Service Facts

Indoor Fan Performance 4YCY4036B

Down Airflow

Horizontal Airflow

4YCY4036 Heating Airflow, horizontal or downflow from .2 to .6" wg

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

Watts 162

173

197

226

256

285

313

343

383

440

525

CFM 1058 1062 1063 1063 1062 1060 1057 1053 1048 1042 1033

Watts 179

230

265

296

329

366

403

431

450

485

555

CFM 1179 1196 1204 1206 1205 1203 1199 1194 1185 1169 1144

Watts 318

336

365

399

435

469

502

533

563

-

-

CFM 1390 1376 1370 1366 1361 1354 1349 1351 1369

-

-

HIGH

External Static Pressure (in. wg)

LOW

MED*

4YCY4036-HOR

Motor Speed

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

Watts 169

182

210

243

273

301

331

370

433

480

530

CFM 1025 1062 1068 1063 1060 1061 1064 1055 1015 975

990

Watts 225

253

283

315

348

381

414

449

484

522

575

CFM 1187 1201 1203 1201 1198 1197 1194 1184 1157 1165 1150

Watts 339

357

390

424

455

483

516

571

669

-

-

CFM 1391 1377 1377 1375 1366 1352 1344 1360 1340

-

-

HIGH

External Static Pressure (in. wg)

LOW

MED*

4YCY4036-DOWN

Motor Speed

Selection

Low Stage High Stage

7-OFF

8-OFF

A

725

1000

7-ON

8-OFF

B

775

1075

7-OFF

8-ON

C

850

1150

7-ON

8-ON

D

925

1250

Selection

Low Stage High Stage

7-OFF

8-OFF

A

825

1100

7-ON

8-OFF

B

875

1175

7-OFF

8-ON

C

950

1275

7-ON

8-ON

D

1025

1375

* can be 1 or 3

4YCY4036 *075

4YCY4036 *096

Switch Settings

Nominal Airflow

Switch Settings

Nominal Airflow

* can be 1 or 3

*Factory Default Setting

Содержание 4YCY4036B-SF-1H

Страница 1: ...p Rise Min Max F Orifice Qty Drill Size Natural Gas POWER CONN V PH HZ Min Brch Cir Ampacity Fuse Size Max amps Fuse Size Recmd amps COMPRESSOR Volts Ph Hz R L Amps L R Amps OUTDOOR COIL TYPE Rows F P...

Страница 2: ...maintenance proceedures on the fan Operat ing the unit without the access panels properly installed may result in severe personal injury or death EXPLOSION HAZARD Propane gas is heavier than air and...

Страница 3: ...TE INDOOR WET BULB 2 FIND INTERSECTION OF OD TEMP ID W B 3 READ LIQUID 4 OR SUCTION 5 PRESSURE IN LEFT COLUMN EXAMPLE 1 OUTDOOR TEMP 82 F 2 INDOOR WET BULB 67 F 3 AT INTERSECTION ACTUAL 4 LIQUID PRESS...

Страница 4: ...4 Service Facts IMPORTANT Retain this wiring diagram please return this document to service information pack upon completion of work...

Страница 5: ...5 Service Facts IMPORTANT Retain this wiring diagram please return this document to service information pack upon completion of work...

Страница 6: ...ame as above 2nd stage heat has a 10 minute delay from the time of 1st stage ignition Comfort Control satisfied Safety Sequences Thisproductisequippedwithsafetydevicestoprotectagainst abnormal conditi...

Страница 7: ...0 5 0 6 0 7 0 8 0 9 1 Watts 169 182 210 243 273 301 331 370 433 480 530 CFM 1025 1062 1068 1063 1060 1061 1064 1055 1015 975 990 Watts 225 253 283 315 348 381 414 449 484 522 575 CFM 1187 1201 1203 1...

Страница 8: ...uid Line Temperature and Refrigerant Pres sure at service valves in the compressor compartment 4 Locate your liquid line temperature in the left column of the table and the intersecting liquid line pr...

Страница 9: ...9 Service Facts...

Страница 10: ...High Suction Pressure Too Low Liquid Refrigerant floodback TXV System Liquid Refrig floodback Cap Tube System I D Coil Frosting Compressor Runs Inadequate or No Cooling Compressor O D fan Do Not Start...

Страница 11: ...itch protection device open Steady ON Normal No Call for Heat 5 Flashes Flame sensed and gas valve not energized or flame sensed and no W signal 6 Flashes Flame Rollout Switch open 7 Flashes Thermosta...

Страница 12: ...Trane 6200 Troup Highway Tyler TX 75707 01 13...

Отзывы: