Indoor Blower Performance

Indoor Fan Performance 4DCY4048

Down Airflow

Horizontal Airflow

4DCY4048-HOR

DIPSWITCH SETTINGS

External Static Pressure (in. wg)

AIRFLOW SETTING

1

2

3

4

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

350 CFM/TON

OFF

OFF

OFF

ON

Watts

187

232

264

291

318

347

379

413

446

472

-

CFM

1355

1387

1396

1392

1382

1370

1360

1351

1341

1326

-

400 CFM/TON*

OFF

OFF

OFF

OFF

Watts

315

324

352

389

428

464

498

529

563

606

-

CFM

1603

1581

1577

1580

1583

1583

1577

1567

1558

1556

-

450 CFM/TON

OFF

OFF

ON

OFF

Watts

301

431

507

552

584

615

651

694

739

779

-

CFM

1752

1794

1812

1816

1812

1806

1800

1797

1793

1785

-

4DCY4048-DOWN

DIPSWITCH SETTINGS

External Static Pressure (in. wg)

AIRFLOW SETTING

1

2

3

4

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

350 CFM/TON

OFF

OFF

OFF

ON

Watts

208

254

284

312

343

379

414

437

460

490

-

CFM

1337

1393

1398

1388

1383

1390

1399

1384

1380

1370

-

400 CFM/TON*

OFF

OFF

OFF

OFF

Watts

302

349

386

423

465

509

552

583

599

628

-

CFM

1574

1580

1585

1589

1594

1598

1601

1597

1584

1556

-

450 CFM/TON

OFF

OFF

ON

OFF

Watts

501

523

555

592

631

672

714

760

800

845

-

CFM

1847

1823

1817

1818

1820

1819

1817

1820

1815

1810

-

Selection

Low Stage High Stage

7-OFF

8-OFF

A

1075

1375

7-ON

8-OFF

B

1100

1450

7-OFF

8-ON

C

1150

1500

7-ON

8-ON

D

1200

1575

Switch Settings

Nominal Airflow

4DCY4048C *09

0

* can be 1 or 3

Indoor Fan Performance 4DCY4060

Down Airflow

Horizontal Airflow

Low Stage High Stage

7-OFF

8-OFF

A

1375

1800

7-ON

8-OFF

B

1450

1900

7-OFF

8-ON

C

1525

1975

7-ON

8-ON

D

1575

2075

 

Switch Settings

Selection

4DCY4060C1115

Nominal Airflow

4DCY4060-HOR

DIPSWITCH SETTINGS

External Static Pressure (in. wg)

AIRFLOW SETTING

1

2

3

4

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

350 CFM/TON

OFF

OFF

OFF

ON

Watts

394

427

464

504

548

591

633

668

-

-

-

CFM

1673

1772

1799

1793

1779

1771

1767

1756

-

-

-

400 CFM/TON*

OFF

OFF

OFF

OFF

Watts

695

642

660

710

764

811

849

893

966

1108

-

CFM

2054

2036

2031

2032

2033

2031

2023

2012

2002

2000

-

4DCY4060-DOWN

DIPSWITCH SETTINGS

External Static Pressure (in. wg)

AIRFLOW SETTING

1

2

3

4

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

350 CFM/TON

OFF

OFF

OFF

ON

Watts

443

461

493

532

571

607

642

680

-

-

-

CFM

1796

1741

1726

1725

1722

1712

1698

1692

-

-

-

400 CFM/TON*

OFF

OFF

OFF

OFF

Watts

740

697

715

763

819

866

892

894

872

835

-

CFM

2012

1987

1979

1977

1976

1969

1950

1913

1852

1759

-

Auxiliary Heating Airflow, horizontal or downflow from .2 to .6” wg.

*Factory Default Setting

Содержание 4DCY4024

Страница 1: ... 2014Trane Pub No 22 1799 20 EN Product Data 4DCY4024 through 4DCY4060 Packaged Convertible Dual Fuel 14 SEER 2 5 Ton 60 120 MBTU R 410A 22 1799 20 EN ...

Страница 2: ... these products including the compressor have been designed and manufactured for maximum service Every Climatuff compressor is designed and manufac tured to exacting specifications Each design is life tested in extreme envi ronments to ensure reliable and long lasting operation in normal applications Each compressor has internal motor protection for added reliability Single Packaged Convertible Du...

Страница 3: ...3 Contents Optional Equipment Listing 4 General Data 5 Indoor Blower Performance 8 TypicalWiring 16 Optional Equipment 14 Dimensional Data 19 Mechanical Specifications 25 ...

Страница 4: ...BAYFLTR201B Head Pressure Control Low Ambient Cool 208 240v Kit 5 BAYLOAM105A Quick Start Kit 4DCY4 1 BAYQSKT300A Crankcase Heater Recip 4DCY4024 30 230v 5 BAYCCHT101A Crankcase Heater Scroll 4DCY4042 48 60 230v 5 BAYCCHT102A Crankcase Heater Scroll 4DCY4036 230v 5 BAYCCHT103A Adapter Curb 4DCY4024 36 to BAYCURB030 38 BAYADAP050A Adapter Curb 4DCY4024 36 to BAYCURB033 BAYADAP051A Adapter Curb 4DCY...

Страница 5: ...60 1 0 1 7 CENTRIFUGAL 10 X 10 DIRECT VARIABLE SEE FAN PERFORMANCE TABLE 1 2 VARIABLE 208 230 1 60 4 3 4 3 CENTRIFUGAL DIRECT 2 1 20 3350 2600 208 230 1 60 0 34 NO THROWAWAY 4 R410A 6 56 H X W X L 45 86 44 5 52 03 481 385 MODEL RATED Volts PH Hz Performance Cooling BTUH Indoor Airflow CFM Power Input KW EER SEER BTU Watt Hr Sound Power Rating dB A 7 HP Heating Performance High Temp BTUH COP Power ...

Страница 6: ...rive No Speeds Motor HP R P M High Low Volts Ph Hz FLA FILTER FURNISHED Type Recommended Recmd Face Area sq ft REFRIGERANT Charge lbs DIMENSIONS Crated in WEIGHT Shipping Net lbs 4DCY4048C1090B 208 230 1 60 47500 1470 3 96 12 0 14 0 73 45000 3 5 3 77 26800 2 3 3 44 8 0 90000 72900 30 60 72000 58320 81 NATURAL LP 1 2 208 230 1 60 33 9 50 50 SCROLL 208 230 1 60 20 5 109 SPINE FIN 2 24 18 01 3 8 EXPA...

Страница 7: ...Drive No Speeds Motor HP R P M High Low Volts Ph Hz FLA FILTER FURNISHED Type Recommended Recmd Face Area sq ft REFRIGERANT Charge lbs DIMENSIONS Crated in WEIGHT Shipping Net lbs 4DCY4048A3096C 208 230 3 60 47000 1470 4 03 10 85 14 0 73 42500 3 5 3 56 26800 2 3 3 44 8 0 96000 77500 30 60 72000 62000 80 NATURAL 1 2 208 230 3 60 25 3 35 35 SCROLL 208 230 3 60 13 7 83 1 SPINE FIN 2 24 18 01 3 8 EXPA...

Страница 8: ...925 7 ON 8 ON D 700 975 4DCY4024 Switch Settings Nominal Airflow Auxiliary Heating Airflow horizontal or downflow from 2 to 6 wg 4DCY4030 HOR DIPSWITCH SETTINGS External Static Pressure in wg AIRFLOW SETTING 1 2 3 4 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 350 CFM TON OFF OFF OFF ON Watts 112 155 176 199 231 270 299 289 197 CFM 867 905 904 899 904 914 907 840 650 400 CFM TON OFF OFF OFF OFF Wat...

Страница 9: ...4DCY4036 Switch Settings Nominal Airflow Auxiliary Heating Airflow horizontal or downflow from 2 to 6 wg 4DCY4042A HOR DIPSWITCH SETTINGS External Static Pressure in wg AIRFLOW SETTING 1 2 3 4 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 350 CFM TON OFF OFF OFF ON Watts 160 185 214 245 277 308 339 368 396 423 CFM 1206 1211 1213 1215 1215 1214 1212 1208 1201 1190 400 CFM TON OFF OFF OFF OFF Watts 23...

Страница 10: ...1817 1818 1820 1819 1817 1820 1815 1810 Selection Low Stage High Stage 7 OFF 8 OFF A 1075 1375 7 ON 8 OFF B 1100 1450 7 OFF 8 ON C 1150 1500 7 ON 8 ON D 1200 1575 Switch Settings Nominal Airflow 4DCY4048C 090 can be 1 or 3 Indoor Fan Performance 4DCY4060 Down Airflow Horizontal Airflow Low Stage High Stage 7 OFF 8 OFF A 1375 1800 7 ON 8 OFF B 1450 1900 7 OFF 8 ON C 1525 1975 7 ON 8 ON D 1575 2075 ...

Страница 11: ...11 Typical Field Wiring ...

Страница 12: ...12 Typical Wiring ...

Страница 13: ...13 Typical Wiring ...

Страница 14: ...s page are prepared by the manufacturer in order to provide detail regarding job layout only These drawings are not intended to be used as a basis to construct build or modify the items depicted in the drawings The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use ...

Страница 15: ...s page are prepared by the manufacturer in order to provide detail regarding job layout only These drawings are not intended to be used as a basis to construct build or modify the items depicted in the drawings The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use ...

Страница 16: ...is to construct build or modify the items depicted in the drawings The manufacturer is not respon sible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use BAYFLTR101 201B 1 2 Filter Rack Mounts in Filter Coil Section BAYACCDOR1A BAYACCDOR2A Hinged Filter Access Door Replaces Filter Coil Access Panel Filter ...

Страница 17: ...d by the manu facturer in order to provide detail regarding job layout only These drawings are not intended to be used as a basis to construct build or modify the items depicted in the drawings The manu facturer is not responsible for the unauthorized use of these drawings and ex pressly disclaims any liability for damages resulting from such unauthorized use Mixed Air Sensor Economizer Unit Appli...

Страница 18: ... not responsible for the unauthorized use of these drawings and expressly disclaims any liability for dam ages resulting from such unauthorized use D C B A E Manual Fresh Air Model Unit Application Models A B C D BAYOSAH001 4YC WC3018 036 4TC 3018 036 4W T Y DCY4024 036 4W Y DCZ6036 22 7 16 20 11 16 12 3 8 9 3 16 BAYOSAH002 4YC WC3042 060 4TC 3042 060 4W T Y DCY4042 060 4W Y DCZ6048 060 25 3 16 20...

Страница 19: ...19 Dimensional Data 4DCY4024 through 4DCY4036 1 of 3 ...

Страница 20: ...20 Dimensional Data 4DCY4024 through 4DCY4036 2 of 3 ...

Страница 21: ...21 Dimensional Data 4DCY4024 through 4DCY4036 3 of 3 ...

Страница 22: ...22 4DCY4042 through 4DCY4060 1 of 3 Dimensional Data ...

Страница 23: ...23 Dimensional Data 4DCY4042 through 4DCY4060 2 of 3 ...

Страница 24: ...24 4DCY4042 through 4DCY4060 3 of 3 Dimensional Data ...

Страница 25: ...d on all four sides by louvered panels Indoor Air Fan Direct drive forward curved centrifugal wheel in a Composite Vortica Blower housing Motor shall have thermal overload protection Perma nently lubricated motor bearings Motor blower assembly isolated from unit with rubber mounts Condenser Fan Direct drive draw through propeller type Weather proofed permanent split capacitor fan motor shall have ...

Отзывы: