Installation
Required reprogramming of CH531 controls
Important:
For a chiller retrofitted with an AFDH drive to operate correctly and efficiently, it is
critical that the actual specific nameplate data values for the chiller be entered in the
CH531 menu parameters listed in the table below (i.e. motor data and compressor
impeller data). If the unit nameplate is missing, unreadable, or of a vintage that did
not include all of the required data categories, contact Trane Technical Services
through the toll-free Trane automated phone support system at 877-788-7263 and
use the menu code sequence of 4-2-7. Provide the support person with the chiller
serial number and request a copy of the shipped-with bill of materials for this unit.
Important:
Make sure your laptop is loaded with the most current version of TechView or
KestrelView software so that you have the most up-to-date version of CVR MP
firmware available to install into the DynaView.
Table 20. CH531 CVR firmware parameter settings with a retrofit AFDH
TechView Configuration View
CH531 Tab Parameter Name
Range
Default Setting
Recommended Setting
Starter type
Not Applicable
Wye-Delta
Non-Comm AFD
Impeller Diameter (CPIM)
210 - 335
275
Enter CPIM from Unit Nameplate
Compressor1: Number of stages
CVHE = 3, CVHF = 2
2
Enter from Unit Nameplate
Condenser Pressure Sensor
Installed, Not Installed
Not Installed
Installed
TechView Configuration View
Starter Tab Parameter Name
Range
Default Setting
Recommended Setting
Restart Inhibit Stop to Start Time
0 - 255 Seconds
30
30
Surge Protection
0 = Disable, 1 = Enable
1
1
Surge Sensitivity
0 - 100%
20
20
Restart Inhibit Stop to Start Time
(or Power Loss Reset Time)
0 - 255 Seconds
30
60
Stop Delay
1 - 30 Seconds
3
30
Unit Voltage
180 - 15000 Volts
460
Enter from Unit Nameplate
Voltage Transformer Ratio
0 - 700
20
Enter from Unit Nameplate
Rated Load Amps (RLA)
0 - 2500 Amps
500
Enter from Unit Nameplate
CT Meter Scale
0 - 2000
0
Choose Correct Scale from
Current Unbalance Trip Point
15 - 100%
30
30
Current Unbalance Grace Period
10 - 255 Seconds
90
90
Maximum Acceleration Time
6 - 64 Seconds
6
6
Acceleration Shutdown Action
Shutdown, Transition
Shutdown
Shutdown
Overload Type
Exponential, Linear
Linear
Linear
Phase Reversal
Enable, Disable
Enable
Disable
Contactor Integrity Test
Enable, Disable
Disable
Disable
Phase Reversal Grace Period
20 - 1000 milliseconds
700
1000
Surge Protection
Enable, Disable
Enable
Enable
Momentary Power Loss
Enable, Disable
Enable
Disable
Содержание AFDH
Страница 11: ...AFDH SVN01A EN 11 Nameplates Note This page has been intentionally left blank...
Страница 65: ...AFDH SVN01A EN 65 Installation Note This page intentionally left blank...
Страница 66: ...66 AFDH SVN01A EN Installation Note This page intentionally left blank...
Страница 67: ...AFDH SVN01A EN 67 Installation Note This page intentionally left blank...