Trane 4PXCAU24BS3HAA Скачать руководство пользователя страница 3

18-AD32D1-4E-EN  

3

Installer’s Guide

Maximum airflow setting, CFM

Coil

Upflow Downflow

Horizontal 

Left

Horizontal 

Right

4PXC*U24BS3HAA

900

750

800

900

4PXC*D24BS3HDA

n/a

n/a

4PXC*U30BS3HAA 1125

925

1000

1125

4PXC*D30BS3HDA

n/a

n/a

4PXC*U32BS3HAA

1350

1200

1350

1350

4PXC*U36BS3HAA

1100

1200

4PXC*D36BS3HDA

n/a

n/a

4PXC*U42BS3HAA 1575

1300

1400

1575

4PXC*D42BS3HDA

n/a

n/a

4PXC*U48BS3HAA 1800

1475

1600

1800

4PXC*D48BS3HDA

n/a

n/a

4PXC*U60BS3HAA 2250

1850

2000

2250

4PXC*D60BS3HDA

n/a

n/a

* May be "A", "B", "C", or "D"

F. MAXIMUM AIRFLOW SETTING, CFM

NOTE:   

Water blow-off could occur in certain installation posi-

tions if the airflow setting exceeds the maximum values 

listed.

IMPORTANT:  

Do not unseal refrigerant tubing until ready to fit refrigerant 

lines.

There is only a holding charge of dry air in the indoor coil, therefore 
no loss of operating refrigerant charge occurs when the sealing 
plugs are removed.

G. INSTALLING / BRAZING REFRIGERANT LINES

Do NOT open refrigerant valve at the outdoor unit until the 

refrigerant lines and coil have been brazed, evacuated, and 

leak checked.  This would cause contamination of the refrig-

erant or possible discharge of refrigerant to the atmosphere.

 

1.  The following steps are to be considered when installing the 
refrigerant lines:

a. Determine the most practical way to run the lines.
b. Consider types of bends to be made and space limitations.
c. Route the tubing making all required bends and properly 

secure the tubing before making final connections.

NOTE:

 Refrigerant lines must be isolated from the structure and 

the holes must be sealed weather tight after installation.

NOTE:   

The TXV setting on this unit may run high superheat  

(15-25°F) by design when measured at the outdoor unit.

Figure 4

Attach Downflow 
Bottom Gasket

Start 
here

Figure 5

Note: when installing coil onto an S-Series furnaces 
in horizontal right  or downflow configuration, bend 
the flanges downward for a flush fit.

BAYGSKT001A0.

 

c.  Attach the 4" gasket material to three sides of the bottom 

of the drain pan as shown. Make sure to start by matching 

up the edge of the gasket material to the inner edge of the 

drain pan by the coil fins and working outwards.

 

d.  The gasket material can be cut or ripped easily so that 

it can be tailored to fit. The gasket material must cover the 

three sides along the entire length of the coil as shown in 

Figure 4.

CAUTION

!

Содержание 4PXCAU24BS3HAA

Страница 1: ...4PXCAU24BS3HAA 4PXCAU32BS3HAA 4PXCBU24BS3HAA 4PXCBU30BS3HAA 4PXCCU30BS3HAA 4PXCBU36BS3HAA 4PXCCU36BS3HAA 4PXCBU42BS3HAA 4PXCCU42BS3HAA 4PXCBU48BS3HAA 4PXCCU48BS3HAA 4PXCDU48BS3HAA 4PXCCU60BS3HAA 4PXCD...

Страница 2: ...ration above 70 RH it is recommended to use the BAYGSKT001A0 gasket kit to prevent water from forming on the bottom of the drain pan and dripping into the supply ductwork a Lay the coil on its back si...

Страница 3: ...This would cause contamination of the refrig erantorpossibledischargeofrefrigeranttotheatmosphere 1 The following steps are to be considered when installing the refrigerant lines a Determine the most...

Страница 4: ...ions using soap bubbles Repair leaks if any after relieving pressure 4 Evacuate and charge the system per the instructions packaged with the outdoor unit I CONDENSATE DRAIN PIPING Condensate drain con...

Страница 5: ...16 5 8 16 5 8 20 1 8 16 5 8 20 1 8 20 1 8 TOP OPENING D 12 3 4 12 3 4 15 3 4 15 3 4 19 1 4 15 3 4 19 1 4 19 1 4 GAS CONNECTION 3 4 3 4 3 4 7 8 7 8 7 8 7 8 7 8 LIQUID CONNECTION 3 8 3 8 3 8 3 8 3 8 3 8...

Страница 6: ...NON BLEED HEIGHT IN 17 1 2 17 1 2 OVERALL WIDTH IN 17 1 2 21 OPENING WIDTH IN 16 5 8 20 1 8 TOP OPENING 15 3 4 19 1 4 GAS CONNECTION 3 4 3 4 LIQUID CONNECTION 3 8 3 8 MATCHED FURNACE WIDTH NO ADAPTER...

Страница 7: ...4PXCDD60BS3HDA MODEL 4PXCDU48BS3 4PXCDD48BS3 4PXCDU60BS3 4PXCDD60BS3 WEIGHT LBS 68 77 REFRIGERANT CONTROL TXV NON BLEED HEIGHT IN 26 7 8 30 3 4 OVERALL WIDTH IN 24 1 2 24 1 2 OPENING WIDTH IN 23 5 8...

Страница 8: ...superheat at indoor coil while holding the bulb in bare hand for one minute Does superheat decrease Measure superheat at indoor coil while placing the bulb in an ice and water bath for one minute Does...

Отзывы: