Section 4. Setting the Unit
4.1 Pad Installation
When installing the unit on a support pad, such
as a concrete slab, consider the following:
• The pad should be at least 1” larger than the
unit on all sides.
• The pad must be separate from any structure.
• The pad must be level.
• The pad should be high enough above grade
to allow for drainage.
• The pad location must comply with National,
State, and Local codes.
Section 5. Refrigerant Line Considerations
5.1 Refrigerant Line and Service Valve Connection Sizes
Table 5.1
A4AC6018A
3/4
3/8
3/4
3/8
A4AC6024A
3/4
3/8
3/4
3/8
A4AC6030A
3/4
3/8
3/4
3/8
A4AC6031A
3/4
3/8
3/4
3/8
A4AC6036A
3/4
3/8
3/4
3/8
A4AC6037A
7/8
3/8
3/4
3/8
A4AC6042A
7/8
3/8
7/8
3/8
A4AC6048A
7/8
3/8
7/8
3/8
A4AC6060A
7/8
3/8
7/8
3/8
5.2 Factory Charge
The outdoor condensing units are factory
charged with the system charge required for the
outdoor condensing unit, ten (10) feet of tested
connecting line, and the smallest rated indoor
evaporative coil match. Always verify proper
system charge via subcooling (TXV/EEV) or
superheat (fixed orifice) per the unit nameplate.
TUBING INFORMATION
LINE TYPE
REFRIGERANT TO ADD AT SPECIFIED
ADDITIONAL LENGTH
Suction
Line
Liquid
Line
20 ft
30 ft
40 ft
50 ft
60 ft
3/4”
3/8"
3 oz
9 oz
15 oz
21 oz
27 oz
7/8"
3/8"
3 oz
9 oz
16 oz
22 oz
28 oz
Line Sizes
Service Valve Connection Sizes
Model
Vapor
Line
Liquid
Line
Vapor Line
Connection
Liquid Line
Connection
A4AC6036B
3/4
3/8
3/4
3/8
A4AC6037B
3/4
3/8
3/4
3/8
A4AC6042B
7/8
3/8
7/8
3/8
A4AC6060B
1-1/8
3/8
3/4
3/8
Содержание A4AC6018A1000A
Страница 24: ...24 88 A4AC6001 1F EN 3 1 2 4 Ton Units PRINTED FROM D158514P01 2 1 2 Ton Units Accumulator...
Страница 25: ...88 A4AC6001 1F EN 25 5 Ton Units PRINTED FROM D158515P01...
Страница 26: ...26 88 A4AC6001 1F EN Section 17 Wiring Diagrams 036B 060B Models 018A 048A Models...
Страница 27: ...88 A4AC6001 1F EN 27 036B 060B Models 018A 048A Models...
Страница 28: ...28 88 A4AC6001 1F EN 060A Models...
Страница 29: ...88 A4AC6001 1F EN 29 060A Models...