WSHP-SVX01L-EN
11
Unit Dimensions and Weights
GEH and EXH Clearance Dimensions
Access to the unit for service purposes should be provided
at installation. All ½-5 tons and EXH070 configurations
(see
Figure 1, p. 11
) require an 18 in. (457 mm) surround
clearance from other mechanical and electrical equipment
(where shown) to enable panel removal from the unit for
service/maintenance ability. NEC requires 36 in. clearance
on the control panel side of the unit. Some local codes
require a greater service clearance than listed below.
Check all code requirements prior to unit installations.
Equipment containing a same-side supply/return
combination requires a 3 in. (229 mm) limitation on one
side. Access to the TXV may not be possible with this 3 in.
(229 mm) clearance. This configuration is typically applied
in a corridor installation, where space limitations force the
left or right side of the unit against a wall.
Service clearance dimensions for the GEH 6-15 tons
horizontal (see
Figure 2, p. 11
) includes a two side access
appropriate for control and blower motor/wheel access.
Some local codes require a greater service clearance than
listed below. Check all code requirements prior to unit
installations.
Figure 1.
GEH ½–5 tons and EXH 1½–6 tons clearance
LEFT RETURN
BACK SUPPLY
UNIT FRONT
LEFT RETURN
RI
G
HT SUPPLY
LEFT RETURN
LEFT SUPPLY
UNIT FRONT
UNIT FRONT
3"
(76)
18" (457)
(4-SIDES)
RI
G
HT RETURN
BACK SUPPLY
UNIT FRONT
RI
G
HT RETURN
LEFT SUPPLY
RI
G
HT RETURN
RI
G
HT SUPPLY
UNIT FRONT
UNIT FRONT
3"
(76)
18" (457)
(4-SIDES)
18" (457)
(4-SIDES)
18" (457)
(4-SIDES)
18" (457)
(3-SIDES)
18" (457)
(3-SIDES)
Figure 2.
GEH 6-15 tons clearance
TOP VIEW
36"
(
9
14)
SERVICE
CLEARANCE
20"
(508)
SERVICE
CLEARANCE
BLOWER ACCESS
PANEL
CON
T
ROL BO
X