background image

 18-AD42D1-1B-EN

Installer’s Guide

Is sub cooling at the

outdoor unit between

8 to 12F?

Troubleshooting Indoor TXV / Cooling Mode

NO

YES

Is superheat

< 5F?

YES

Correct air

flow

problem

Is air flow at least

350 CFM per ton?

YES

NO

Remove sensing bulb from the

suction line. Measure superheat

at indoor coil while holding the

bulb in bare hand for one minute.

Does superheat decrease?

Measure superheat at indoor coil

while placing the bulb in an ice

and water bath for one minute.

Does superheat increase?

YES

Replace the

TXV

TXV is OK

NO

Is superheat

< 25F?

YES

NO

Is indoor

temperature more

than 85F?

NO

Is sub cooling less

than 8F?

YES

Confirm that charge

is correct and look

for dirty or restricted

outdoor coil.

Confirm that

charge is

correct.

NO

Before starting

, insure the

blower wheel, indoor and outdoor

coils are clean.

Is the liquid line

temperature at indoor

coil within 8F of outdoor

liquid line temperature?

YES

Verify line set is

sized properly

for application

NO

The system is running at max

capacity and this may be

causing the High superheat.

Wait until indoor temperature

is less than 80F and check

superheat again.

YES

YES

Verify Inlet screen

of inlet tube

assembly is clear

of debris

NO

Verify Inlet screen

of inlet tube

assembly is clear

of debris

NO

Содержание 4TXCB004DS3HCC

Страница 1: ...an expose you to chemicals including lead which are known to the State of California to case cancer and birth defects or other reproductive harm For more information go to www P65Warnings ca gov A GEN...

Страница 2: ...out of the coil enclosure b Optional for maximum efficiency Remove the horizontal drain pan from the coil and discard 2 DOWNFLOW GASKET INSTALLATION OPTIONAL For unusually humid applications that expe...

Страница 3: ...out of the coil enclosure b When present remove the 2 outer water diverter baffles See Figure 2 2 Attach the coil and furnace in the orientation shown in Figure 6 For S Series furnaces bend flanges t...

Страница 4: ...l and slide back into the coil cabinet c Bend rear tab on top baffle inward towards the coil to avoid interference with splash guard See Figure 12 d Wedge flange of Splash Guard between Channel for Sp...

Страница 5: ...K CHECK 1 Using a manifold gauge connect an external supply of dry nitrogen to the gauge port on the liquid line 2 Pressurize the connecting lines and indoor coil to 150 PSIG maximum 3 Leak check braz...

Страница 6: ...refrigerant or condensate lines Once the outer doors are removed the inner coil panels can be easily removed The inside and outside of the coil can be easily cleaned withabrushandvacuumwiththepanelsr...

Страница 7: ...18 AD42D1 1B EN 7 Installer s Guide Outline Drawing for model 4TXCB004DS3HCC 4TXCD010DS3HCC From Dwg D346710 Rev A...

Страница 8: ...NO Is superheat 25F YES NO Is indoor temperature more than 85F NO Is sub cooling less than 8F YES Confirm that charge is correct and look for dirty or restricted outdoor coil Confirm that charge is co...

Страница 9: ...18 AD42D1 1B EN 9 Installer s Guide...

Страница 10: ...ications For more information please visit www trane com or www americanstandardair com The manufacturer has a policy of continuous data improvement and it reserves the right to change design and spec...

Отзывы: