VARIABLE 
SPEED, SINGLE-ZONE COMMAND SIGNAL TO THE BK INPUT SUCH AS WITH VARIABLE SPEED, SINGLE-ZONE
AND MULTI-ZONE SYSTEM CONTROLLERS. ON SINGLE SPEED COOLING, ONLY/NON-HEAT PUMP 
HUMIDISTAT. FOR TWO COMPRESSOR OR TWO SPEED SYSTEMS, JUMPER YLo TO O 

24 V

FACTORY WIRING

INTER-COMPONENT WIRING

LINE V

24 V
LINE V

FIELD WIRING

Содержание BAYSTAT253A

Страница 1: ...to your thermostat See Fig 2 However the humidity control can be mounted in any other convenient location in the living area or equipment room NOTE The humidity control electrical connections are not...

Страница 2: ...l case IMPORTANT Use 18 to 22 gauge wire for correct wiring Fig 4 Positioning return air duct template M19830 THERMOSTAT WALLPLATE MOUNTING TEMPLATE MOUNTING HOLES 2 WIRING HOLES FOR MOUNTING ON RIGHT...

Страница 3: ...ram for system with 2 speed fan motor Fig 7 Typical wiring diagram of current sensing relay with humidifier Fig 8 Typical wiring diagram of sail switch with humidifier Fig 9 Typical wiring diagram for...

Страница 4: ...mperature changes To reduce relative humidity reduce the setpoint approximately 3 RH humidity every 24 hours To increase relative humidity increase the setpoint approximately 3 RH every 24 hours Setpo...

Страница 5: ...air Fig 10 Wiring for variable speed air handler 5 6 SUPPL HTR CONTROL BOX 8 3 7 2 1 LOW VOLTAGE WIRING TO BE NO 18 A W G MINIMUM CONDUCTOR 2 WHEN HEATERS ARE USED DISCARD POWER LEADS WITH POLARIZED...

Страница 6: ...MON TERMINAL 7 THE Y TERMINAL FROM THE THERMOSTAT MST BE WIRED TO THE Y TERMINAL OF THE FURNACE CONTROL FOR PROPER BLOWER OPERATION DURING COOLING 2 LOW VOLTAGE 24 V WIRING TO BE NO 18 A W G MINIMUM 3...

Страница 7: ...BAYSTAT253A HUMIDITY CONTROL 7 69 1698 Pub No 22 5203 01...

Страница 8: ...69 1698 G H 11 03 For more information contact your local Dealer Distributor BAYSTAT253A HUMIDITY CONTROL Pub No 22 5203 01 American Standard Inc 6200 Troup Highway Tyler TX 75711 9010...

Отзывы: