ARTC-SVX006A-EN
61
13. Symptom: No low voltage (24 Vac)
Possible Causes
Potential Solutions
Transformer primary side fuse open
Check fuse prong contact points; Replace fuse
Transformer defective
Replace transformer
No primary voltage on transformer
Check breakers, fuses; Check power supply specifications
14. Symptom: Thermal Expansion valve superheat too high
Possible Causes
Potential Solutions
Water/glycol temperature too warm
Check setpoints; Check charge
Obstructed filter dryer
Replace dryer core
Low refrigerant charge
Recharge refrigerant as per data plate
Improper and not enough heat transfer at air coil
Check tube and fin surface; Check fan settings
Sensing bulb not properly located
Check if secured to pipe or insulated; Check sensor position on pipe
Defective or improper settings of EXV/TXV
Check EXV/TXV functions; Check EXV/TXV settings
15. Symptom: Thermal expansion valve superheat too low
Possible Causes
Potential Solutions
Sensing bulb not properly located
Check if secured to pipe or insulated; Check sensor position on pipe
Defective thermostatic element (TXV is cooling mode)
Replace power head
EXV/TXV valve superheat setting is too low or not functioning properly
Check EXV/TXV settings and functionality
16. Symptom: Contactor/relay inoperative
Possible Causes
Potential Solutions
Coil shorted or open
Replace coil
Mechanical parts broken or jammed
Replace assembly
Contacts pitted or burned
Replace contactors
No 24 Vac to coil
Replace secondary fuse to transformer; Check transformer
17. Symptom: Freeze protection safety activated
Possible Causes
Potential Solutions
Chiller setpoint is too low
Use a proper setpoint
Low water flow
Clean strainer; Check pump, VFD and differential pressure settings
Low suction pressure
See “low suction pressure”