Installer’s Guide

L.  LEAK CHECK
1. Using a manifold gauge, connect an external supply of dry 
nitrogen to the gauge port on the liquid line.  
2. Pressurize the connecting lines and indoor coil to 150  PSIG 
maximum.
3. Leak check brazed line connections using soap bubbles.  
Repair leaks (if any) after relieving pressure.
4. Evacuate and charge the system per the instructions pack-
aged with the outdoor unit.
M.  CONDENSATE DRAIN PIPING
Condensate drain connections are located in the drain pan 
at the bottom of the coil/enclosure assembly.  The female 
threaded fitting protrudes outside of the enclosure for external 
connection.  A field fabricated trap is required in this line.  
See Figure 18.
1. The drain hole in the drain pan must be cleared of all 
insulation.
2. Insulate the drain line to prevent sweating and dripping.
It is always recommended that an auxiliary drain pan be in-
stalled under a horizontally installed evaporator coil or 90% 
gas furnace. Connect the auxiliary drain line to a separate 
drain line (no trap is needed in this line).  

Field fabricated trap

2" MIN.

2" MIN.

CAP OR PLUG

Trap must be within 4' 

of furnace / air handler 

condensate drain connection.

Close as possible

Figure 18

Figure 19

Figure 20

N.  CLEANING THE COIL
The two piece door (3-piece on 24.5" wide models) allows 
removal of the outer casing doors without interference from 
refrigerant or condensate lines.  Once the outer doors are 
removed the split inner coil panels can be easily removed.  
The inside and outside of the coil can be easily cleaned with 
a brush and vacuum with the panels removed.  See Figure 19.
The foil covered insulation on 4NXC  coils should be wiped 
down and residual dirt and dust should be vacuumed up to 
maintain good air quality. See Figure 20.

Содержание 4NXCA018AC3HCA

Страница 1: ...ile Home use The height of the Furnace Coil and discharge duct work must be 7 ft or less Inspect the coil for shipping damaged Notify the transporta tion company immediately if the coil is damaged B A...

Страница 2: ...ews See Figure 2 b Replace only the top baffle using the same screws previously removed c The 2 outer water diverter baffles and the two piece factory baffle must be removed and the top baffle replace...

Страница 3: ...same screws previously removed c Installation of the 1 2 wide gasket behind the front and back triangular baffles is required for downflow ap plications d Remove the coil by sliding the coil out of t...

Страница 4: ...ombustible flooring a Place the coil case on the furnace supply air ple num b Secure the coil case to the plenum c Set the furnace on top of the coil case making sure that the back side of the dischar...

Страница 5: ...brackets for coil furnace alignment are included with the furnaces a In horizontal left the 4NXC coil case is rotated so the apex of the coil is away from the furnace and the auxiliary drain pan is no...

Страница 6: ...rflow for horizontal right installation This placement supersedes previous furnace Installer s Guide stating install with the apex of the coil pointing in the direction of airflow for horizontal appli...

Страница 7: ...ANT LINES 1 The following steps are to be considered when installing the refrigerant lines a Determine the most practical way to run the lines b Consider types of bends to be made and space limita tio...

Страница 8: ...he drain line to prevent sweating and dripping It is always recommended that an auxiliary drain pan be in stalled under a horizontally installed evaporator coil or 90 gas furnace Connect the auxiliary...

Страница 9: ...2 18 1 4 22 1 2 OVERALL WIDTH B IN 14 1 2 17 1 2 17 1 2 OPENING WIDTH C IN 13 5 8 16 5 8 16 5 8 TOP OPENING D 12 3 4 15 3 4 15 3 4 GAS CONNECTION 3 4 BRAZE LIQUID CONNECTION 3 8 BRAZE MATCHED FURNACE...

Страница 10: ...ARY DRAIN 3 4 NPT FOR VERTICAL POSITION PRIMARY DRAIN 3 4 NPT FOR VERTICAL POSITION 18 1 8 OPENING IN WRAPPER 21 1 2 3 1 8 7 8 19 3 8 MODEL 4NXCD063BC3HCA WEIGHT LBS 80 REFRIGERANT CONTROL TXV NON BLE...

Страница 11: ...the refrigerant system 17 Charge the system per the charging instructions with the outdoor unit P TXV CHANGE OUT 1 Unbraze the liquid line field connection 2 Remove the front panel and manifold panel...

Страница 12: ...decrease Measure superheat at indoor coil while placing the bulb in an ice and water bath for one minute Does superheat increase YES Replace the TXV NO TXV is OK NO Is superheat 20F NO YES NO Is indoo...

Отзывы: