Installation
60
WSHP-SVX01L-EN
2. Find the blower motor relay. The relay is located in
Figure 61, p. 60
. The relay location is consistent in all
control configurations.
Removing Speed-tap Wire
3.
For units w/o Hot Gas Reheat:
Remove undesired
speed-tap wire from 1K4 relay at spade 3. Wire tie the
lead, to eliminate a short.
4.
For units with Hot Gas Reheat:
Remove undesired
speed-tap wire from 1K8 relay at spade 6. Wire tie the
lead, to eliminate a short. Hot Gas Reheat requires both
speed taps to be adjusted to enable reheat as the lower
speed tap.
Connecting Desired Speed-tap Wire
5.
For units w/o Hot Gas Reheat:
Select desired speed-
tap wire. Connect desired speed tap wire to 1K4 relay
at spade 3.
6.
For units with Hot Gas Reheat
Select desired
speed-tap wire. Connect desired speed tap wire to 1K8
relay at spade 6.
7.
Install service front panel. Reconnect power to the unit.
Hole Plug Installation
1.
Locate two Hayco plastic plugs enclosed with the
Installation, Operation and Maintenance manual.
2. Use these plugs to plug the two shipping bolt holes in
the bottom of the GEVE/EVXVE units after shipping
bolt removal.
Figure 61.
Relay location
Figure 62.
Wiring change
Figure 63.
Connecting speed-tap wire
Table 38. 4-speed motor (115, 208, 230, 265)
Lead Colors
Lead Black
Blue
Orange
Red
Speed
High
Medium High
Medium Low
Low
Table 39. 3-speed motor (380, 415, 460)
Lead Colors
Lead Black
Blue
Orange
Speed
High
Medium Low
Note:
When using the medium or low speed tap, the purple wire must be
jumpered to the high speed tap (blk).
Table 40. 2-speed motor (575)
Lead Colors
Lead Black
Blue
Speed
High
Low
Figure 64.