5.3.6 Group 6 Airflow Settings
MENU ITEM
OPTIONS [DEFAULT]
DESCRIPTION
Variable Speed Blower On Delay - Cooling
[No Delay],
1 Minute @ 50%; 7.5 Minutes @ 80%,
1 Minute @ 50%; 4 Minutes @ 80%,
7.5 Minutes @ 80%,
4 Minutes @ 80%,
1 Minute @ 50%,
30 Seconds
Select the blower on delay for cooling operation
Non Variable Speed Blower On Delay - Cooling
[No Delay],
15 Seconds, 30 Seconds
Select the blower on delay for cooling operation
Variable Speed Blower Off Delay - Cooling
[No Delay],
1.5 Minutes @ 100%,
45 Seconds @ 100%,
30 Seconds % 50%,
1.5 Minutes @ 50%,
3 Minutes @ 50%,
30 Seconds @ 35%
Select the blower off delay for cooling operation
Non Variable Speed Blower Off Delay - Cooling
[No Delay],
30 Seconds,
60 Seconds,
90 Seconds
Select the blower off delay for cooling operation
Variable Speed Blower On Delay - Compressor Heating
[No Delay],
1 Minute @ 50%; 7.5 Minutes @ 80%,
1 Minute @ 50%; 4 Minutes @ 80%,
7.5 Minutes @ 80%,
4 Minutes @ 80%,
1 Minute @ 50%,
30 Seconds
Select the blower on delay for compressor
heating operation
Non Variable Speed Blower On Delay - Compressor
Heating
[No Delay],
15 Seconds,
30 Seconds
Select the blower on delay for compressor
heating operation
Variable Speed Blower Off Delay - Compressor Heating
[No Delay],
1.5 Minutes @ 100%,
45 Seconds @ 100%,
30 Seconds % 50%,
1.5 Minutes @ 50%,
3 Minutes @ 50%,
30 Seconds @ 35%
Select the blower off delay for compressor
heating operation
Non Variable Speed Blower Off Delay - Compressor
Heating
[No Delay],
30 Seconds,
60 Seconds,
90 Seconds
Select the blower off delay for compressor
heating operation
Hydronic Heat Blower On Delay
[No Delay],
30 Seconds,
60 Seconds
Select the blower on delay for hydronic heating
operation
Hydronic Heat Blower Off Delay
[No Delay],
30 Seconds,
60 Seconds,
90 Seconds
Select the blower off delay for hydronic heating
operation
Compressor Low Stage Air Flow% - Compressor Cooling
35% - 60% [50%]
Select the 1st stage air flow for a two stage/two
compressor unit in cooling mode
Compressor Low Stage Air Flow% - Compressor Cooling
55% - [80%]
Select the 1st stage air flow for a two stage/
single compressor unit in cooling mode
Compressor Low Stage Air Flow% - Compressor Heating
35% - 60% [50%]
Select the 1st stage air flow for a two stage/two
compressor unit in heating mode
Compressor Low Stage Air Flow% - Compressor Heating
55% - [80%]
Select the 1st stage air flow for a two stage/
single compressor unit in heating mode