Table 21. CT meter scales for TechView or Tracer TU
Required reprogramming of AdaptiView controls
Reprogramming retrofit AdaptiView controls (CVR firmware)
Important:
For a chiller retrofitted with an AFDH drive to operate correctly and efficiently, it is
critical that the actual specific nameplate data values for the chiller be entered in the
UC800 menu parameters listed in the table below (i.e. motor data and compressor
impeller data). If the unit nameplate is missing, unreadable, or of a vintage that did
not include all of the required data categories, contact Trane Technical Services
through the toll-free Trane automated phone support system at 877-788-7263 and
use the menu code sequence of 4-2-7. Provide the support person with the chiller
serial number and request a copy of the shipped-with bill of materials for this unit.
Important:
Make sure your laptop is loaded with the most current version of Tracer TU tool
software so that you have the most up-to-date version of CVR MP firmware available
to install into the UC800.
Note:
CVR MP firmware is always used in the UC800 on AdaptiView control systems or display
upgrades that were retrofitted in place of all earlier versions of chiller controllers with only
one specific exception - factory installed CH530 controls. Factory installed CH530 control
systems used CTV MP firmware so the new AdaptiView controls will also use CTV MP
firmware.
Actual Motor
RLA Amps (A)
X13580269
CT Extension
CT Ratio
(A:A)
CT Rating
(A)
CT Meter Scale
134 - 184
03
200:0.1
200
200
185 - 267
04
275:0.1
275
275
268 - 334
05
400:0.1
400
400
335 - 467
06
500:0.1
500
500
468 - 667
07
700:0.1
700
700
668 - 1000
08
1000:0.1
1000
1000
Содержание AFDH
Страница 11: ...AFDH SVN01A EN 11 Nameplates Note This page has been intentionally left blank...
Страница 65: ...AFDH SVN01A EN 65 Installation Note This page intentionally left blank...
Страница 66: ...66 AFDH SVN01A EN Installation Note This page intentionally left blank...
Страница 67: ...AFDH SVN01A EN 67 Installation Note This page intentionally left blank...