Trane 4PXCAU24BS3HAA Скачать руководство пользователя страница 4

 18-AD32D1-4E-EN

Installer’s Guide

NOTE:  

TXV bulb MUST be protected (wrapped with wet rag) or 

removed, while brazing the tubing. Overheating of the 

sensing bulb will affect the functional characteristics and 

performance of the comfort coil.

1. Remove both rubber plugs from the indoor coil.
2. Field supplied tubing should be cut square, round and free of burrs 
at the connecting end.  Clean the tubing to prevent contaminants 
from entering the system.
3. Run the refrigerant tubing into the stub tube sockets of the 
indoor unit coil.

PAINTED AREAS OF THE UNIT MUST BE SHIELDED DURING 
BRAZING.

4. Flow a small amount of nitrogen through the tubing while brazing.
5. Use good brazing technique to make leakproof joints.
6. Minimize the use of sharp 90 degree bends.
7. Insulate the suction line and its fittings.
8. Do NOT allow un-insulated lines to come into contact with each 
other.

When replacing the bulb and hose clamp, the clamp should 

be "snug" but not "tight" -  spec is to torque the hose clamp 

to 20+/-5in-lb. 

9. Wrap the TXV with insulation after the hose clamp has been 
installed.

H.  LEAK CHECK

1. Using a manifold gauge, connect an external supply of dry 
nitrogen to the gauge port on the liquid line.  
2. Pressurize the connecting lines and indoor coil to 150  PSIG 
maximum.
3. Leak check brazed line connections using soap bubbles.  Repair 
leaks (if any) after relieving pressure.
4. Evacuate and charge the system per the instructions packaged 
with the outdoor unit.

I.  CONDENSATE DRAIN PIPING

Condensate drain connections are located in the drain pan at the 
bottom of the coil/enclosure assembly.  The female threaded fit-
ting protrudes outside of the enclosure for external connection.  A 
field fabricated trap is not required for proper drainage due to the 

Figure 7

Figure 8

J.  CLEANING THE COIL

The two piece door (3-piece on 24.5" wide models) allows removal 
of the outer casing doors without interference from refrigerant or 
condensate lines.  Once the outer doors are removed the split 
inner coil panels can be easily removed.  The inside and outside 
of the coil can be easily cleaned with a brush and vacuum with 
the panels removed.  See Figure 7.

The foil covered insulation on 4PXC  coils should be wiped down 
and residual dirt and dust should be vacuumed up to maintain 
good air quality. See Figure 8.

Figure 6

Capillary tubes will come 

out the top of bulb when 

positioned correctly.

positive pressure of the furnace; however, it is  recommended to 
prevent efficiency loss of conditioned air. 
1. The drain hole in the drain pan must be cleared of all insulation.
2. Insulate the primary drain line to prevent sweating where dew 
point temperatures may be met.  (Optional depending on climate 
and application needs)  
3. Connect the secondary drain line to a separate drain line (no 
trap is needed in this line).  

Содержание 4PXCAU24BS3HAA

Страница 1: ...4PXCAU24BS3HAA 4PXCAU32BS3HAA 4PXCBU24BS3HAA 4PXCBU30BS3HAA 4PXCCU30BS3HAA 4PXCBU36BS3HAA 4PXCCU36BS3HAA 4PXCBU42BS3HAA 4PXCCU42BS3HAA 4PXCBU48BS3HAA 4PXCCU48BS3HAA 4PXCDU48BS3HAA 4PXCCU60BS3HAA 4PXCD...

Страница 2: ...ration above 70 RH it is recommended to use the BAYGSKT001A0 gasket kit to prevent water from forming on the bottom of the drain pan and dripping into the supply ductwork a Lay the coil on its back si...

Страница 3: ...This would cause contamination of the refrig erantorpossibledischargeofrefrigeranttotheatmosphere 1 The following steps are to be considered when installing the refrigerant lines a Determine the most...

Страница 4: ...ions using soap bubbles Repair leaks if any after relieving pressure 4 Evacuate and charge the system per the instructions packaged with the outdoor unit I CONDENSATE DRAIN PIPING Condensate drain con...

Страница 5: ...16 5 8 16 5 8 20 1 8 16 5 8 20 1 8 20 1 8 TOP OPENING D 12 3 4 12 3 4 15 3 4 15 3 4 19 1 4 15 3 4 19 1 4 19 1 4 GAS CONNECTION 3 4 3 4 3 4 7 8 7 8 7 8 7 8 7 8 LIQUID CONNECTION 3 8 3 8 3 8 3 8 3 8 3 8...

Страница 6: ...NON BLEED HEIGHT IN 17 1 2 17 1 2 OVERALL WIDTH IN 17 1 2 21 OPENING WIDTH IN 16 5 8 20 1 8 TOP OPENING 15 3 4 19 1 4 GAS CONNECTION 3 4 3 4 LIQUID CONNECTION 3 8 3 8 MATCHED FURNACE WIDTH NO ADAPTER...

Страница 7: ...4PXCDD60BS3HDA MODEL 4PXCDU48BS3 4PXCDD48BS3 4PXCDU60BS3 4PXCDD60BS3 WEIGHT LBS 68 77 REFRIGERANT CONTROL TXV NON BLEED HEIGHT IN 26 7 8 30 3 4 OVERALL WIDTH IN 24 1 2 24 1 2 OPENING WIDTH IN 23 5 8...

Страница 8: ...superheat at indoor coil while holding the bulb in bare hand for one minute Does superheat decrease Measure superheat at indoor coil while placing the bulb in an ice and water bath for one minute Does...

Отзывы: