18-AC108D1-1D-EN
21
STEP 9
- Record System Information for refer-
ence.
Record system pressures and temperatures
after charging is complete.
Outdoor model number = _________________
Measured Outdoor Ambient = __________ º F
Measured Indoor Ambient = __________ º F
Measured Liquid Line Temp = __________ º F
The Subcooling Charging method in cooling is
not
recommended below 55º F outdoor temperature.
The recommended method of charging at outdoor temperatures below 55º F is weighing in the charge. Return
when weather conditions permit charge verification through subcooling.
STEP 1
- Determine additional charge.
Note
:
The nameplate charge value represents
the amount of refrigerant shipped in the outdoor
unit and is compatible with 10 feet of AHRI rated
refrigerant lines and the smallest AHRI rated
coil.
Using the method below, find the charge associ-
ated with the additional length of tubing above
10 ft. and record it below.
14.3 Subcooling Charging Below 55º F Outdoor Temp.
Measured Suction Line Temp = __________ º F
Liquid Gage Pressure = __________ PSIG
Suction Gage Pressure = __________ PSIG
Calculating Charge Using the Weigh-In Method
1)
Measure in feet the distance between the
outdoor unit and the indoor unit. (Include
the entire length of the line from the service
valve to the IDU.) Subtract 10 ft from this
entire length and record on line 1.
2)
Enter the charge multiplier (0.6 oz/ft). Each
linear foot of interconnecting tubing requires
the addition of 0.6 oz of refrigerant.
3)
Multiply the total length of refrigerant tubing
(Line 1) times the value on Step 2. Record
the result on Line 3 of the Worksheet.
4)
This is the amount of refrigerant to weigh-in
prior to opening the service valves.
1. Total Line length (ft) – 10 ft ______________
2. Charge multiplier
x ___0.6 oz _____
3. Step 1 x Step 2
= _____________
4. Refrigerant (oz)
=
_____________
Weigh-In Method can be used for the initial
installation, or anytime a system charge is being
replaced. Weigh-In Method can also be used
when power is not available to the equipment
site or operating conditions (indoor/outdoor
temperatures) are not in range to verify with the
subcooling charging method.
Содержание 4TTA4
Страница 24: ...24 18 AC108D1 1D EN 3 5 4 Ton Units PRINTED FROM D158514P01 5 Ton Units PRINTED FROM D158515P01...
Страница 25: ...18 AC108D1 1D EN 25 Section 17 Wiring Diagrams 036A3 042A3 048A3 060A3 Models...
Страница 26: ...26 18 AC108D1 1D EN 036A3 042A3 048A3 060A3 Models...
Страница 27: ...18 AC108D1 1D EN 27 036A4 042A4 048A4 060A4 Models...
Страница 28: ...28 18 AC108D1 1D EN 036A4 042A4 048A4 060A4 Models...