Trane ADD1B060A9H31B Скачать руководство пользователя страница 11

Installer’s Guide

18-CD21D1-12

    When the upflow furnace is installed in the hori-

zontal right or left application and a return duct 
is attached to the top side as shown in Figure 11, 
remove the filter from the furnace and install in a 
remote location.

    Do not install the filter in the return duct directly 

above the furnace in horizontal applications. 

    When the upflow furnace is installed in the hori-

zontal right or left application and a close coupled 

(less  than  36")  return  duct  is  attached  to  the  bot

-

tom side of the furnace as shown in Figure 11, se-

curely  attach  a  1/2"  mesh  metal  hardware  cloth 

protective screen to the inside bottom of the filter 
grill 

to prevent personal injury from contact-

ing moving parts when reaching into the re-
turn opening to replace the filter.

    Close coupled (less than 36") return (filter directly 

beneath bottom side return) is not recommended 
due to noise considerations.

 

    Downflow Furnaces: 

  Brackets  are  factory  sup

-

plied to mount filters in the return air duct work.

  8. Connect the duct work to the furnace. See Outline 

Drawing for supply and return duct size and loca-
tion. Flexible duct connectors are recommended 
to connect both supply and return air ducts to the 
furnace.

    If only the front of the furnace is accessible, it is 

recommended that both supply and return air ple-
nums are removable.

 9. 

The horizontal installation of the upflow fur-
nace requires an external filter section. Do 
NOT use the bottom return filter within the 
furnace. Filter kits are available for horizon-
tal applications.

 

 10. When replacing a furnace, old duct work should 

be cleaned out. Thin cloths should be placed over 
the registers and the furnace fan should be run for 
10 minutes. Don’t forget to remove the cloths be-
fore you start the furnace.

FILTER

REMOVE FILTER FROM UPFLOW 

FURNACE WHEN RETURN DUCT IS 

ATTACHED TO FURNACE TOP SIDE 

(HORIZONTAL LEFT OR RIGHT AP-

PLICATIONS) AS SHOWN.

Close coupled (less than 36")

 

return (filter directly beneath bottom 

side return) not recommended due to 

noise considerations. If used, securely 

attach 1/2" mesh metal hardware cloth 

protective screen to the inside bottom 

of filter grill.

q

*

SEE OUTLINE DRAWING

w

LOCATING

NOTCHES

PROVIDED

FOR SIDE

RETURN

CUTOUT

FRONT 

of Furnace

*

*

*

*

CUT OUT

FOR 

SIDE

FILTER

BOTTOM FILTER RACK INSTALLATION

Airflow

e

 11.  The bottom panel of the upflow furnace must be 

removed for bottom return air. After removing the 
filter, lay the furnace on its back.  Remove the two 

5/16" hex screws securing the front of the bottom 

channel to the cabinet. Rotate the channel down-
ward (or remove by lowering the front edge of the 
channel and pulling forward). Slide the bottom 
return air panel out of the cabinet.  Rotate the 
front channel to its original position and reinstall 

the two 5/16” screws.  

RETURN AIR FILTERS

TYPICAL UPFLOW RETURN AIR
FILTER INSTALLATIONS

These furnaces require high velocity type air filters.  
The filters may be installed within the furnace blower 

compartment  for  UPFLOW  furnaces  in  either  a  BOT

-

TOM or SIDE (left side or right side) return air inlet.  
Some filters may need to be trimmed for side or bottom 
filter use.

NOTE: 

For upflow 5 ton airflow models where the airflow 

requirement exceeds 1800 CFM -  Models will require 

return air openings and filters on: (1) both sides, or (2) 

one side and the bottom, or (3) just the bottom.

The furnace and the bottom filter rack, BAYRACK960,  

installation can be seen in Figure 13.

Содержание ADD1B060A9H31B

Страница 1: ...with this unit Please return to service information pack upon completion of work Installer s Guide UD1B100A9H31B UD1B100G9H31A UD1C100A9H51B UD1C100G9H51A UD1D120A9H51B UD1D120G9H51A UD1D140A9H51B UD1...

Страница 2: ...ate mark ing e 100 of the furnace combustion air requirement must come from outside the structure SAFETY SECTION CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each ap...

Страница 3: ...ty signal words are used to designate a degree or level of seriousness associated with a particular hazard The signal words for safety markings are WARNING and CAUTION a WARNING indicates a potentiall...

Страница 4: ...avoid physical damage from vehicles GENERAL INSTALLATION INSTRUCTIONS The manufacturer assumes no responsibility for equip ment installed in violation of any code or regulation It is recommended that...

Страница 5: ...D TUD1A040A9H21B TUD1A040G9H21A 14 1 2 9 5 8 13 1 4 13 TUD1B060A9H31B TUD1B060G9H31A TUD1B080A9H31B TUD1B080G9H31A TUD1B100A9H31B TUD1B100G9H31A 17 1 2 9 5 8 16 1 4 16 TUD1C080A9H41B TUD1C080G9H41A T...

Страница 6: ...6 18 CD21D1 12 Installer s Guide From Dwg 21C341700 Sh 1 Rev 0 DD1 HF OUTLINE DRAWING ALL DIMENSIONS ARE IN INCHES...

Страница 7: ...coil in the horizontal posi tion See Figure 4 IMPORTANT The 2 4TXC cased coil must be placed downstream of the furnace In horizontal installations the apex of the coil may point either toward or away...

Страница 8: ...ir open ings provided in the furnace casing must be kept free of obstructions which restrict the flow of air Airflow restrictions affect the efficiency and safe operation of the furnace Keep this in m...

Страница 9: ...rcial buildings Buildings with indoor pools Furnaces installed in commercial laundry rooms Furnaces installed in hobby or craft rooms Furnaces installed near chemical storage areas Exposure to the fol...

Страница 10: ...the space containing the furnace Minimum return air entering temperature for the furnace is 55 F Where there is no complete return duct system the re turn connection must be run full size from the fur...

Страница 11: ...Thin cloths should be placed over the registers and the furnace fan should be run for 10 minutes Don t forget to remove the cloths be fore you start the furnace FILTER REMOVE FILTER FROM UPFLOW FURNAC...

Страница 12: ...ACK960 The following checklist should be used when installing a right or left side return filter on an upflow furnace a Remove the filter b Leave the bottom panel in place c Make side cutout by follow...

Страница 13: ...stream of the fur nace See Figure 17 UPFLOW FILTER CLIP BRACKET INSTALLATION 1 Determine the location to be used The furnace cabinet has dimples for location of the alter nate furnace clips Side retur...

Страница 14: ...4 or the CAN CGA B149 Installation Codes and these instructions Determine that there is no blockage or restriction leakage corrosion and other deficiencies which could cause an unsafe condition 3 As f...

Страница 15: ...isions of ANSI Z21 47 and CAN CGA 2 3 standards Category I furnaces operate with a non positive vent static pressure and with a flue loss of not less than 17 percent NOTE If desired a side wall termin...

Страница 16: ...ATIONS d ELECTRICAL CONNECTIONS WARNING The cabinet must have an uninterrupted or unbroken ground according to National Electrical Code ANSI NFPA 70 latest edition and Canadian Electrical Code CSA C22...

Страница 17: ...SING A 1 STAGE HEATING THERMOSTAT NO COOLING From Dwg 21B341437 P01 OUTDOOR UNIT NO TRANSFORMER SEE NOTE 6 From Dwg B341436 Rev 1 SEE NOTE 8 FURNACE TWIN SEE NOTE 7 B C B C TO 115 V 1 PH 60 HZ POWER S...

Страница 18: ...PERATION OF UNIT NO 2 IS SYNCRONIZED WITH UNIT NO 1 VIA SIGNALS FROM TWIN CONNECTION SEE NOTE 4 SEE NOTE 3 ISOLATION RELAY FIELD SUPPLIED SEE NOTE 4 ISOLATION RELAY SEE NOTE 4 B C B C B C From Dwg 21B...

Страница 19: ...g by closing its individual manual shut off valve dur ing any pressure testing of the gas supply piping sys tem at test pressures equal to or less than 1 2 psig CAUTION Use a backup wrench on the gas...

Страница 20: ...from the utility company and compare to the nameplate rating This must not exceed the nameplate rating Gas Valve Adjustment Changes can be made by adjusting the manifold pres sure See Table 12 or cha...

Страница 21: ...the heating value obtained from the local utility supplier for the gas being delivered at the in stalled altitude Input rate changes can be made by adjusting the manifold pressure min 3 0 max 3 7 in...

Страница 22: ...is satisfied TO SHUT OFF For complete shutdown Move the control switch on the main gas valve to the OFF position See Figures 25 and 26 Disconnect the electrical supply to the unit CAUTION If this is d...

Страница 23: ...CONTROL AND SAFETY SWITCH ADJUSTMENT LIMIT SWITCH CHECK OUT The limit switch is a safety device designed to close the gas valve should the furnace become overheated Since proper operation of this swit...

Страница 24: ...g cycle the pressure switch will cause the gas valve to close and shut the unit down Carbon monoxide fire or smoke can cause serious bodi ly injury death and or property damage A variety of potential...

Отзывы: