Installer’s Guide

4TEE3F AIR HANDLERS WITH 2 STEP HEAT PUMP

4TEE3F AIR HANDLERS WITH 2 STEP COOLING

STEP

Air Handler

REQUIRED WIRING

• Refer to Field Hook-up Diagrams.

• 4TTX6/4TWX6/4A7A6/4A6H6 units require 80% airflow with “Y1”

(firststage), 100% airflow with “Y2” (second stage).

Note A –

 The installer must jumper at the LVTB “R” to “O”.

Note B –

 Cut/remove the factory installed “BK” jumper.

• Connect “Y1” from thermostat to “Y/Y2” at VS Air Handler to “Y1” at

Outdoor Unit.

• Connect “Y2” from thermostat to “BK” at VS Air Handler to “Y2” at

Outdoor Unit.

STEP

LEGEND

FACTORY WIRING

FIELD WIRING

Notes:
1. ODT-B must be set lower than ODT-A.
2. If ODT-B is not used, connect A Jumper wire from W3 to W2. If ODT-A is
not used, connect a jumper wire from W2 to W1.
3.  If electric heat does not have 3rd contactor (CH), connect a jumper wire
from W3 to W2. If electric heat does not have 2nd contactor (BH), connect a
jumper wire from W2 to W1.
4. X2 must be connected to variable speed air handler terminal W3, as
shown, for proper indoor air flow during the defrost cycle.
5. Connect only if used with applicable indoor thermostat.
6. When heaters are used, discard power leads with polarized plug PM-A and
connect 1-PF to mating plug in the heater control box as shown.

REQUIRED WIRING

• Refer to Field Hook-up Diagrams.

• 4TTX6/4TWX6/4A7A6/4A6H6 units require 80% airflow with “Y1”

(firststage), 100% airflow with “Y2” (second stage).

Note A –

 The installer must jumper at the LVTB “R” to “O”.

Note B –

 Cut/remove the factory installed “BK” jumper.

• Connect “Y1” from thermostat to “Y/Y2” at VS Air Handler to “Y1” at

Outdoor Unit.

• Connect “Y2” from thermostat to “BK” at VS Air Handler to “Y2” at

Outdoor Unit.

Notes:
1. Be sure power supply agrees with equipment nameplate.
2. Power wiring and grounding of equipment must comply with local codes.
3. Low voltage wiring to be No. 18 AWG minimum conductor.
4. If outdoor thermostat (ODT) is not used, connect W2 to W3.
5. Be sure the jumper between “R” and “BK” is cut or removed
(See Note B below).
6. With “O” and “Y/Y2” energized, indoor fan is at 80% airflow.
7. With “O”, “Y/Y2” and “BK” energized, indoor fan is at 100% airflow.
8. When heaters are used, discard power leads with polarized plug PM-A and
connect 1-PF to mating plug in the heater control box as shown.

See Note B

Содержание 4TEE3F31B1000B

Страница 1: ...ct your local distributor or the manufacturer as listed on the air handler nameplate These air handlers are shipped from the factory in the upflow or horizontal right configuration and are fully convertible to downflow or horizontal left Refer to Sec tion C beginning on page 4 for additional information INSPECTION Check carefully for any shipping damage This must be reported to and claims made aga...

Страница 2: ...the air handler must be made to allow access for refrigerant lines or attach refrigerant lines to air handler when installing This area may also be used for other purposes includ ing an electric hot water heater but in no case shall a fossil fuel device be installed and or operated in the same closet alcove or utility room In addition these air handlers are suitable for installa tion in an attic g...

Страница 3: ...structions These should only be installed on the supply air side of the system Atomizing style humidifiers are not recommended with the use of this unit C UNIT INSTALLATION UPFLOW a For maximum efficiency the horizontal drip tray should be removed See Figures 5 6 and 7 B Two Piece Cabinet Disassembly OPTIONAL NOTE For easier installation into tight areas the 4 and 5 ton air handlers can be disasse...

Страница 4: ...to support the total weight must be pro vided Provide a minimum height of 14 inches for proper unrestricted airflow d If a return air duct is connected to the air han dler it must be the same dimensions as shown in the outline drawing on page 13 e Pedestal and unit should be isolated from the foundation using a suitable isolating material f Openings where field wiring enters the cabinet must be co...

Страница 5: ...and isolated carefully to pre vent sound transmission Vibration isolators pur chased locally must be placed under the unit e It is always recommended that an auxiliary drain pan be installed under a horizontal air handler See Condensate Piping to prevent possible dam age to ceilings f Isolate the auxiliary drain pan from the unit or from the structure g Connect the auxiliary drain line to a separa...

Страница 6: ...nly needs to be suspended at both ends See Figure 11 d If the unit is not suspended it must be supported as mentioned above and isolated carefully to pre vent sound transmission Vibration isolators pur chased locally must be placed under the unit e It is always recommended that an auxiliary drain pan be installed under a horizontal air handler See Condensate Drain Piping to prevent pos sible damag...

Страница 7: ...ns Return ple num should be flanged Sheetmetal screws must be 1 2 in length or shorter See Figure 12 NOTE Any duct board return connection can be made to the sides of the unit using tape or mastic Rail Figure 11 Mounting Installation Options g Connect the auxiliary drain line to a separate drain line no trap is needed in this line and ter minate according to national and local codes h If a return ...

Страница 8: ...he tubing Overheating of the sensing bulb will affect the func tional characteristics and performance of the air han dler IMPORTANT Do NOT unseal refrigerant tubing until ready to cut and fit refrigerant lines 1 Remove both sealing caps from indoor coil 2 Field supplied tubing should be cut squared off en suring the tube is still round and free of burrs at the connecting end Clean the tubing to pr...

Страница 9: ...ighten the drain pipe excessively Sup port the condensate piping and traps outside the unit to prevent strain on the drain coupling H ELECTRICAL POWER WIRING WARNING ELECTRICAL SHOCK HAZARD LOCK UNIT DISCONNECT SWITCH IN OPEN POSITION BEFORE SERVICING UNIT FAILURE TO FOLLOW THIS WARNING COULD RESULT IN PROPERTY DAMAGE PERSONAL INJURY OR DEATH 1 These Air Handlers are shipped from the factory wired...

Страница 10: ...TION Disconnect power to the air handler before changing dip switch positions Failure to follow this procedure may result in equip ment damage Blower speed changes are made on the ECM Fan Con trol mounted on the control box The ECM Fan Control controls the variable speed motor There is a bank of 8 dip switches See Figure 17 The dip switches work in pairs to match the airflow for the outdoor unit s...

Страница 11: ...NECT 1 PF TO MATING PLUG IN THE HEATER CONTROL BOX AS SHOWN 3 TERMINAL W2 WILL HAVE INTERNAL CONNECTIONS ONLY IF 2ND CONTACTOR IS USED BY THE HEATER FOR CONTROLLING POWER TO ELECTRIC HEAT ELEMENTS IF 2ND BH CONTACTOR IS NOT USED THEN FIELD CONNECTIONS TO W2 CAN BE OMITTED AS APPROPRIATE 4 CONNECTIONS TO R BK O AND Y MUST BE MADE AS SHOWN FOR PROPER OPERATION OF BLOWER WITH HUMIDISTAT IN COOLING 4T...

Страница 12: ...E HEATER CONTROL BOX AS SHOWN 3 TERMINAL W2 WILL HAVE INTERNAL CONNECTIONS ONLY IF 2ND CONTACTOR IS USED BY THE HEATER FOR CONTROLLING POWER TO ELECTRIC HEAT ELEMENTS IF 2ND BH CONTACTOR IS NOT USED THEN FIELD CONNECTIONS TO W2 CAN BE OMITTED AS APPROPRIATE 4 IF ODT IS NOT USED THEN CONNECT APPROPRIATE JUMPER FROM W1 TO W2 TO W3 ON LVTB 5 CONNECTIONS TO R BK O AND Y MUST BE MADE AS SHOWN FOR PROPE...

Страница 13: ...low during the defrost cycle 5 Connect only if used with applicable indoor thermostat 6 When heaters are used discard power leads with polarized plug PM A and connect 1 PF to mating plug in the heater control box as shown REQUIRED WIRING Refer to Field Hook up Diagrams 4TTX6 4TWX6 4A7A6 4A6H6 units require 80 airflow with Y1 firststage 100 airflow with Y2 second stage Note A The installer must jum...

Страница 14: ...14 18 GE04D2 15 Installer s Guide 4TEE 3 F OUTLINE DRAWING ...

Страница 15: ...E04D2 15 15 Installer s Guide 4TEE3F AIR HANDLERS DIMENSIONAL DATA Model No H W 4TEE3F31B 43 00 21 50 4TEE3F37B 45 00 23 50 4TEE3F40B 51 75 26 00 4TEE3F49B 4TEE3F49C 57 90 4TEE3F65B 4TEE3F66A 62 75 H W 21 0 ...

Страница 16: ... RECOMMENDATIONS 1 Be sure the disconnect switch is OFF and safety label if any is attached 2 Check on field wiring for tight connections and grounding according to codes 3 Check circuit protection for proper size per nameplate specifications 4 Check control box panel in place and secured NOTE OPERATION OF HEATERS MUST BE CHECKED DURING THE OPERATION CHECK OF THE TOTAL SYSTEM J CHECKOUT PROCEDURES...

Отзывы: