Step 3 — Review Location and Recommendation
Information

H

Ho

orriizzo

on

ntta

all A

Aiirrffllo

ow

w U

Un

niittss

1. Location of the unit must allow service clearance

around it to ensure adequate serviceability,
maximum capacity, and peak operating efficiency.

2. These units are designed for outdoor installation.

They may be installed directly on a slab, wood
flooring, or on Class A, B, or C roof covering
material. The discharge air from the condenser fans
must be unrestricted for a minimum of 3 feet above
the unit.

3. Check the handling facilities to ensure the safety of

personnel and the unit(s).

4. The unit must be mounted level for proper drainage

of water through the drain holes in the base pan.

5. The unit should not be exposed to direct roof water

runoff.

6. Flexible duct connectors must be of a flame

retardant material. All duct work outside of the
structure must be insulated and weatherproofed in
accordance with local codes.

7. Holes through exterior walls or roof must be sealed

in accordance with local codes.

8. All fabricated outdoor ducts should be as short as

possible.

C

Clle

ea

arra

an

ncce

ess

1. The recommended clearances for single-unit

installations are illustrated in Figures 1 to 6.

2. Any reduction of the unit clearances indicated in

these figures may result in condenser coil
starvation or the recirculation of warm condenser
air. Actual clearances, which appear to be
inadequate should be reviewed with a local
engineer.

3. See the unit’s nameplate for the absolute minimum

clearance between the unit and any combustible
surfaces.

D

Do

ow

wn

n A

Aiirrffllo

ow

w U

Un

niittss

1. Location of the unit must allow service clearance

around it to ensure adequate serviceability,
maximum capacity, and peak operating efficiency.

2. Refer to the Installation section for instruction on

converting the supply and return airflow covers to
down airflow.

3. The field assembled Roof Mounting Curb

(BAYCURB050A or BAYCURB051A) or a field
fabricated curb should be in place before the unit is
hoisted to the roof top.
The Roof Mounting Curb (frame) must be installed
on a flat, level section of the roof (maximum of 1/4"
per foot pitch) and provide a level mounting surface
for the unit. Also, be sure to provide sufficient
height above the roof to prevent water from
entering the unit.

4. Be sure the mounting curb spans structural

members (trusses) of the roof, thereby providing
sufficient support for the weight of the unit, the
curb, the duct(s), and any factory or field installed
accessories.

5. The unit must be mounted level for proper drainage

of water through the drain holes in the base pan.

6. Be sure the hole in the structure for the ducts is

large enough to accommodate the fabricated ducts
and the insulation surrounding them. Flexible duct
connectors must be of a flame retardant material.
All duct work outside of the structure must be
insulated and weatherproofed in accordance with
local codes.

7. Holes through exterior walls or roof must be sealed

in accordance with local codes.

8. These units are design certified for outdoor

installation. They may be installed directly on a
slab, wood flooring, or on Class A, B, or C roof
covering material. The discharge air from the
condenser fans must be unrestricted for a minimum
of 3 feet above the unit.

9. Check the handling facilities to ensure the safety of

personnel and the unit(s).

C

Clle

ea

arra

an

ncce

ess

1. The recommended clearances for single-unit

installations are illustrated in Figures 1 to 6.

2. Any reduction of the unit clearances indicated in

these figures may result in condenser coil
starvation or the recirculation of warm condenser
air. Actual clearances, which appear to be
inadequate should be reviewed with a local
engineer.

3. See the unit’s nameplate for the absolute minimum

clearance between the unit and any combustible
surfaces.

Содержание 4TCC4024A1000A

Страница 1: ...alified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags stickers and labels that are attached to the equipment Ju...

Страница 2: ...tr ri ic ca al l c cu ur rr re en nt t a ar re e g gr ro ou un nd de ed d I If f g gr ro ou un nd di in ng g w wi ir re es s s sc cr re ew ws s s st tr ra ap ps s c cl li ip ps s n nu ut ts s o or r w...

Страница 3: ...Step 2 Determine Unit Clearances 5 Step 3 Review Location and Recommendation Information 11 Step 4 Unit Installation 12 Step 5 Unit Startup 21 Sequence of Operation 22 Maintenance 23 Important Product...

Страница 4: ...t 1 Check for damage after the unit is unloaded Report promptly to the carrier any damage found to the unit Do not drop the unit I Im mp po or rt ta an nt t To prevent damage to the sides and top of t...

Страница 5: ...18 EB30D1 1G EN 5 Step 2 Determine Unit Clearances Figure 1 2 3 TON MODELS Note The view labeled Bottom Side represents the base as viewed looking up from underneath the unit...

Страница 6: ...43 1 95 204 8 451 171 1 377 406 5 16 0 594 1 23 4 4TCC4036 61 7 136 38 9 86 27 7 61 43 7 96 205 7 453 172 0 379 414 3 16 3 697 6 27 5 4WCC4024 52 9 117 33 3 73 24 1 53 38 3 84 182 3 402 148 6 328 430...

Страница 7: ...18 EB30D1 1G EN 7 Figure 3 2 3 TON MODELS S St te ep p 2 2 D De et te er rm mi in ne e U Un ni it t C Cl le ea ar ra an nc ce es s...

Страница 8: ...N Figure 4 3 5 5 TON MODELS Note The view labeled Bottom Side represents the base as viewed looking up from underneath the unit S St te ep p 2 2 D De et te er rm mi in ne e U Un ni it t C Cl le ea ar...

Страница 9: ...54 4 120 252 6 557 205 4 453 433 0 17 0 743 3 29 3 4TCC4060 78 0 172 46 3 102 34 9 77 59 0 130 265 8 586 218 6 482 414 0 16 3 635 0 25 0 4WCC4042 64 4 142 47 6 105 39 5 87 49 9 110 248 6 547 9 201 4 4...

Страница 10: ...10 18 EB30D1 1G EN Figure 6 3 5 5 TON MODELS S St te ep p 2 2 D De et te er rm mi in ne e U Un ni it t C Cl le ea ar ra an nc ce es s...

Страница 11: ...nstruction on converting the supply and return airflow covers to down airflow 3 The field assembled Roof Mounting Curb BAYCURB050A or BAYCURB051A or a field fabricated curb should be in place before t...

Страница 12: ...the unit to direct roof water runoff 6 Seal all holes through exterior walls in accordance with local codes 7 Continue with the following installation sections to complete the installation Ductwork F...

Страница 13: ...on during lifting Always test lift the unit to determine the exact unit balance and stability before hoisting it to the installation location 4 When the curb and air ducts have been properly installed...

Страница 14: ...with local codes 11 Access and service clearances for the unit must be given careful consideration when locating the duct entrance openings Figures 1 to 6 provide unit dimensions 12 Continue with the...

Страница 15: ...V SUHSDUHG E WKH PDQXIDFWXUHU LQ RUGHU WR SURYLGH GHWDLO UHJDUGLQJ MRE OD RXW RQO 7KLV GUDZLQJ LV QRW LQWHQGHG WR EH XVHG DV D EDVLV WR FRQVWUXFW EXLOG RU PRGLI WKH LWHP GHSLFWHG LQ WKH GUDZLQJ 7KH PD...

Страница 16: ...port Center Support required on all frame applications Angle Iron Frame Table 5 Typical Rooftop Down Airflow Application with Frame Return Air Roof Flashing Channel Iron Center Support center support...

Страница 17: ...rproofed between the unit and the building When attaching ductwork to a horizontal unit provide a flexible watertight connection to prevent noise transmission from the unit to the ducts The flexible c...

Страница 18: ...hi in n s si ig gh ht t o of f t th he e u un ni it t If disconnect must be mounted to the cabinet the location shown in Table 9 p 18 should be the only one considered O Ov ve er r C Cu ur rr re en n...

Страница 19: ...RS FIELD INSTALLED JUMPERS 756977i2 FIELD PROVIDED FIELD CONNECTED WIRED UNIT HEATER AREA UNIT CONTROL BOX ELECTRIC HEATER CONTROL BOX HEATER FUSES UNIT FUSES GROUND WIRE UNIT LOW VOLTAGE AREA UNIT LO...

Страница 20: ...completion of wiring check all electrical connections including factory wiring within the unit and make sure all connections are tight Replace and secure all electrical box covers and access panels b...

Страница 21: ...e used in the A AU UT TO O mode O Op pe er ra at ti in ng g P Pr re es ss su ur re e C Ch he ec ck ks s After the unit has operated in the cooling mode for a short period of time install pressure gaug...

Страница 22: ...ought on when the indoor temperature drops 1 1 2 degrees below the thermostat setting T TS SH H 2 2 contacts close providing power to the W W terminal on the indoor thermostat and to the supplementary...

Страница 23: ...ters of the same type and size D Do o n no ot t a at tt te em mp pt t t to o c cl le ea an n d di is sp po os sa ab bl le e f fi il lt te er rs s Permanent type filters can be cleaned by washing them...

Страница 24: ...BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB 6HUYLFH QIRUPDWLRQ DOO RXU LQVWDOOLQJ GHDOHU LI WKH XQLW LV LQRSHUDWLYH HIRUH RX FDOO DOZD V FKHFN WKH IROORZLQJ WR EH VXUH VHUYLFH LV UHTXL...

Страница 25: ...18 EB30D1 1G EN 25 N No ot te es s...

Страница 26: ...26 18 EB30D1 1G EN N No ot te es s...

Страница 27: ...18 EB30D1 1G EN 27 N No ot te es s...

Страница 28: ...com The AHRI Certified mark indicates company participation in the AHRI Certification program For verification of individual certified products go to ahridirectory org The manufacturer has a policy o...

Отзывы: