Electrical Data
20
ACC-SVN67M-EN
Table 9. Air temperature rise 380/415 volt (50 Hz)
(a)
(Degrees °C)
(b)
(Degrees °F)
(c)
6 Ton
7.5 Ton
8.5 Ton
10 Ton
6 Ton
7.5 Ton
8.5 Ton
10 Ton
kW
Voltage
Stages
4100 M
3
/H 5100 M
3
/H 5800 M
3
/H
6800
M
3
/H
kW
Voltage
Stages
2400
cfm
3000
cfm
3400
cfm
4000
cfm
TSC072E
D
TSC090E
D
TSC102E
D
TSC120E
D
TSC072
ED
TSC090
ED
TSC102
ED
TSC120
ED
11.3/
13.5
380-
415/50/3
1
8.3/9.9
6.6/7.9
—
—
11.3/
13.5
380-
415/50/3
1
14.9/ 17.8 11.9/ 14.2
—
—
16.9/
20.2
380-
415/50/3
2
12.4/14.8
9.9/11.8
8.7/10.4
7.4/8.9
16.9/
20.2
380-
415/50/3
2
22.3/ 26.6 17.8/ 21.3 15.7/ 18.8 13.4/ 16.0
22.6/
26.9
380-
415/50/3
2
16.5/19.7
13.2/15.7
11.7/13.9
9.9/11.8
22.6/
26.9
380-
415/50/3
2
29.8/ 35.4 23.8/ 28.3 21.0/ 25.0 17.9/ 21.3
33.8/
40.4
380-
415/50/3
2
—
—
—
14.8 / 17.7
33.8/
40.4
380-
415/50/3
2
—
—
—
26.7/ 31.9
(a) For minimum design airflow, see performance table for each unit.
(b) To calculate the temperature rise in Celsius at different airflow, use the following formula: Temperature rise (
°
C) across electric heater = (kW x 2985)/(M3/H).
(c) To calculate the temperature rise in Fahrenheit at different airflow, use the following formula: Temperature rise (
°
F) across electric heater = (kW x 3414)/(1.08/H).
Table 10. Cooling only units with electric heater — single power source — 380/415 volt three phase (50 Hz)
Standard Indoor Fan Motor
Oversized Indoor Fan Motor
Unit Model
No.
Heater Model No.
Heater
(a)
kW
Rating
Heater
MBh
Control
Stages
MCA
Maximum Fuse
Size Or
Maximum
Circuit Breaker
MCA
Maximum Fuse
Size Or
Maximum Circuit
Breaker
TSC072ED
BAYHTRS418
11.3/13.5
39/47
1
26.9/28.9
35/35
28.1/30.1
35/35
BAYHTRS427
16.9/20.2
58/69
2
37.5/40.5
40/45
38.8/41.8
40/45
BAYHTRS436
22.6/26.9
78/92
2
48.3/52.1
50/60
49.5/53.4
50/60
TSC090ED
BAYHTRS418
11.3/13.5
39/47
1
28.1/30.1
35/35
30.3/32.3
35/35
BAYHTRS427
16.9/20.2
58/69
2
38.8/41.8
40/45
40.9/43.9
45/45
BAYHTRS436
22.6/26.9
78/92
2
49.5/53.4
50/60
51.6/55.5
60/60
TSC102ED
BAYHTRT427
16.9/20.2
58/69
2
38.8/41.8
40/45
40.9/43.9
45/45
BAYHTRT436
22.6/26.9
78/92
2
49.5/53.4
50/60
51.6/55.5
60/60
TSC120ED
BAYHTRT427
16.9/20.2
58/69
2
40.9/43.9
45/45
40.9/43.9
45/45
BAYHTRT436
22.6/26.9
78/92
2
51.6/55.5
60/60
51.6/55.5
60/60
BAYHTRT454
33.8/40.4
116/138
2
73.1/79.0
80/80
73.1/79.0
80/80
(a) kW and MBh shown for 380V/415V.
Table 11. Heat pump units with electric heater — single power source — 380/415 volt three phase (50 Hz)
Standard Indoor Fan Motor
Oversized Indoor Fan Motor
Unit Model No. Heater Model No.
Heater
(a)
kW
Rating
Heater
MBh
Control
Stages
MCA
Maximum Fuse
Size Or Maximum
Circuit Breaker
MCA
Maximum Fuse
Size Or Maximum
Circuit Breaker
WSC072ED
BAYHTRS418
11.3/13.5
39/47
1
43.4/45.4
50/50
44.4/46.4
50/50
BAYHTRS427
16.9/20.2
58/69
2
54.1/57.1
60/60
55.1/58.1
60/60
BAYHTRS436
22.6/26.9
78/92
2
64.8/68.7
70/70
65.8/69.7
70/70
WSC090ED
BAYHTRS418
11.3/13.5
39/47
1
46.3/48.3
50/50
48.0/50.0
50/50
BAYHTRS427
16.9/20.2
58/69
2
56.9/59.9
60/60
58.6/61.6
60/60
BAYHTRS436
22.6/26.9
78/92
2
67.7/71.6
70/70
69.4/73.3
70/70
WSC120ED
BAYHTRT427
16.9/20.2
58/69
2
63.3/66.3
70/70
—
—
BAYHTRT436
22.6/26.9
78/92
2
74.0/77.9
80/80
—
—
BAYHTRT454
33.9/40.4
116/138
2
95.5/101.4
100/110
—
—
(a) kW and MBh shown for 380V/415V.