Installation Verification and Run Test

Installation Verification and Run Test

Before run test

Do not apply power before installation has been completed.

Electric wiring must be connected correctly and securely.

Connection piping shut-off valves should be in open position.

The unit must be rid of all debris and scrap.

Run test 

Press the "ON/OFF" button on the wireless remote control to initiate operation.

Press the MODE button to select COOL, HEAT,  FAN to verify the normal operation of the unit.

Items to verify:

Possible problems they generate:

Has the indoor unit been firmly installed?

The unit may drop, shake or emit noise

Have you done the refrigerant leak test?

It may cause insufficient cooling/heating capacity

Is thermal insulation sufficient?

It may cause condensation and dripping

Does the unit drain appropriately?

It may cause condensation and dripping

Is the voltage in accordance with the rated voltage 

marked on the nameplate?

It may cause electric malfunction or damage the 

unit

Is the electric wiring and piping connection installed 

correctly and securely?

It may cause electric malfunction or damage the 

unit

Has the unit been connected to a secure earth 

connection?

It may cause electric current leakage

Has the proper power cord been specified?

It may cause electric malfunction or damage to unit

Has the inlet and the outlet been covered?

It may cause insufficient cooling/heating capacity

Has the length of connection pipes and refrigerant 

charge been recorded?

Refrigerant charge will be inadequate

Содержание 4MXW5

Страница 1: ...stalled adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags stickers...

Страница 2: ......

Страница 3: ...in death or serious injury CAUTIONs Indicates a potentially hazardous situation which if not avoided could result in minor or moderate injury It may also be used to alert against unsafe practices NOTI...

Страница 4: ...General Information 5 Accessories 6 Typical Installation 7 Installation Location 8 Indoor Unit Outdoor Unit 9 Vacuum Pump and Leak Inspection 13 Outdoor Condensation Drainage heat pump only 14 Connec...

Страница 5: ...n On arrival inspect the unit before signing the delivery note Specify any damage on the unit on the delivery note and send a registered letter of protest to the last carrier of the goods within 71 ho...

Страница 6: ...6 MS SVN047B EN Accessories Accessories Figure 1 Accessories for Installation 0 10...

Страница 7: ...MS SVN047B EN 7 Installation Installation Figure 2 Names and functions of each part...

Страница 8: ...air filters can be easily removed Outdoor Unit WARNING Adequate Support Wall structure must be adequate to support the weight of the unit Failure to ensure adequate structural support could result in...

Страница 9: ...irections shown as follows Figure 4 Piping directions Drill a 65mm diameter hole in the wall if the units is up to 18MBH or a 95mm diameter hole if the unit is up to above 18MBH The perforation should...

Страница 10: ...See figure below 3 The entire length of the indoor drain hose should be wrapped around with insulation Figure 6 Drain Hose Hanging the Unit on the Wall 1 While directing piping and wiring either from...

Страница 11: ...asten the flared nut manually and then tighten the nut using a spanner wrench or a torque wrench Table 1 Tightening torque Note First connect the connection pipe to the indoor unit then connect to the...

Страница 12: ...t and attach power wiring cord to terminal block Wiring should match that of the indoor unit 3 Using a wire clamp attach the power wiring cord inside the control panel for cooling and heating unit use...

Страница 13: ...6 If vacuum gauge does not rise above 500 microns in one 1 minute the evacuation should be complete 7 Blank off vacuum pump and micron gauge and close vales on manifold gauge set Note DO NOT VENT REFR...

Страница 14: ...gerant flow If refrigerant lines are longer than fifteen feet 8m it will be necessary to adjust system refrigerant charge upon completion of installation Outdoor Condensation Drainage Heat Pump type o...

Страница 15: ...ant leak test It may cause insufficient cooling heating capacity Is thermal insulation sufficient It may cause condensation and dripping Does the unit drain appropriately It may cause condensation and...

Страница 16: ...mm 6 1 4 6 1 4 6 1 4 6 1 4 Gas pipe mm 9 52 3 8 9 52 3 8 12 1 2 12 1 2 Maximum Distance Height m 15 15 20 20 Length m 30 30 40 40 Standard Efficiency 60hz Cooling Only 4MYW5509A1 4TYK5509A1 4MYW5512A...

Страница 17: ...4TXK5512AB 4MXW5518AB 4TXK5518AB 4MXW5524AB 4TXK5524AB Refrigerant Charge kg R410A 0 70 R410A 0 96 R410A 1 25 R410A 1 40 Length m 5 5 5 5 Additional Gas Charge g m 15 15 20 20 Outside Diameter Liq pip...

Страница 18: ...re Hazards with Improperly Installed and Grounded Field Wiring Improperly installed and grounded field wiring poses fire and electrocution hazards To avoid these hazards you must follow requirements f...

Страница 19: ...9 325 725 8 1 7 1 0 287 225 81 7 3 3 1 02725 0 3 63 63 20 287 1 6 1 02725 1 0 1 7 5 1 78 1 1 1 208 8 3 0DLQ RDUG 1 1 6 7 2 0 62 7 21 75 RPS DQG 7 7 1 1 1 02725 0 2 1 5 3527 725 29 5 2 5 29 203 8 9 8...

Страница 20: ...ZKHQ WKH YROWDJH RI WHUPLQDO 3 DQG 1 DW 3 LV KLJKHU WKDQ 9 WR SUHYHQW WKH ULVN RI HOHFWULFDO VKRFN 0 5 1 5 1 0 5 725 3 7 50 1 2 2 7 50 1 7 3 9 9 9 9 97 97 5 32 5 3 RDUG 3 LOWHU 1 8 1 1 1 8 2 7 50 1 1...

Страница 21: ...MS SVN047B EN 21 Wiring Diagrams Figure 18 4TYK4518A1 4TXK5524A1 Outdoor Unit Heat Pump Figure 19 4MXW5509AB 4MXW5512AB Indoor Unit Heat Pump...

Страница 22: ...22 MS SVN047B EN Wiring Diagrams Figure 20 4MXW5518AB 4MXW5524AB Indoor Unit Heat Pump Figure 21 4TXK5509AB Outdoor Unit Heat Pump...

Страница 23: ...MS SVN047B EN 23 Wiring Diagrams Figure 22 4TXK5512AB Outdoor Unit Heat Pump Figure 23 4TXK5512AB 4TXK5524AB Outdoor Unit Heat Pump...

Страница 24: ...bles and increase industrial productivity and efficiency We are a global business of 13 million committed to a world of sustainable progress and enduring results Trane has a policy of continuous produ...

Отзывы: