INSTALLER'S GUIDE

18-HB13D7-5

BAYHTR -- HEATER DATA

Heater

Model No.

Number

of

Circuits

Phase

240 VOLT

208 VOLT

Capacity

Heater

Amps per 

Circuit

Capacity 

Heater

Amps per 

Circuit

KW   BTUH

KW   BTUH

BAYH++

1

1

4.80

16400

20

3.60

12300

17.3

BAYH++

1

1

7.68

26200

32

5.76

19700

27.7

BAYH++

1

1

9.60

32800

40

7.20

24600

34.6

BAYHTR3410 000

1

3

9.60

32800

34.6

7.20

24600

30

BAYHTR1415 BRK

2

1

15.36

52400

40/24

11.53

39300

34.6/20.8

BAYHTR3415 000

1

3

15.36

52400

38.2

11.53

39300

33.1

BAYHTR1419 BRK

2

1

19.20

65500

32/48

14.42

49200

27.7/41.6

BAYHTR1425 BRK

3

1

24.96

85200

44/40/20

18.73

63900

38.1/34.6/17.3

 +++ = 000, BRK, PDC
 000 = pigtails, BRK = contains Circuit Breakers, PDC = contains Pull Disconnect

8. Connect the female polarized plug (disconnected 

in item 2 from the wire bundle next to the knock-
outs) to the male polarized plug on the bottom of 
the heater control box

9. Refer to the heater minimum  airflow chart on the 

air handler rating nameplate for the appropriate 
minimum blower speed tap to be used with the 
approved heater installed.

10. For heaters with self contained disconnect, an 

opening in the blower access panel is provided 
so that the disconnect may be operated with-
out removal of the blower access panel.  Open 

the plastic "AirTite" disconnect cover in the 
front panel opening by loosening the screw on 
the cover door.  Cut out the fiberglass insula-
tion only in the area where the disconnect will 
extend through the opening.

11.  Replace  all  panels  removed  during  the  heater 

installation

IMPORTANT: The BAYHTR** electric heat accessory, de-

signed for use with this air handler, may include up to a 

combination of three 30 and / or 60 amp circuit breakers to 

provide an electrical disconnect for service personnel that 

is intended to help protect internal electrical components 

in the event of a short circuit or ground fault. As designed, 

the circuit breakers supplied in the BAYHTR* accessory do 

not provide over-current protection of the branch circuit. 

Therefore, the branch circuit(s) shall be sized and protected 

according to the unit nameplate.