Condensate Drain Piping

- The drain hose should run straight

down the wall to a level where the
runoff will not stain the wall.

- There should be no traps.
- Avoid putting the end of the

hose in water.

- To conveniently drain the system,

the drain hose must slant
downward, with a slope of at least
1 : 50 to prevent leakage.
Figure 12 shows the unit in the
floor mounted position.

- When the drain hose is placed in

the room, insulate the hose with
foam polyethylene to avoid
damage to the ceiling or furniture.

Electrical Installation

All wiring and grounding must comply
with local electrical codes.

1. Wiring

Important Safeguards:
- Check the unit nameplate for

electrical rating. Be sure wiring
is done according to local
codes and wiring diagram.

- Connect electrical ground to all

units.

- Wiring should not touch

motors or moving parts.

- The manufacturer will accept no

responsibility for problems
caused by unauthorized
changes in the internal wiring.

- Pass the system wiring

through the PVC pipe conduit
or metal conduit, referred to
Unit Installation section.
(both power and control lines).

- Make sure all connections are

tight.

2. Electrical Connections

See Section: Wiring System
Diagram.

Note:

- All wiring must comply with

local codes.

- After completing the connections,

re-confirm them to be in
accordance with the unit and
system wiring diagrams.

Figure 12

Drain hose

Indoor unit

Slant

UNT-SVN009-EN.p65

9/9/09, 9:57 AM

7

Содержание AQUA NEW STYLUS CFEB 04 C0M1

Страница 1: ...Series 50 60 Hz 50 Hz Models Cooling Only CFEB 04 C0M1 CFEB 06 C0M1 CFEB 08 C0M1 CFEB 10 C0M1 CFEB 12 C0M1 CFEB 14 C0M1 CFEB 16 C0M1 CFEB 20 C0M1 60 Hz Models Cooling Only CFEB 04 C0M2 CFEB 06 C0M2 CF...

Страница 2: ...fy the dealer at the same time The unit should be totally inspected within 7 days of delivery If any concealed damage is discovered send a registered letter of protest to the carrier within 7 days of...

Страница 3: ...ation 5 Connection of Water Piping 6 Position of Piping Hole 6 Condensate Drain Piping 7 Electrical Installation 7 Remote Control Installation 8 Electronic Room Thermostat 9 Installation Typical Wirin...

Страница 4: ...be kept as short as possible Figure 1 6 Do not install unit in direct sunlight or near other heat sources as this may affect performance Do not allow outside air to directly enter unit or condensate...

Страница 5: ...nward 5 Pull air filters upward Figure 6 0 83 17 5 0 83 17 5 8 5 215 B A 6 Unscrew at the return grille Figure 7 7 Unscrew at the grille bottom hinges pull out the screw and unscrew at the side panel...

Страница 6: ...piping connections connect the female connections to the male adapter of the water piping connections at the inlet and outlet of the coil Then screw in and fasten the connections with an adjustable w...

Страница 7: ...iring Important Safeguards Check the unit nameplate for electrical rating Be sure wiring is done according to local codes and wiring diagram Connect electrical ground to all units Wiring should not to...

Страница 8: ...he remote control near heat sources or expose to the direct rays of the sun 2 Do not expose the control to the indoor unit s supply air stream 3 Do not place in a confined space 4 Attach the remote co...

Страница 9: ...ocated at or near the water drop or water mist Be careful not to leave any copper wire or piece of metal inside the control set Precaution This room thermostat is an electronic control device which re...

Страница 10: ...10 UNT SVN009 EN Typical Wiring Diagram WIRING DIAGRAM UNT SVN009 EN p65 9 9 09 9 57 AM 10...

Страница 11: ...11 UNT SVN009 EN Typical Wiring Diagram CFEB CHILLED WATER FANCOIL UNIT WITH WIRELESS CONTROL COOLING ONLY UNT SVN009 EN p65 9 9 09 9 57 AM 11...

Страница 12: ...12 UNT SVN009 EN CFEB CHILLED WATER FANCOIL UNIT WITH WIRED CONTROL COOLING ONLY Typical Wiring Diagram UNT SVN009 EN p65 9 9 09 9 57 AM 12...

Страница 13: ...0 0 59 627 1 24 71 A RUBBER ISOLATOR QTY C 254 3 10 02 359 1 14 15 74 2 2 93 234 3 9 23 RETURN AIR OUTLET CONNECTION INLET CONNECTION 610 7 24 06 123 1 215 0 143 6 DIMENSIONAL DATA 6 4 4 REV A 035 10...

Страница 14: ...6 RETURN AIR 234 3 9 23 74 2 2 93 OUTLET CONNECTION INLET CONNECTION 400 0 15 76 42 0 1 65 131 5 5 18 D 375 0 14 78 140 0 5 52 DIMENSIONAL DATA 8 8 REV B 035 1047 Sept 08 09 ECN NO 09114 09221 OUTLET...

Страница 15: ...15 UNT SVN009 EN Notes UNT SVN009 EN p65 9 9 09 9 57 AM 15...

Страница 16: ...Literature Order Number UNT SVN009 EN Date Sep 2009 Supersedes Apr 2008 Stocking Location Bangkok Thailand UNT SVN009 EN p65 9 9 09 9 57 AM 16...

Отзывы: