WSHP-SVX014F-EN
41
Figure 40.
Step 10
11. Thread the valve’s wire lead through the low
voltage hole of the heat pump. Refer the figure
below.
Figure 41.
Step 11
12. Wire the valve to the terminal strip according to the
unit wire diagram located on the service control
panel.
RED = 1TB1-14
BLK = 1TB1-18
WHT = 1TB1-15
Figure 42.
Step 12
13. Bundle excess valve wire, and wire tie the bundle
neatly.
Figure 43.
Step 13
14. Install control side service panel.
15. Install the hanging isolation grommets (refer the
figure below) into the hanging brackets The unit
isolators were located in the return-air section of
the unit. See Step 2. Isolators for the economizing
package are located with the economizer.