824 Programmable Comfort Control
18-HD72D1-1
page 23
5.3.4 Group 4 Accessories Settings
MENU ITEM
OPTIONS [DEFAULT] DESCRIPTION
Filtration Type Installed
Air Cleaner,
[Media Filter]
Select the filter type installed
Humidifier Installed
[None], Yes
Select whether a humidifier is installed
Humidifier - Select Relay Panel Aux Contact
[Aux 1], Aux 2
Select which set of Aux contacts is connected to the humidifier
Humidifier Type
[Powered/Bypass], Steam
Select what type of humidifier is installed
Humidifier Control
[RH Control], Frost Control
Select how the humidifier will be controlled (Outdoor temperature
sensor must be connected and enabled to allow this setting to be
selected)
Humidifier Fan Action
[Humidify with Active Heat
Call], Humidify without
Active Heat Call
Select when the humidifier is allowed to operate (Humidification is
disallowed during cooling mode or when the System Mode is Auto but
the last call was cooling)
Airflow During Humidifier Only Mode
35% - 100% [50%]
Select the desired airflow when the humidifier is operating without an
active call for heat
UV Light Installed
[None], Yes
Select whether a UV Light is installed
Dehumidifier Installed
[None], Yes
Select whether a ventilation system is installed
Dehumidifier - Select Relay Panel Aux
Contact
Aux 1, [Aux 2]
Select which set of aux contacts is controlling the ventilation system
Dehumidifier Control Options
[Stand Alone Operation],
With Active Call for Cooling
Only
Run System Fan with Dehumidifier Request
Yes, [No]
Outdoor Temperature Ventilation Override
[Disable], Enable
Select whether an outdoor temperature override is allowed (Outdoor
temperature sensor must be connected and enabled to allow this
setting to be selected)
Ventilation - Minimum Outdoor Temperature
*-10°F - 50°F [0°]
Select the minimum outdoor temperature that ventilation is allowed
Ventilation - Maximum Outdoor Temperature
80°F - 110°F [100°F]
Select the maximum outdoor temperature that ventilation is allowed
Minimum Ventilation Runtime
0 - 60 Minutes [5 Minutes]
Select the minimum runtime per hour for ventilation system
Acculate Overridden Runtime
[No], Yes
Select whether the overridden ventilation runtime will be made up
Acculate Period
[4 hours -recover
only when outdoor
conditions are favorable],
24 hours - recover
only when outdoor
conditions are favorable,
4 hours - recover as
need to meet minimum,
24 hours - recover as
needed to meet minimum
Select when to recover missed ventilation runtime due to outdoor
conditions exceeding the minimum/maximum outdoor temperate for
ventilation (The first two options will not meet AHRAE 62.2 standard for
minimum ventilation requirements)