Installer’s Guide

K.  BRAZING TO EVAPORATOR SECTION

IMPORTANT:  

Do not unseal refrigerant tubing until ready to cut and fit 

refrigerant lines.

There is only a holding charge of dry air in the indoor coil, 
therefore no loss of operating refrigerant charge occurs when 
the sealing plugs are removed.

NOTE:  

TXV bulb MUST be protected (wrapped with wet rag) or 

removed, while brazing the tubing. Overheating of the 

sensing bulb will affect the functional characteristics and 

performance of the comfort coil.

1. Remove both seals from the indoor coil.  The braze caps 
are soft soldered.
2. Field supplied tubing should be cut square, round and free 
of burrs at the connecting end.  Clean the tubing to prevent 
contaminants from entering the system.
3. 

Run the refrigerant tubing into the stub tube sockets 

of the indoor unit coil.
PAINTED AREAS OF THE UNIT MUST BE SHIELDED 

DURING BRAZING.
4. Braze and evacuate according to indoor and outdoor instal-
lation instructions.
5. Flow a small amount of nitrogen through the tubing while 
brazing.
6. Use good brazing technique to make leakproof joints.
7. Minimize the use of sharp 90 degree bends.
8. Insulate the suction line and its fittings.
9. Do NOT allow un-insulated lines to come into contact with 
each other.

CAUTION

!

Do NOT open refrigerant valve at the outdoor unit until the 

refrigerant lines and coil have been brazed, evacuated, and 

leak checked.  This would cause contamination of the refriger-

ant or possible discharge of refrigerant to the atmosphere.

I. INSTALLING REFRIGERANT LINES

1.  The following steps are to be considered when installing 
the refrigerant lines:
a. Determine the most practical way to run the lines.
b. Consider types of bends to be made and space limita-
tions.

NOTE:  

Large diameter tubing sizes will be difficult to bend once 

it has been shaped.

c. Determine the best starting point for routing the refrigerant 
tubing --INSIDE OR OUTSIDE THE STRUCTURE.
d. Provide a pull through hole of sufficient size to allow both 
liquid and gas lines to clear.  The location of this hole (if prac-
tical) should be just above the wall plate which is resting on 
the foundation.
e. Be sure the roll of tubing is of sufficient length.
f. Uncoil the tubing - do not kink or dent. 
g. Route the tubing making all required bends and properly 
secure the tubing before making final connections.
NOTE: These lines must be isolated from the structure and 

the holes must be sealed weather tight after installation.

J.  FIELD FABRICATED INTERCONNECTING LINES
1.  The following procedure should be used for connecting 
tubing to the coil or the Outdoor Unit.
2.  More information concerning the installation of refriger-
ant lines is covered in the Installers Guide packaged with the 
outdoor unit.  Evacuation, leak testing and brazing procedures 
are included in those instructions before starting the instal-
lation of refrigerant lines.

Maximum airflow setting, CFM

Coil

Horizontal 

Left

Horizontal 

Right

Downflow

4NXCA018AC3HCA
4NXCA024AC3HCA

900

900

800

4NXCB025AC3HCA
4NXCB031AC3HCA

1125

1125

1000

4NXCB032AC3HCA
4NXCB036AC3HCA

1200

1350

1200

4NXCD063BC3HCA

2250

2250

1750

H. MAXIMUM AIRFLOW SETTING, CFM

NOTE:   

Water blow-off could occur in certain installation posi-

tions if the airflow setting exceeds the maximum values 

listed.

Содержание 4NXCA018AC3HCA

Страница 1: ...ile Home use The height of the Furnace Coil and discharge duct work must be 7 ft or less Inspect the coil for shipping damaged Notify the transporta tion company immediately if the coil is damaged B A...

Страница 2: ...ews See Figure 2 b Replace only the top baffle using the same screws previously removed c The 2 outer water diverter baffles and the two piece factory baffle must be removed and the top baffle replace...

Страница 3: ...same screws previously removed c Installation of the 1 2 wide gasket behind the front and back triangular baffles is required for downflow ap plications d Remove the coil by sliding the coil out of t...

Страница 4: ...ombustible flooring a Place the coil case on the furnace supply air ple num b Secure the coil case to the plenum c Set the furnace on top of the coil case making sure that the back side of the dischar...

Страница 5: ...brackets for coil furnace alignment are included with the furnaces a In horizontal left the 4NXC coil case is rotated so the apex of the coil is away from the furnace and the auxiliary drain pan is no...

Страница 6: ...rflow for horizontal right installation This placement supersedes previous furnace Installer s Guide stating install with the apex of the coil pointing in the direction of airflow for horizontal appli...

Страница 7: ...ANT LINES 1 The following steps are to be considered when installing the refrigerant lines a Determine the most practical way to run the lines b Consider types of bends to be made and space limita tio...

Страница 8: ...he drain line to prevent sweating and dripping It is always recommended that an auxiliary drain pan be in stalled under a horizontally installed evaporator coil or 90 gas furnace Connect the auxiliary...

Страница 9: ...2 18 1 4 22 1 2 OVERALL WIDTH B IN 14 1 2 17 1 2 17 1 2 OPENING WIDTH C IN 13 5 8 16 5 8 16 5 8 TOP OPENING D 12 3 4 15 3 4 15 3 4 GAS CONNECTION 3 4 BRAZE LIQUID CONNECTION 3 8 BRAZE MATCHED FURNACE...

Страница 10: ...ARY DRAIN 3 4 NPT FOR VERTICAL POSITION PRIMARY DRAIN 3 4 NPT FOR VERTICAL POSITION 18 1 8 OPENING IN WRAPPER 21 1 2 3 1 8 7 8 19 3 8 MODEL 4NXCD063BC3HCA WEIGHT LBS 80 REFRIGERANT CONTROL TXV NON BLE...

Страница 11: ...the refrigerant system 17 Charge the system per the charging instructions with the outdoor unit P TXV CHANGE OUT 1 Unbraze the liquid line field connection 2 Remove the front panel and manifold panel...

Страница 12: ...decrease Measure superheat at indoor coil while placing the bulb in an ice and water bath for one minute Does superheat increase YES Replace the TXV NO TXV is OK NO Is superheat 20F NO YES NO Is indoo...

Отзывы: