background image

Page 12

INSTALLER'S GUIDE

Minimum Heating Airflow Settings

Section 7. Tables

 MODEL NO.

BAYEVAC04BK1

BAYEVAC04LG1

BAYEVAC05BK1

BAYEVAC05LG1

BAYEVAC08BK1

BAYEVAC08LG1

BAYEVAC10BK1

BAYEVAC10LG1

BAYEVAC10LG3

BAYEVCB15LG3

BAYEVBC15BK1

BAYEVBC20BK1

BAYEVCC25BK1

TAM8C0A24V21

638/713

638/900

675 

1

1

 /900

600/713

--

--

--

--

TAM8C0B30V21

723/808

723/1020

765/1020

680/808

765/1063

850/1105

--

--

TAM8C0C36V31

876/979

876/1236

927/1236

824/979

927/1288

1030/1339

1236/1442

--

TAM8C0C42V31

978/1093

978/1380

1035/1380

920/1093

1035/1438

1150/1495

1380/1610

--

TAM8C0C48V41

1063/1188

1063/1500

1125/1500

1000/1188

1125/1563

1250/1625

1500/1750

1625/1813

TAM8C0C60V51

1063/1188

1063/1500

1125/1500

1000/1188

1125/1563

1250/1625

1500/1750

1625 

1

1

 /1813

MINIMUM HEATER AIRFLOW CFM - HEATER MATRIX

WITHOUT HEAT PUMP / WITH HP

SEE AIR HANDLER NAMEPLATE FOR APPROVED COMBINATIONS

1

1

 Heater not qualified for 208V when installed in horizontal left position without Heat Pump

MODEL NO.

BAYEVAC04BK1

BAYEVAC04LG1

BAYEVAC05BK1

BAYEVAC05LG1

BAYEVAC08BK1

BAYEVAC08LG1

BAYEVAC10BK1

BAYEVAC10LG1

BAYEVAC10LG3

BAYEVCB15LG3

BAYEVBC15BK1

BAYEVBC20BK1

BAYEVCC25BK1

TAM7A0A24H21

638/713

638/900

675 

1

1

 /900

600/713

--

--

--

--

TAM7A0B30H21

723/808

723/1020

765/1020

680/808

765/1063

850/1105

--

--

TAM7A0C36H31

876/979

876/1236

927/1236

824/979

927/1288

1030/1339

1236/1442

--

TAM7A0C42H31

978/1093

978/1380

1035/1380

920/1093

1035/1438

1150/1495

1380/1610

--

TAM7A0C48H41

1063/1188

1063/1500

1125/1500

1000/1188

1125/1563

1250/1625

1500/1750

1625/1813

TAM7B0C60H51

1063/1188

1063/1500

1125/1500

1000/1188

1125/1563

1250/1625

1500/1750

1625 

1

1

 /1813

MINIMUM HEATER AIRFLOW CFM - HEATER MATRIX

WITHOUT HEAT PUMP / WITH HP

SEE AIR HANDLER NAMEPLATE FOR APPROVED COMBINATIONS

1

1

 Heater not qualified for 208V when installed in horizontal left position without Heat Pump

MODEL NO.

BAYEVAC04BK1

BAYEVAC04LG1

BAYEVAC05BK1

BAYEVAC05LG1

BAYEVAC08BK1

BAYEVAC08LG1

BAYEVAC10BK1

BAYEVAC10LG1

BAYEVAC10LG3

BAYEVCB15LG3

BAYEVBC15BK1

BAYEVBC20BK1

BAYEVCC25BK1

TAMGA0A24H21

638/713

638/900

675

1

1

 /900

600/713

--

--

--

--

TAMGA0C36H31

876/979

876/1236

927/1236

824/979

927/1288

1030/1339

1236/1442

--

TAMGA0C48H41

1063/1188

1063/1500

1125/1500

1000/1188

1125/1563

1250/1625

1500/1750

1625/1813

TAMGA0C60H51

1063/1188

1063/1500

1125/1500

1000/1188

1125/1563

1250/1625

1500/1750

1625

1

1

 /1813

MINIMUM HEATER AIRFLOW CFM - HEATER MATRIX

WITHOUT HEAT PUMP / WITH HP

SEE AIR HANDLER NAMEPLATE FOR APPROVED COMBINATIONS

1

1

 Heater not qualified for 208V when installed in horizontal left position without Heat Pump

Содержание BAYEVAC04BK1B

Страница 1: ...back grounds of electrical and mechanical experience Any attempt to repair a central air conditioning product may result in personal injury and or property damage The manufacturer or seller cannot be responsible for the interpretation of this information nor can it as sume any liability in connection with its use LIVE ELECTRICAL COMPONENTS During installation testing servicing and troubleshooting ...

Страница 2: ...ab and Screw In document pack Heater Element Terminations Wiring diagram not shown This electric heater accessory is designed to provide power directly to the air handler from the accessory heater s power supply eliminating the need for addi tional circuits The power and control wiring each use a single wire harness to connect the heater and the air handler 1 Check the unit heater label to confirm...

Страница 3: ...ulti poise 4 way M Product Tier Multi speed 7 Major Design Modifications Letter Sequence A No Descriptor Air Handler Coil 0 Size Footprint 17 5 x 21 5 A 21 0 x 21 5 B 23 5 x 21 5 C Cooling Size Air Handler AH Coil 1 000 BTU s 18 24 30 36 42 48 60 0 9 0 9 Electric Heat Input Electric Heat kW 05 08 10 15 20 25 0 9 0 9 Airflow Type Capability H Hi Effy Multi speed 1 5 nom Tonnage cfm ton H 1 5 Power ...

Страница 4: ...nimum Cabinet Width A B C A Maximum Cabinet Width A B C C Electric Heat Input Electric Heat kW 04 05 08 10 15 20 25 0 9 0 9 Connection Breaker B K Lugs L G Power Supply 208 230 1 60 1 200 1 50 A 208 230 3 60 3 Major Design Modifications Letter Sequence A Minor Design Modifications Letter Sequence A Unit Parts Identifier Letter Sequence A Record Your Heater Size _________ The heater in this example...

Страница 5: ...the cabinet size they match with for example the Filler Plate for cabinet B is marked B CAB 3 Tighten the Filler Plate screws loosened previously and add a screw provided to the bottom of each plate to hold Filler Plates in place Two Width Adjustment Brackets are located at the back of the heater assembly The heater comes sized for the smallest cabinet it will fit in For this example our heater fi...

Страница 6: ...be rotated in order to comply with National Electric Code NEC Section 240 81 The NEC requires that circuit breakers operated verti cally must be oriented so that the on position of the breaker is upward Field Connections ON Screw Screw Circuit Breaker Breaker Bracket Factory Connections Circuit Breaker Assembly STEP3 Attach Retainer Tabs and Edge Guard Note For A cabinet widths only the right side...

Страница 7: ...FLGA B or C Supply Duct Flange Kit install the kit before inserting the heater STEP 3 Insert heater assembly into heater compart ment 1 Move factory wiring out of the way and into the grooves provided in cabinet 2 Slide heater into heater compartment of air handler Section 6 Install Heater STEP 1 Remove Heater Compartment Panel Heater Compartment Panel Breaker Cover Pigtail Harness Wire Tie ...

Страница 8: ...d to secure the factory supplied conduit nut from the inside of heater compartment 2 Connect field supplied 3 4 or 1 1 2 conduit to conduit nut Note Reducing bushings may be required for your application Retainer Tab Filler Plate B and C only Conduit Entry Points STEP 5 Route High Voltage wiring to unit Select a conduit entry point Drill a hole for the desired conduit size on units without a plug ...

Страница 9: ...e is 45 in lbs Field wiring Factory wiring Ground Field wiring Factory wiring Ground Breaker Model LG lug Model Factory wiring Field wiring BLK BLK RED RED GREEN GREEN STEP 9 Install the seal plate Breaker models only 1 Place the seal plate over the breaker so the tab on the right side is in place 2 Snap on the left side of the seal plate that has the slot by the tab Place over breaker first Snap ...

Страница 10: ...UPPLY PER LOCAL CODE EL EC TR IC HE AT CO NT RO L LO W VO LT AG E WI RING T11 T12 T1 T2 T3 T4 T5 T6 T7 T8 T9 T10 EHC IN AIR HA ND LE R GR GR BK RD 3 1 HIG H VOL TAG E WIR ING IN AIR HAN DLE R MOD EL BAYE ABC2 0BK1 HEAT ER RATI NGS KW A MPS AT A B 240 VOLT S 208 VOLT S 4 80 20 4 80 20 3 6 1 7 3 3 6 17 3 C 4 80 20 3 6 1 7 3 CIRC UIT I CIRC UIT II 9 60 40 9 60 4 0 7 20 34 6 7 20 3 4 6 D 4 80 20 3 6 1...

Страница 11: ...I 9 60 40 9 60 40 7 20 34 6 7 20 3 4 6 D 4 80 20 3 6 1 7 3 TOTA L HEAT ER RATI NGS KW A MPS RD RD RD RD RD RD FE MA LE TER MIN ALS MA LE TER MIN ALS POL PLU G FEM ALE HO USI NG POL PLU G MA LE HO USI NG PD POW ER DIS CO NNE CT HTR HEA TER CTC O CYC LIN G TEM PER ATU RE LIM IT SW ITC H COL OR OF WIR E COL OR OF MAR KER BK BLA CK RD RED OR ORA NGE BR BRO WN YL YEL LOW PR PUR PLE BL BLU E WH WHI TE G...

Страница 12: ... 900 600 713 TAM7A0B30H21 723 808 723 1020 765 1020 680 808 765 1063 850 1105 TAM7A0C36H31 876 979 876 1236 927 1236 824 979 927 1288 1030 1339 1236 1442 TAM7A0C42H31 978 1093 978 1380 1035 1380 920 1093 1035 1438 1150 1495 1380 1610 TAM7A0C48H41 1063 1188 1063 1500 1125 1500 1000 1188 1125 1563 1250 1625 1500 1750 1625 1813 TAM7B0C60H51 1063 1188 1063 1500 1125 1500 1000 1188 1125 1563 1250 1625 ...

Страница 13: ...rect kw of the heater model for normal opera tion Heater Data Table 3 1 BAYEV HEATER DATA Heater Model No Number of Circuits 240 VOLT 208 VOLT Capacity Heater Amps per Circuit Capacity Heater Amps per Circuit kW BTUH kW BTUH BAYEVAC04BK1 1 3 84 13100 16 0 2 88 9800 13 8 BAYEVAC04LG1 1 3 84 13100 16 0 2 88 9800 13 8 BAYEVAC05BK1 1 4 80 16400 20 3 60 12300 17 3 BAYEVAC05LG1 1 4 80 16400 20 3 60 1230...

Страница 14: ...g or by the kW jumper position 3 The AFC sends a command to the serial communicating blower motor to run proper airflow and close the blower interlock relay on the EHC 4 As demand from the thermostat increases the EHC will communicate to the AFC the required airflow when ener gizing additional relays NOTE The EHC has lead lag or rotating logic built in that energizes the electric heat relays based...

Страница 15: ...Page 15 INSTALLER S GUIDE ...

Страница 16: ...pplications For more information please visit www trane com or www americanstandardair com The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice We are committed to using environmentally conscious print practices 2020 18 GJ09D1 10A EN 29 Apr 2020 Supersedes 18 GJ09D1 10 August 2014 ...

Отзывы: