Electrical Data
ACC-SVN67M-EN
19
10
THC120F4
BAYHTRD418*
18.0
1
32.5
35
—
—
10
THC120F4
BAYHTRD427*
27.0
2
46.0
50
—
—
10
THC120F4
BAYHTRD436*
36.0
2
59.5
60
—
—
10
THC120F4
BAYHTRD454*
54.0
2
70.4
80
—
—
10
TZC120F4
BAYHTRD418A
18
1
21.7
43
—
—
10
TZC120F4
BAYHTRD427A
27
2
32.5
60
—
—
10
TZC120F4
BAYHTRZ436A
36
2
43.3
77
—
—
10
TZC120F4
BAYHTRZ454A
54
2
65.0
91
—
—
575 Volts Three Phase
6
TZC072FW
BAYHTRAW18*
18
1
17.3
37
—
—
6
TZC072FW
BAYHTRAW36*
36
2
34.6
64
—
—
7.5
TZC090FW
BAYHTRAW18*
18
1
17.3
37
—
—
7.5
TZC090FW
BAYHTRAW36*
36
2
34.6
64
—
—
8.5
TZC102FW
BAYHTRAW18*
18
1
17.3
37
—
—
8.5
TZC102FW
BAYHTRAW36*
36
2
34.6
64
—
—
10
TZC120FW
BAYHTRBW18*
18
1
17.3
37
—
—
10
TZC120FW
BAYHTRZW36*
36
2
34.6
64
—
—
10
TZC120FW
BAYHTRZW54*
54
2
52.0
75
—
—
(a) Heater kW ratings are at 208V/240V for 208V/230V units, 480V for 460V units.
Table 7. Unit wiring with electric heat (single point connection) - high efficiency and eFlex™ - 6 to 10 tons (continued)
Standard Indoor Motor
Oversized Indoor Motor
Tons
Unit Model
Number
Heater Model
Number
Heater kW
Rating
(a)
Control
Stages
MCA
Max Fuse Size or
Max Circuit
Breaker
MCA
Max Fuse Size or
Max Circuit
Breaker
Table 8. Air temperature rise 380/415 volt (50 Hz)
(a)
(Degrees °C)
(b)
(Degrees °F)
(c)
6 Ton
7.5 Ton
10 Ton
6 Ton
7.5 Ton
10 Ton
kW
Voltage
Stages
4100
M
3
/H
5100
M
3
/H
6800
M
3
/H
kW
Voltage
Stages
2400
cfm
3000
cfm
4000
cfm
WSC072ED WSC090ED WSC120 ED
WSC072ED
WSC090E
D
WSC120E
D
11.3
380-415/50/3
1
8.3
6.6
—
11.3
380-415/50/3
1
14.9
11.9
—
12.5
380-415/50/3
1
9.1
7.3
—
12.5
380-415/50/3
1
16.5
13.2
—
13.5
380-415/50/3
1
9.9
7.9
—
13.5
380-415/50/3
1
17.8
14.2
—
16.9
380-415/50/3
2
12.4
9.9
7.4
16.9
380-415/50/3
2
22.3
17.8
13.4
18.8
380-415/50/3
2
13.8
11.0
8.3
18.8
380-415/50/3
2
24.8
19.8
14.9
20.2
380-415/50/3
2
14.8
11.8
8.9
20.2
380-415/50/3
2
26.6
21.3
16.0
22.6
380-415/50/3
2
16.5
13.2
9.9
22.6
380-415/50/3
2
29.8
23.8
17.9
25.0
380-415/50/3
2
18.3
14.6
11.0
25.0
380-415/50/3
2
32.9
26.3
19.8
26.9
380-415/50/3
2
19.7
15.7
11.8
26.9
380-415/50/3
2
35.4
28.3
21.3
33.9
380-415/50/3
2
—
—
14.9
33.9
380-415/50/3
2
—
—
26.8
37.5
380-415/50/3
2
—
—
16.5
37.5
380-415/50/3
2
—
—
29.6
40.4
380-415/50/3
2
—
—
17.7
40.4
380-415/50/3
2
—
—
31.9
(a) For minimum design airflow, see performance table for each unit.
(b) To calculate the temperature rise in Celsius at different airflow, use the following formula: Temperature rise (
°
C) across electric heater = (kW x 2985)/(M3/H).
(c) To calculate the temperature rise in Fahrenheit at different airflow, use the following formula: Temperature rise (
°
F) across electric heater = (kW x 3414)/(1.08/H).