54
ARTC-SVX006A-EN
Heat Pump Troubleshooting
General Approach to Fault
Isolation
Trane manufactures heat pump with embedded fault
detection and diagnostics in each module’s controller that
offers continuous dedicated monitoring to record and report
faults as they occur in real time allowing repairs to be
performed in a timely manner.
Various faults occurring in a building’s HVAC system can
lead to unnecessary energy consumption and poor thermal
comfort for a building’s occupants. Fault detection and
isolation plays a significant role in monitoring, maintaining,
and repairing heat pump to improve operator safety and
minimize operating costs.
Fault detection is recognizing that a problem has occurred,
even if the root cause is not yet known. Fault isolation is the
process of reducing potential causes to determine the most
likely source of heat pump failure.
Controller Diagnostic Codes
The following table assists in explaining the alarm codes
that appear in the remote interface panel in the event of an
alarm. The alarm history is accessed by pressing the alarm
log key.
Table 11.
Interface panel diagnostic code key
ALARM
RESET
ACTION
c.pCOe UI1 sensor failure
Auto
Shuts down Circuit 2 if Low Pressure sensor selected for Suction Pressure Alarm
c.pCOe UI2 sensor failure
Auto
Shuts down Circuit 2
c.pCOe UI9 sensor failure
Auto
Warning
c.pCOe UI10 sensor failure
Auto
Warning
c.pCOe Offline Alarm
Auto
Shuts down Circuit 2
c.pCOe wrong config Alarm
Auto
Warning
UI1 sensor failure
Auto
Shuts down circuit 1 if Low Pressure sensor selected for Suction Pressure Alarm
UI2 sensor failure
Auto
Shuts down Circuit 1
UI3 sensor failure
Auto
Shuts down local cooling control if Module is in Stand-alone Mode and
respective Entering / Leaving Water sensor selected for Temperature Control
UI3 sensor failure
Auto
Shuts down local heating control if Module is in Stand-alone Mode and
respective Entering / Leaving Water sensor selected for Temperature Control
UI4 sensor failure
Auto
Locks out module
UI4 sensor failure
Auto
Warning
UI5 sensor failure
Auto
Warning
UI6 sensor failure
Auto
Warning
UI7 sensor failure
Auto
Modules switch into Stand-alone Mode if both respective Cooling / Heating Mode
selected and respective Entering / Leaving Water sensor selected for
Temperature Control
UI8 sensor failure
Auto
Modules switch into Stand-alone Mode if both respective Cooling / Heating Mode
selected and respective Entering / Leaving Water sensor selected for
Temperature Control
UI11 sensor failure
Auto
Control panel heating / cooling control is disabled
UI12 sensor failure
Auto
Warning
Compressor 1 overload
User
Shutdown compressor 1
Compressor 2 overload
User
Shutdown compressor 2
EVD offline
Auto
Warning
EVD System Alarm
Auto
Warning
EVD Driver A Alarm
Auto
Warning