background image

6

18-BC51D1-4

Installer’s Guide

SUBCOOLING CHARGING IN COOLING ABOVE 55°F OD AMBIENT

SUBCOOLING CHARGING BELOW 55°F OD AMBIENT – IN HEATING ONLY

The Trane company has always recommended installing
Trane approved matched indoor and outdoor systems.

All Trane split systems are ARI rated with only TXV indoor
systems.

The benefits of installing approved indoor and outdoor split
systems are maximum efficiency, optimum performance and
the best overall system reliability.

The following charging methods are therefore
prescribed for systems with indoor TXVs.

1. Subcooling (in the cooling mode) is the only

recommended method of charging above
55°F ambient temperatures.

2. For best results - the indoor temperature

should be kept between 70°F to 80°F. Add
system heat if needed.

3. At start-up, or whenever charge is removed

or added, the system must be operated for a
minimum twenty (20) minutes to stabilize
before accurate measurements can be made.

4. Measure Liquid Line Temperature and

Refrigerant Pressure at service valves.

5. Determine total refrigerant line length,

and height (lift) if indoor section is above
the condenser.

6. Determine the Design Subcool Charging

Temperature from the unit nameplate.

7. Locate this value in the appropriate column

of the Subcooling Charging Table. Locate
your liquid line temperature in the left
column of the table, and the intersecting
liquid line pressure under your nameplate
subcool value column. Add refrigerant to
raise the pressure to match the table, or

SUBCOOL CHARGING TABLE CORRECTIONS FOR LINE LENGTH AND RISE

60
50
40
30
25

Add 10 psig to Subcool Charging Table Pressure

20
15

Use Design Subcool Value from Table

10

0

Subtract 10 psig from S.C. Table Pressure

10

20

25

30

40

60

80

TOTAL REFRIGERANT LINE LENGTH  (FEET)

REFRIGERANT

LINE LIFT (FEET)

1. The Subcool Charging Method in cooling is not recom-

mended below 55°F outdoor ambient.

2. The only recommended method of charging at outdoor

ambients below 55°F, is to weigh in the charge in the
heating mode.

3. Use Nameplate charge plus standard charge adders for

line length.

4. Check liquid line temperature and pressure (at the

OD valves) to obtain a minimum of 10°F subcooling.

5. Add charge if a minimum of 10°F subcooling is not obtained

with the nameplate charge plus line length correction.

6. It is important to return in the spring or summer to

accurately charge the system in the cooling mode at
outdoor ambients above 55°F.

8

9

10

11

12

13

14

55

179

182

185

188

191

195

198

60

195

198

201

204

208

211

215

65

211

215

218

222

225

229

232

70

229

232

236

240

243

247

251

75

247

251

255

259

263

267

271

80

267

271

275

279

283

287

291

85

287

291

296

300

304

309

313

90

309

313

318

322

327

331

336

95

331

336

341

346

351

355

360

100

355

360

365

370

376

381

386

105

381

386

391

396

402

407

413

110

407

413

418

424

429

435

441

115

435

441

446

452

458

464

470

120

464

470

476

482

488

495

501

125

495

501

507

514

520

527

533

R-410A REFRIGERANT CHARGING CHART

Refer to Service Facts or 

Installer's Guide for charging method. 

LIQUID

TEMP

(

˚

F) 

DESIGN SUBCOOLING (

˚

F)

LIQUID GAGE PRESSURE (PSI)

From Dwg. D154557P01 Rev. 2

remove refrigerant to lower the pressure. Again, wait
twenty (20) minutes for the system conditions to stabilize
before adjusting charge again.

8. When system is correctly charged, you can refer to

System Pressure Curves (in Service Facts) to verify
typical performance.

Содержание 4TWR3

Страница 1: ...use by individuals posses sing adequate backgrounds of electrical and mechanical experience Any attempt to repair a central air conditioning product may result in personal injury and or property dama...

Страница 2: ...should not exceed sixty 60 feet liquid line 8 Locate and install indoor coil or air handler in accordance with instruction included with that unit C INSTALLING REFRIGERANT LINES CAUTION If using exist...

Страница 3: ...indoor units is completed the field brazed connections must be checked for leaks Pressurize through the service valve ports the indoor unit and field refrigerant lines with dry nitrogen to 350 400 ps...

Страница 4: ...te and relative capacity of the heat pump system By measuring the change in delta T we can determine the need for defrost The coil sensor also serves to sense outdoor coil temperature for termination...

Страница 5: ...E W IR IN G C O M P R E S S O R IO L R U N C A P A C IT O R S T A R T C A P A C IT O R S T A R T R E L A Y C O N T A C T O R C O N T A C T S L O W V O L T A G E W IR IN G C O N T R O L T R A N S F O R...

Страница 6: ...Subcool Charging Table Pressure 20 15 Use Design Subcool Value from Table 10 0 Subtract 10 psig from S C Table Pressure 10 20 25 30 40 60 80 TOTAL REFRIGERANT LINE LENGTH FEET REFRIGERANT LINE LIFT FE...

Страница 7: ...946 37 1 4 870 34 1 4 7 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 508 20 4TWR3060A 4 1 1045 41 1 8 946 37 1 4 870 34 1 4 7 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 508 20 4TWR4018A 3 1 933 36 3 4 829 32...

Страница 8: ...nry been sealed If mortar is used prevent mortar from coming into direct contact with copper tubing 5 Verify tightness of all electrical connects 6 Observe outdoor fan during on cycle for clearance an...

Отзывы: