Trane 4TEE3F31B1000B Скачать руководство пользователя страница 16

Trane
6200 Troup Highway
Tyler, TX 75707
www.trane.com

05/10

The manufacturer has a policy of continuous product and product data

improvement, and it reserves the right to change design and specifications

without notice.

The following warning complies with State of California law, Proposition 65.

 ▲

WARNING:

 

This product contains

fiberglass wool insulation! 

Fiberglass dust and ceramic

fibers are believed by the State of California to cause
cancer through inhalation. Glasswool fibers may also 
cause respiratory, skin, or eye irritation.

PRECAUTIONARY MEASURES 

 

 Avoid breathing fiberglass dust.

  Use a NIOSH approved dust/mist respirator.

  Avoid contact with the skin or eyes. Wear long-

    sleeved, loose-fitting clothing, gloves, and eye
    protection.

  Wash clothes separately from other clothing: rinse

    washer thoroughly.

  Operations such as sawing, blowing, tear-out, and

    spraying may generate fiber concentrations requiring
    additional respiratory protection. Use the appropriate
    NIOSH approved respirator in these situations.

FIRST AID MEASURES

Eye Contact     -   

 Flush eyes with water to remove dust.

                               If symptoms persist, seek medical
                               attention.

Skin Contact   -    

Wash affected areas gently with soap

                              and warm water after handling. 

     

SUPPLEMENTARY HEATERS CHECKOUT PROCEDURES,

IF USED DOES HEATER REQUIRE A SPECIAL CIRCUIT?

SEE “LIMITATIONS AND RECOMMENDATIONS”

1. Be sure the disconnect switch is “OFF”, and safety label (if any) is attached ............................... [ ]

2. Check on field wiring for tight connections and grounding according to codes ............................ [ ]

3. Check circuit protection for proper size per nameplate specifications .......................................... [ ]

4. Check control box panel — in place and secured ........................................................................... [ ]

NOTE: OPERATION OF HEATERS MUST BE CHECKED DURING THE OPERATION CHECK OF THE
TOTAL SYSTEM.

J.  CHECKOUT PROCEDURES

After installation has been completed, it is recommended that the Air Handler be checked against the following
checklist.

1.

Make sure power is “OFF” at power disconnect

switch ........................................................................... [ ]

2.

Check all field wiring for tight connections.

See that grounding of unit is in accord with code ..... [ ]

3.

Make sure unit suspension (if used) is secure

and that there are no tools or loose debris in,
around or on top of the unit ....................................... [ ]

4.

Check all duct outlets; they must be open

and unrestricted .......................................................... [ ]

5.

Check drain lines and be sure all joints are tight [ ]

6.

Make sure secondary drain pan is installed ....... [ ]

7.

Check power supply for correct requirements

per unit nameplate .................................................... [ ]

8.

Check filters for proper size. Inform owner of

proper procedure for removal and reinstallation ...... [ ]

9.

Energize the system and carefully observe

its operation; make any necessary adjustment ........ [ ]

10. Instruct owner, engineer (if possible) on proper
operating procedure and leave Use and Care
Manual with owner .................................................... [ ]

WARNING

!

ELECTRICAL SHOCK HAZARD
LOCK UNIT DISCONNECT SWITCH IN OPEN POSITION
BEFORE SERVICING UNIT.  FAILURE TO FOLLOW THIS
WARNING COULD RESULT IN PROPERTY DAMAGE,
PERSONAL INJURY, OR DEATH.

Содержание 4TEE3F31B1000B

Страница 1: ...ct your local distributor or the manufacturer as listed on the air handler nameplate These air handlers are shipped from the factory in the upflow or horizontal right configuration and are fully convertible to downflow or horizontal left Refer to Sec tion C beginning on page 4 for additional information INSPECTION Check carefully for any shipping damage This must be reported to and claims made aga...

Страница 2: ...the air handler must be made to allow access for refrigerant lines or attach refrigerant lines to air handler when installing This area may also be used for other purposes includ ing an electric hot water heater but in no case shall a fossil fuel device be installed and or operated in the same closet alcove or utility room In addition these air handlers are suitable for installa tion in an attic g...

Страница 3: ...structions These should only be installed on the supply air side of the system Atomizing style humidifiers are not recommended with the use of this unit C UNIT INSTALLATION UPFLOW a For maximum efficiency the horizontal drip tray should be removed See Figures 5 6 and 7 B Two Piece Cabinet Disassembly OPTIONAL NOTE For easier installation into tight areas the 4 and 5 ton air handlers can be disasse...

Страница 4: ...to support the total weight must be pro vided Provide a minimum height of 14 inches for proper unrestricted airflow d If a return air duct is connected to the air han dler it must be the same dimensions as shown in the outline drawing on page 13 e Pedestal and unit should be isolated from the foundation using a suitable isolating material f Openings where field wiring enters the cabinet must be co...

Страница 5: ...and isolated carefully to pre vent sound transmission Vibration isolators pur chased locally must be placed under the unit e It is always recommended that an auxiliary drain pan be installed under a horizontal air handler See Condensate Piping to prevent possible dam age to ceilings f Isolate the auxiliary drain pan from the unit or from the structure g Connect the auxiliary drain line to a separa...

Страница 6: ...nly needs to be suspended at both ends See Figure 11 d If the unit is not suspended it must be supported as mentioned above and isolated carefully to pre vent sound transmission Vibration isolators pur chased locally must be placed under the unit e It is always recommended that an auxiliary drain pan be installed under a horizontal air handler See Condensate Drain Piping to prevent pos sible damag...

Страница 7: ...ns Return ple num should be flanged Sheetmetal screws must be 1 2 in length or shorter See Figure 12 NOTE Any duct board return connection can be made to the sides of the unit using tape or mastic Rail Figure 11 Mounting Installation Options g Connect the auxiliary drain line to a separate drain line no trap is needed in this line and ter minate according to national and local codes h If a return ...

Страница 8: ...he tubing Overheating of the sensing bulb will affect the func tional characteristics and performance of the air han dler IMPORTANT Do NOT unseal refrigerant tubing until ready to cut and fit refrigerant lines 1 Remove both sealing caps from indoor coil 2 Field supplied tubing should be cut squared off en suring the tube is still round and free of burrs at the connecting end Clean the tubing to pr...

Страница 9: ...ighten the drain pipe excessively Sup port the condensate piping and traps outside the unit to prevent strain on the drain coupling H ELECTRICAL POWER WIRING WARNING ELECTRICAL SHOCK HAZARD LOCK UNIT DISCONNECT SWITCH IN OPEN POSITION BEFORE SERVICING UNIT FAILURE TO FOLLOW THIS WARNING COULD RESULT IN PROPERTY DAMAGE PERSONAL INJURY OR DEATH 1 These Air Handlers are shipped from the factory wired...

Страница 10: ...TION Disconnect power to the air handler before changing dip switch positions Failure to follow this procedure may result in equip ment damage Blower speed changes are made on the ECM Fan Con trol mounted on the control box The ECM Fan Control controls the variable speed motor There is a bank of 8 dip switches See Figure 17 The dip switches work in pairs to match the airflow for the outdoor unit s...

Страница 11: ...NECT 1 PF TO MATING PLUG IN THE HEATER CONTROL BOX AS SHOWN 3 TERMINAL W2 WILL HAVE INTERNAL CONNECTIONS ONLY IF 2ND CONTACTOR IS USED BY THE HEATER FOR CONTROLLING POWER TO ELECTRIC HEAT ELEMENTS IF 2ND BH CONTACTOR IS NOT USED THEN FIELD CONNECTIONS TO W2 CAN BE OMITTED AS APPROPRIATE 4 CONNECTIONS TO R BK O AND Y MUST BE MADE AS SHOWN FOR PROPER OPERATION OF BLOWER WITH HUMIDISTAT IN COOLING 4T...

Страница 12: ...E HEATER CONTROL BOX AS SHOWN 3 TERMINAL W2 WILL HAVE INTERNAL CONNECTIONS ONLY IF 2ND CONTACTOR IS USED BY THE HEATER FOR CONTROLLING POWER TO ELECTRIC HEAT ELEMENTS IF 2ND BH CONTACTOR IS NOT USED THEN FIELD CONNECTIONS TO W2 CAN BE OMITTED AS APPROPRIATE 4 IF ODT IS NOT USED THEN CONNECT APPROPRIATE JUMPER FROM W1 TO W2 TO W3 ON LVTB 5 CONNECTIONS TO R BK O AND Y MUST BE MADE AS SHOWN FOR PROPE...

Страница 13: ...low during the defrost cycle 5 Connect only if used with applicable indoor thermostat 6 When heaters are used discard power leads with polarized plug PM A and connect 1 PF to mating plug in the heater control box as shown REQUIRED WIRING Refer to Field Hook up Diagrams 4TTX6 4TWX6 4A7A6 4A6H6 units require 80 airflow with Y1 firststage 100 airflow with Y2 second stage Note A The installer must jum...

Страница 14: ...14 18 GE04D2 15 Installer s Guide 4TEE 3 F OUTLINE DRAWING ...

Страница 15: ...E04D2 15 15 Installer s Guide 4TEE3F AIR HANDLERS DIMENSIONAL DATA Model No H W 4TEE3F31B 43 00 21 50 4TEE3F37B 45 00 23 50 4TEE3F40B 51 75 26 00 4TEE3F49B 4TEE3F49C 57 90 4TEE3F65B 4TEE3F66A 62 75 H W 21 0 ...

Страница 16: ... RECOMMENDATIONS 1 Be sure the disconnect switch is OFF and safety label if any is attached 2 Check on field wiring for tight connections and grounding according to codes 3 Check circuit protection for proper size per nameplate specifications 4 Check control box panel in place and secured NOTE OPERATION OF HEATERS MUST BE CHECKED DURING THE OPERATION CHECK OF THE TOTAL SYSTEM J CHECKOUT PROCEDURES...

Отзывы: