Operating Pressures

Use the form on 

p. 29

 to log system and unit temperatures 

during start-up.

General:

 There are many variables (airflow, air temperatures) 

in an air conditioning system that will affect operating 
refrigerant pressures and temperatures. The chart below 

shows approximate conditions and is based on airflow at the 
rated SCFM, entering air at 80.6°F DB, 66.2 °F WB in cooling, 
68°F DB in heating. (+)Heating data with 35°F EWT is based 
on the use of an anti-freeze solution having a freezing point 20 
°F lower than the minimum expected entering temperature.

Table 17. Operating pressures 

Model

Entering 

Water Temp 

°F

Water Flow 

GPM

Operating Data

Cooling

Heating

Suction 

Pressure, 

PSIG

Discharge 

Pressure, 

PSIG

Water Temp 

Rise °F

Air Temp 

Drop °F DB

Suction 

Pressure 

PSIG

Discharge 

Pressure 

PSIG

Water Temp 

Drop °F

Air Temp 

Rise °F DB

GET*009

35 

1.80 

93-107

298-379

6-8

11-15

GET*009

35 

2.25 

96-111

300-382

5-6

12-15

GET*009

45 

1.80 

138-159

177-226

12-15

11-15

111-128

315-401

6-8

13-17

GET*009

45 

2.25 

137-157

171-217

9-12

12-15

114-131

316-403

5-7

14-18

GET*009

55 

1.80 

140-161

203-258

11-14

11-14

129-149

331-421

8-10

15-19

GET*009

55 

2.25 

139-160

197-250

9-12

12-15

133-153

332-423

6-8

16-20

GET*009

68 

1.80 

143-164

244-310

11-14

11-14

156-179

354-450

9-11

18-22

GET*009

68 

2.25 

142-164

237-301

9-11

12-15

161-185

357-454

7-9

18-23

GET*009

75 

1.80 

144-166

269-342

11-14

11-14

172-197

367-467

10-12

19-24

GET*009

75 

2.25 

144-165

262-333

9-11

11-15

177-204

372-473

8-10

19-25

GET*009

86 

1.80 

146-168

313-399

11-14

11-14

199-229

389-496

11-14

21-26

GET*009

86 

2.25 

146-168

306-389

8-11

11-15

206-237

394-501

9-12

21-27

GET*009

95 

1.80 

148-170

355-452

11-13

11-14

GET*009

95 

2.25 

147-170

347-441

8-11

11-14

GET*012

35 

2.40 

91-104

279-355

6-8

19-24

GET*012

35 

3.00 

94-108

281-358

4-6

19-24

GET*012

45 

2.40 

144-166

170-216

11-14

18-23

109-125

294-374

6-8

21-27

GET*012

45 

3.00 

144-166

164-208

9-11

19-24

111-128

295-375

5-6

21-27

GET*012

55 

2.40 

145-167

197-251

11-14

18-23

127-146

308-392

7-9

24-31

GET*012

55 

3.00 

145-167

191-243

9-11

18-23

130-149

311-396

6-7

25-31

GET*012

68 

2.40 

146-168

240-305

11-14

17-22

153-176

329-419

8-10

27-35

GET*012

68 

3.00 

146-168

233-296

9-11

18-23

158-181

332-423

7-9

28-36

GET*012

75 

2.40 

147-169

266-338

11-14

17-21

169-195

341-434

9-11

29-37

GET*012

75 

3.00 

146-169

259-329

9-11

17-22

174-200

345-438

7-9

29-37

GET*012

86 

2.40 

148-170

312-397

11-14

16-20

197-226

362-460

10-13

30-39

GET*012

86 

3.00 

148-170

304-387

9-11

16-21

203-234

365-465

8-10

31-39

GET*012

95 

2.40 

149-172

357-454

11-14

15-19

GET*012

95 

3.00 

149-172

348-443

9-11

15-19

GET*015

35 

2.80 

90-103

272-346

6-8

19-24

GET*015

35 

3.80 

94-108

275-350

4-6

19-24

GET*015

45 

2.80 

146-168

173-220

12-15

18-23

108-124

286-364

6-8

21-27

GET*015

45 

3.80 

145-167

165-210

9-11

19-24

111-128

288-367

5-6

21-27

GET*015

55 

2.80 

146-169

202-257

12-15

18-23

125-144

299-381

7-9

24-31

GET*015

55 

3.80 

146-168

193-245

9-11

18-23

130-149

302-385

6-7

25-31

GET*015

68 

2.80 

148-170

245-312

12-15

17-22

151-174

317-404

9-11

27-35

GET*015

68 

3.80 

147-170

235-299

9-11

18-23

157-181

321-409

7-9

28-36

GET*015

75 

2.80 

148-171

272-346

12-15

17-21

167-192

328-417

10-12

29-37

GET*015

75 

3.80 

148-171

261-332

9-11

17-22

174-200

333-423

7-9

29-37

Содержание Axiom GET024-036

Страница 1: ...uipment The installation starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly installed adjusted or...

Страница 2: ...that is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the app...

Страница 3: ...y of Trane and may not be used or reproduced in whole or in part without written permission Trane reserves the right to revise this publication at any time and to make changes to its content without o...

Страница 4: ...g Hinged Acoustic Door Assembly 16 Supply Air Ductwork 17 Chassis Installation 17 Supply Grille Installation 18 Cleaning and Flushing the Water Loop 18 Using Antifreeze 19 Low Voltage Wiring 19 Low Vo...

Страница 5: ...turn air door tamper resistant HEX 4 Hinged return air door with key lock Digit 17 Control Types C Tracer ZN510 controls D Deluxe 24V controls H UC400 B J UC400 B with Air Fi Wireless Communications D...

Страница 6: ...0 Open Digit 15 Supply Air Arrangement 0 Field cut supply air arrangement 1 Back and front supply air arrangement 2 Back and left supply air arrangement 3 Back and right supply air arrangement 4 Front...

Страница 7: ...tion around the compressor enclosure and vibration isolation between the chassis and cabinet An additional dampening treatment is applied around the compressor enclosure to achieve greater acoustical...

Страница 8: ...claims MAY NOT be accepted by the freight company Verify that the refrigerant charge has been retained during shipment by use of gauges Schrader taps are located external to the cabinet on the 3 ton e...

Страница 9: ...175 150 024 225 195 036 225 195 Chassis 009 88 78 012 107 97 015 112 102 018 117 107 024 174 164 036 190 180 Unit Location and Clearances Locate the unit in an indoor area The ambient temperature surr...

Страница 10: ...s and Weights with Standard Base Figure 2 GET009 036 Table 2 Dimensional data GET009 036 w standard base GET A inches B inches C inches D inches E inches F inches 009 012 16 16 8 1 8 39 1 8 14 015 018...

Страница 11: ...ET009 036 11 279 FOR 86 2184 CABINET HEIGHT 3 76 FOR 94 2388 CABINET HEIGHT 66 10 3 4 8 1 2 Table 3 Dimensional data GET009 036 with 6 inch extended base GET A inches B inches C inches D inches E inch...

Страница 12: ...1 8 54 5 8 Figure 4 Return air hinged acoustical door with standard base RETURN AIR OPENING FLANGE ON CABINET RETURN AIR OPENING FLANGE ON CABINET 2 X 4 STUD A B SHEET ROCK OPENING TOP VIEW SIDE VIEW...

Страница 13: ...024 036 27 1 8 54 5 8 Figure 5 Return air hinged acoustical door with 6 inches extended base RETURN AIR OPENING FLANGE ON CABINET RETURN AIR OPENING FLANGE ON CABINET 2 X 4 STUD A B SHEET ROCK OPENING...

Страница 14: ...t no power is present with a voltmeter WARNING Proper Field Wiring and Grounding Required Failure to follow code could result in death or serious injury All field wiring MUST be performed by qualified...

Страница 15: ...through the cabinet for piping with suitable material to help eliminate air leakage 11 See Cleaning and Flushing the Water Loop p 18 for system flushing Note Remove shipping straps from risers Water C...

Страница 16: ...of drywall to allow for frame mounting Units Utilizing Hinged Acoustic Door Assembly Figure 8 Mock up of stud placement 1 Locate the side studs a minimum of 1 inches and a maximum of 1 3 8 inches from...

Страница 17: ...r verifying that the air panel gasket is sealed to the coil secure the air panel to the door frame using the slots located on the sides of the air panel Figure 12 Secure to door frame 8 Install filter...

Страница 18: ...cabinet discharge opening Ensure there are no air gaps between the cabinet supply air and the grille This helps prevent recirculation of supply air into the return air opening behind the drywall 2 Se...

Страница 19: ...ing the cabinet assembly simply plug the male portion of thermostat zone sensor plug into the female portion of the plug located inside the unit s junction box 2 Mount the thermostat zone sensor or Tr...

Страница 20: ...to the unit Table 11 Lead change Lead Colors Lead Speed High Low Blower 1G 9A ECM CFM Settings To adjust the CFM disconnect the power to the unit Set the DIP switch located in the control box to the...

Страница 21: ...42 0 124 Low Yes 401 0 112 383 0 109 362 0 106 340 0 103 318 0 100 295 0 097 High No 418 0 125 400 0 122 379 0 120 356 0 117 332 0 113 309 0 110 Low No 304 345 0 097 331 0 095 313 0 092 292 0 090 GET0...

Страница 22: ...0 472 967 0 464 949 0 454 927 0 444 Model External Static Pressure in of wg Speed Tap Ducted Unit CFM 0 60 0 65 0 70 0 75 0 80 0 85 Max Min CFM KW CFM KW CFM KW CFM KW CFM KW CFM KW GET015 High Yes 64...

Страница 23: ...0 0 163 0 177 0 191 0 205 0 087 0 268 0 282 0 282 C 584 0 056 0 066 0 076 0 087 0 099 0 111 0 123 0 135 0 148 0 160 0 172 0 066 0 230 0 242 0 242 D 522 0 039 0 048 0 058 0 069 0 080 0 091 0 102 0 114...

Страница 24: ...208 60 1 8 5 7 9 36 0 0 60 1 2 10 48 15 230 60 1 8 5 7 9 36 0 0 60 1 2 10 48 15 265 60 1 7 0 6 4 30 0 0 60 1 2 8 60 15 GET018 FreeDischarge PSC Motor 208 60 1 10 3 9 6 42 0 0 70 1 8 12 70 20 230 60 1...

Страница 25: ...between the front air panel and the coil Initial Unit Start up Start up with deluxe controls is included below Notes Reference WSHP IOP 2 for Tracer ZN510 start up Reference BAS SVX065 EN for Tracer...

Страница 26: ...3 399 11 14 11 14 199 229 389 496 11 14 21 26 GET 009 86 2 25 146 168 306 389 8 11 11 15 206 237 394 501 9 12 21 27 GET 009 95 1 80 148 170 355 452 11 13 11 14 GET 009 95 2 25 147 170 347 441 8 11 11...

Страница 27: ...24 55 6 10 137 158 197 251 9 11 18 23 121 139 302 384 6 7 25 31 GET 024 68 4 70 139 160 246 313 11 14 17 22 142 164 318 405 8 11 27 35 GET 024 68 6 10 139 160 238 303 9 11 18 23 147 169 321 409 7 8 28...

Страница 28: ...0 16 7 The following table is provided for use in calculating glycol requirements for the unit Table 20 Water volume Unit Water Side Volume Cubic In Water Side Volume Cubic Ft Water Side Volume Gallon...

Страница 29: ...ilures complete the following checks and data entries before the system is put into full operation MODE Heat Cool Entering fluid temperature F F Leaving fluid temperature F F Temperature differential...

Страница 30: ...ell water it is important to check the cleanliness of the water to refrigerant heat exchanger Should it become contaminated with dirt and scaling as a result of bad water the heat exchanger will have...

Страница 31: ...such as leaking connection broken or disconnected wires etc If everything appears to be in order but the unit still fails to operate properly refer to the troubleshooting chart on p 32 General Operat...

Страница 32: ...icted thermal expansion valve Replace X X Defective reversing valve See WSHP IOM for touch test chart X X Thermostat improperly located Relocate X X Unit undersized Recalculate heat gains losses X X I...

Страница 33: ...OTROS TIPOS DE CONDUCTORES UTILICE NICAMENTE CONDUCTORES DE COBRE LAS TERMINALES DE LA UNIDAD NO EST N DISE ADAS SI NO LO HACE PUEDE OCASIONAR DA O AL EQUIPO 2309 7379 RCAP6047 4 29 15 5 11 09 LOWE G...

Страница 34: ...ES INTO MANUAL LOCKOUT MODE ISOLATED GENERAL ALARM CONTACTS CONTACTS CLOSE 11 52 22B 21A 26H 6 CONTACTS RATED FOR CLASS 2 24V TERMINAL AL1 AL2 L2 L1 M FIELD INSTALLED DEVICE 6 2B1S1 47A 46A 49A 48A B...

Страница 35: ...ADAS SI NO LO HACE PUEDE OCASIONAR DA O AL EQUIPO REV SHALL NOT BE COPIED OR ITS THIS DRAWING IS PROPRIETARY AND CONSENT OF THE TRANE COMPANY PARTIES WITHOUT THE WRITTEN CONTENTS DISCLOSED TO OUTSIDE...

Страница 36: ...IELD INSTALLED DEVICE 6 2B1S1 47A 46A 49A 48A B 1TB1 1 2 21 7 6 7 37 1TB1 CUSTOMER LOW V TERM BLOCK 6 7 8 53 54 55 56 57 58 59 60 2L1 J9 6 P9 6 J9 5 P9 5 44B 45B P9 1 J9 1 P9 2 J9 2 46B 47B P9 3 J9 3...

Страница 37: ...Figure 24 Tracer UC400 B with ECM Unit Wiring WSHP SVX10H EN 37...

Страница 38: ...Figure 25 Tracer UC400 B with PSC motor Unit Wiring 38 WSHP SVX10H EN...

Страница 39: ...shipment There is a standard five year compressor parts warranty Extended Warranty The optional extended warranty is a second through fifth year warranty The time starts at the end of standard 1 year...

Страница 40: ...are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial...

Отзывы: