Section 2. Unit Location Considerations
2.1 Unit Dimensions and Weight
2.2 Refrigerant Piping Limits
1. The maximum length of refrigerant lines
from outdoor to indoor unit should NOT
exceed sixty (60) feet.
2. The maximum vertical change should not
exceed sixty (60) feet.
3. Service valve connection diameters are
shown in Table 5.1.
Note:
For line lengths greater than sixty (60)
feet, Refer to Refrigerant Piping Application
Guide, SS-APG006-EN or Refrigerant Piping
Software Program, 32-3312-03 (or latest revi-
sion).
When mounting the outdoor unit on a roof, be sure the roof will support the unit’s weight.
Properly selected isolation is recommended to alleviate sound or vibration transmission to the building structure.
D
W
H
60’
Max
Vertical
Change
Standard
Line Set
60’ Max
Line Length
60’
Max
Vertical
Change
A4AC6018A
29 x 30 x 33
161
A4AC6024A
29 x 30 x 33
162
A4AC6030A
37 x 30 x 33
184
A4AC6031A
33 x 30 x 33
156
A4AC6036A
37 x 34 x 37
212
A4AC6037A
37 x 34 x 37
212
A4AC6042A
45 x 34 x 37
252
A4AC6048A
45 x 34 x 37
256
A4AC6060A
45 x 34 x 37
272
* Weight values are estimated.
Unit Dimensions and Weight
Models
H x D x W (in)
Weight* (lb)
A4AC6036B
29 x 30 x 33
177
A4AC6037B
37 x 34 x 37
161
A4AC6042B
37 x 34 x 37
212
A4AC6060B
45 x 34 x 37
256
Содержание A4AC6018A1000A
Страница 24: ...24 88 A4AC6001 1F EN 3 1 2 4 Ton Units PRINTED FROM D158514P01 2 1 2 Ton Units Accumulator...
Страница 25: ...88 A4AC6001 1F EN 25 5 Ton Units PRINTED FROM D158515P01...
Страница 26: ...26 88 A4AC6001 1F EN Section 17 Wiring Diagrams 036B 060B Models 018A 048A Models...
Страница 27: ...88 A4AC6001 1F EN 27 036B 060B Models 018A 048A Models...
Страница 28: ...28 88 A4AC6001 1F EN 060A Models...
Страница 29: ...88 A4AC6001 1F EN 29 060A Models...