Is sub cooling at the

outdoor unit between

8 to 12F?

Troubleshooting Indoor TXV / Cooling Mode

NO

YES

Is superheat

< 5F?

YES

Correct air

flow

problem

Is air flow at least

350 CFM per ton?

YES

NO

Remove sensing bulb from the

suction line. Measure superheat

at indoor coil while holding the

bulb in bare hand for one minute.

Does superheat decrease?

Measure superheat at indoor coil

while placing the bulb in an ice

and water bath for one minute.

Does superheat increase?

YES

Replace the

TXV

TXV is OK

NO

Is superheat

< 25F?

YES

NO

Is indoor

temperature more

than 85F?

NO

Is sub cooling less

than 8F?

YES

Confirm that charge

is correct and look

for dirty or restricted

outdoor coil.

Confirm that

charge is

correct.

NO

Before starting

, insure the

blower wheel, indoor and outdoor

coils are clean.

Is the liquid line

temperature at indoor

coil within 8F of outdoor

liquid line temperature?

YES

Verify line set is

sized properly

for application

NO

The system is running at max

capacity and this may be

causing the High superheat.

Wait until indoor temperature

is less than 80F and check

superheat again.

YES

YES

Verify Inlet screen

of inlet tube

assembly is clear

of debris

NO

Verify Inlet screen

of inlet tube

assembly is clear

of debris

NO

Содержание 4PXCAU24BS3HAA

Страница 1: ...4PXCAU24BS3HAA 4PXCAU32BS3HAA 4PXCBU24BS3HAA 4PXCBU30BS3HAA 4PXCCU30BS3HAA 4PXCBU36BS3HAA 4PXCCU36BS3HAA 4PXCBU42BS3HAA 4PXCCU42BS3HAA 4PXCBU48BS3HAA 4PXCCU48BS3HAA 4PXCDU48BS3HAA 4PXCCU60BS3HAA 4PXCD...

Страница 2: ...ration above 70 RH it is recommended to use the BAYGSKT001A0 gasket kit to prevent water from forming on the bottom of the drain pan and dripping into the supply ductwork a Lay the coil on its back si...

Страница 3: ...This would cause contamination of the refrig erantorpossibledischargeofrefrigeranttotheatmosphere 1 The following steps are to be considered when installing the refrigerant lines a Determine the most...

Страница 4: ...ions using soap bubbles Repair leaks if any after relieving pressure 4 Evacuate and charge the system per the instructions packaged with the outdoor unit I CONDENSATE DRAIN PIPING Condensate drain con...

Страница 5: ...16 5 8 16 5 8 20 1 8 16 5 8 20 1 8 20 1 8 TOP OPENING D 12 3 4 12 3 4 15 3 4 15 3 4 19 1 4 15 3 4 19 1 4 19 1 4 GAS CONNECTION 3 4 3 4 3 4 7 8 7 8 7 8 7 8 7 8 LIQUID CONNECTION 3 8 3 8 3 8 3 8 3 8 3 8...

Страница 6: ...NON BLEED HEIGHT IN 17 1 2 17 1 2 OVERALL WIDTH IN 17 1 2 21 OPENING WIDTH IN 16 5 8 20 1 8 TOP OPENING 15 3 4 19 1 4 GAS CONNECTION 3 4 3 4 LIQUID CONNECTION 3 8 3 8 MATCHED FURNACE WIDTH NO ADAPTER...

Страница 7: ...4PXCDD60BS3HDA MODEL 4PXCDU48BS3 4PXCDD48BS3 4PXCDU60BS3 4PXCDD60BS3 WEIGHT LBS 68 77 REFRIGERANT CONTROL TXV NON BLEED HEIGHT IN 26 7 8 30 3 4 OVERALL WIDTH IN 24 1 2 24 1 2 OPENING WIDTH IN 23 5 8...

Страница 8: ...superheat at indoor coil while holding the bulb in bare hand for one minute Does superheat decrease Measure superheat at indoor coil while placing the bulb in an ice and water bath for one minute Does...