3

Installer’s Guide

F. FURNACE IN HORIZONTAL RIGHT POSITION 

CAUTION

!

Both the coil and furnace must be fully supported. Do not 

attempt to suspend the coil using the brackets.
Note: When installing onto an S-Series furnaces in horizontal 

right  or  downflow  configuration  the  flanges  will  be  bent 

downward for a flush fit. See Figure 5. 

CAUTION

!

To prevent damage to pan, ensure Heat Shield is assembled 

to Horizontal Drain Pan. See Figure 8.

 

IMPORTANT: 

The 4TXC cased coil must be placed downstream of the 

furnace. See Figure 6 for proper orientation.

1.  HORIZONTAL RIGHT COIL CONVERSION:  

While not required, optional removal of some coil 
components will maximize airflow efficiency. 
a.  Remove the coil by sliding the coil out of the coil  
     enclosure.  
b.  When present, remove the (2) outer water diverter  
     baffles. See Figure 2.

2.  Attach the coil and furnace in the orientation shown 

in Figure 6. For S-Series furnaces, bend flanges to 
accommodate installation as shown in Figure 5. For 
legacy upflow or horizontal furnaces, attach as shown in 
Figure 7. 

3.  There are self drilling screws included which can be used 

for this connection. Seal all gaps between the furnace and 
coil.

UPFLOW FURNACE IN 

HORIZONTAL RIGHT AIRFLOW POSITION

Airflo

w

 

CASED COIL

Figure 6

Figure 5

NOTE: 

For S-Series furnaces, bend outlet flanges inward 

or outward to suit installation. Coil and furnace will nest 
together.

Ensure Heat Shield is secure

on end of Horizontal Drain Pan

Figure 8

CASED

COIL

UPFLOW

FURNACE

TOP COIL FLANGE
FITS INSIDE OF

FURNACE

TOP FLANGE FOR

HORIZONTAL RIGHT
APPLICATION

UPFLOW

Figure 7

NOTE: 

For legacy upflow 

or horizontal furnaces in 
horizontal right.

Содержание 4TXCB004DS3HCC

Страница 1: ...an expose you to chemicals including lead which are known to the State of California to case cancer and birth defects or other reproductive harm For more information go to www P65Warnings ca gov A GEN...

Страница 2: ...out of the coil enclosure b Optional for maximum efficiency Remove the horizontal drain pan from the coil and discard 2 DOWNFLOW GASKET INSTALLATION OPTIONAL For unusually humid applications that expe...

Страница 3: ...out of the coil enclosure b When present remove the 2 outer water diverter baffles See Figure 2 2 Attach the coil and furnace in the orientation shown in Figure 6 For S Series furnaces bend flanges t...

Страница 4: ...l and slide back into the coil cabinet c Bend rear tab on top baffle inward towards the coil to avoid interference with splash guard See Figure 12 d Wedge flange of Splash Guard between Channel for Sp...

Страница 5: ...K CHECK 1 Using a manifold gauge connect an external supply of dry nitrogen to the gauge port on the liquid line 2 Pressurize the connecting lines and indoor coil to 150 PSIG maximum 3 Leak check braz...

Страница 6: ...refrigerant or condensate lines Once the outer doors are removed the inner coil panels can be easily removed The inside and outside of the coil can be easily cleaned withabrushandvacuumwiththepanelsr...

Страница 7: ...18 AD42D1 1B EN 7 Installer s Guide Outline Drawing for model 4TXCB004DS3HCC 4TXCD010DS3HCC From Dwg D346710 Rev A...

Страница 8: ...NO Is superheat 25F YES NO Is indoor temperature more than 85F NO Is sub cooling less than 8F YES Confirm that charge is correct and look for dirty or restricted outdoor coil Confirm that charge is co...

Страница 9: ...18 AD42D1 1B EN 9 Installer s Guide...

Страница 10: ...ications For more information please visit www trane com or www americanstandardair com The manufacturer has a policy of continuous data improvement and it reserves the right to change design and spec...

Отзывы: