background image

 

Page 3

Installer’s Guide

Introduction

Contents

Safety Considerations 

2

Introduction 3
Step 1-Inspect Shipment 

3

Step 2-Determine Unit Clearances  

4

Step 3-Review Location and Recommendation  

 

                     Information  

10

Step 4-Unit Installation 

 11

    Install Flue Hood 

11

    Ground Level Installation 

11

    Rooftop Installation -- Curb Mounting 

11

        Covert Horizontal Airflow to Down Airflow 

11     

        Install Full Perimeter Roof Mounting Curb 

11        

        Lifting and Rigging 

12

        Placing the Unit  on the Mounting Curb 

 12

    Rooftop Installation -- Frame Mounting 

13

    Rooftop Installation -- No Curb/Fram 

13

    Ductwork Installation 

16

         Attaching Downflow Ductwork to Roof Curb 

16

         Attaching Downflow Ductwork to Roof Frame 

16

         Attaching Horizontal Ductwork to Unit 

16

    Condensate Drain Piping 

16

    Gas Piping Installation 

17

    Pipe Delivery Schedule (natural gas only) 

17

    Gas Pressure Set-up Precautions 

17

    Gas Supply Line Pressure (all fuels) 

17

    Verify Manifold Pressure 

18

    Input Check and Adjustment 

18

    High Altitude Installation 

19

    Air Filter Installation 

19

    Electrical Wiring 

19

        Electrical Connections 

19

        Electrical Power 

19

        Disconnect Switch 

20

        Over current Protection 

20

        Power Wiring 

20

        Control Wiring (Class II) 

20

        Thermostat Operation 

20

       Field Wiring Diagram 

21 

Step 5-Unit Startup 

22

    Pre-start Quick Checklist 

22

    Starting the Unit in the Cooling Mode 

22

        Operating Pressures 

22

        Voltage Check 

22

        Cooling Shutdown 

22

    Starting the Unit in Heat Pump Heating Mode 

22

    Gas Furnace Heating Cycle 

22

    Starting the Unit in Gas Heating Mode 

23

    Heating Shut-down 

23

    Final Installation Checklist 

23

Sequence of Operation 

24

Maintenance 26
    Owner Maintenance  

26

    Service Maintenance 

26

        Cooling Season 

26

        Heating Season 

26

       Flue Hood and Combustion Blower Cleaning 

27

ECM Fan Motor Adjustments 

27   

Status LEDs  

28

Read this manual carefully before attempting to install, oper-
ate, or perform maintenance on this unit. Installation and 
maintenance should be performed by qualified service techni-
cians only. Do NOT use this furnace for temporary heating of 
buildings under construction.

As shipped from the factory, this unit is for use with natural gas 
only. It is listed by Underwriters Laboratory. An LP Gas conver-
sion kit is available. Extreme mounting kits for slab and curbs 
are also available.
Packaged units are designed for outdoor mounting with a 
vertical condenser discharge. They can be located either at 
ground level or on a roof in accordance with local codes or 
National Fuel Gas Code (ANSI-Z223.1A) Latest Revision. 
Since these units are designed exclusively for outdoor opera-
tion, additional flue venting systems are not required. Each 
unit contains an operating charge of refrigerant as shipped. 
Extreme mounting kits are available for slab (BAYEX-
MK003A), utility curb (BAYEXMK002B), or curb (BAYEX-
MK001A) mountings.
The indoor fan motor speed adjustment is provided in the 
Service Maintenance section on page 26.
This guide is organized as follows:

 

Step 1- Inspect Shipment

 

Step 2- Determine Unit Clearances

 

Step 3- Review Location and Recommendation Information

 

Step 4- Unit Installation

 

Step 5- Unit Startup

 

Sequence of Operation

 

Maintenance

Step 1—Inspect Shipment

 1.  Check for damage after the unit is unloaded. Report promptly 

to the carrier any damage found to the unit. Do not drop the 
unit.

IMPORTANT:

 To prevent damage to the sides and top of the 

unit when hoisting, use “spreader bars” as shown on page 13.

 2. Check the unit’s nameplate to determine if the unit is correct for 

the intended application. The power supply must be adequate 
for the unit and all accessories.

 3. Check to be sure the refrigerant charge has been retained 

during shipment.  Remove the Compressor access panel to 
access the 1/4" flare pressure taps.

 4. The Flue Hood is included with the unit's literature pack. 
5. If this unit is being installed on a curb, verify that the correct 

curb is provided for the unit. 

 •

 4DCL4024-036 use model BAYCURB050A.

 •

 4DCL4042-060 use model BAYCURB051A.

6.  If the unit is being hoisted, accessory kit BAYLIFT002B is 

recommended. It includes a kit of four (4) lifting lugs and  
instructions.

 

NOTE:

 If practical, install any internal accessories to the  

unit at the shop.

 

    

 

      

NOTE:

 The packaged units have been evaluated in ac-

cordance with the Code of Federal Regulations, Chapter 

XX, Part 3280 or the equivalent. "SUITABLE FOR MO-

BILE HOME USE".

RELEASED 10/Aug/2020 16:34:00 GMT

Содержание 4DCL4024

Страница 1: ...ards during installation and service the electrical supply must be disconnected and the main gas valve must be turned off If operating checks must be performed with the unit operating it is the technician s responsibility to recognize these hazards and proceed safely WARNING SAFETY HAZARD Do not operate the unit without the evaporator fan or coil access pan els in place Reinstall the access panels...

Страница 2: ...erate fiber concentrations requiring additional respiratory pro tection Use the appropriate NIOSH approved respirator in these situations FIRST AID MEASURES Eye Contact Flush eyes with water to remove dust If symptoms persist seek medical attention Skin Contact Wash affected area gently with soap and warm water after handling This product contains fiberglass wool insulation Fiberglass dust and cer...

Страница 3: ...ctory this unit is for use with natural gas only It is listed by Underwriters Laboratory An LP Gas conver sion kit is available Extreme mounting kits for slab and curbs are also available Packaged units are designed for outdoor mounting with a vertical condenser discharge They can be located either at ground level or on a roof in accordance with local codes or National Fuel Gas Code ANSI Z223 1A L...

Страница 4: ...Unit Clearances Figure 1 4DCL4024 through 4DCL4036 1 of 3 Figures 1 through 6 show the unit critical dimensions NOTE The view labed Bottom Side represents the base as viewed looking up from underneath the unit RELEASED 10 Aug 2020 16 34 00 GMT ...

Страница 5: ...Page 5 Installer s Guide Figure 2 4DCL4024 through 4DCL4036 2 of 3 RELEASED 10 Aug 2020 16 34 00 GMT ...

Страница 6: ...Page 6 Installer s Guide Figure 3 4DCL4024 through 4DCL4036 3 of 3 4DCL4024 060 4DCL4030 070 4DCL4036 4DCL6036 070 RELEASED 10 Aug 2020 16 34 00 GMT ...

Страница 7: ...Page 7 Installer s Guide Figure 4 4DCL4042 through 4DCL 4060 1 of 3 NOTE The view labed Bottom Side represents the base as viewed looking up from underneath the unit RELEASED 10 Aug 2020 16 34 00 GMT ...

Страница 8: ...Page 8 Installer s Guide Figure 5 4DCL4042 through 4DCL4060 2 of 3 RELEASED 10 Aug 2020 16 34 00 GMT ...

Страница 9: ...Page 9 Installer s Guide Figure 6 4DCL4042 through 4DCL4060 3 of 3 4DCL4042 090 4DCL4048 090 4DCL4060 115 RELEASED 10 Aug 2020 16 34 00 GMT ...

Страница 10: ...tion section for instruction on converting the supply and return airflow covers to down airflow 3 The field assembled Roof Mounting Curb BAYCURB050A or BAYCURB051A or a field fabricated curb should be in place before the unit is hoisted to the roof top The Roof Mounting Curb frame must be installed on a flat level section of the roof maximum of 1 4 per foot pitch and provide a level mounting surfa...

Страница 11: ... mate rial shall be maintained on air outlet duct Rooftop Installation Curb Mounting Convert Horizontal Airflow to Down Airflow The factory ships the unit for horizontal airflow Perform this procedure to convert the unit to down airflow 1 Remove the three 3 sheet metal screws securing the supply air cover and the four 4 sheet metal screws securing the return air cover from the base of the unit Rem...

Страница 12: ... clevis hooks pins or bolts to the unit casing casing hardware corner lugs angles tabs or flanges Failure to observe these warnings may result in equipment damage 1 Before preparing the unit for lifting check the unit dimension draw ings for center of gravity for lifting safety Figures 1 to 6 page 4 9 Because of placement of internal components the unit s weight may be unevenly distributed Approxi...

Страница 13: ...cations using field fabricated ducts and sleeper rails rather than a curb or frame use the following procedure 1 Locate and secure the sleeper rails to the roof Three 3 sleeper rails are required One on each end to support the edges of the unit and one across the center of the unit The center rail must run inside both drip lips Vibration isolators should be installed as indicated on Figure 9 adjus...

Страница 14: ...facturer is not responsible for the unauthorized use of this drawing and expressly disclaims any liability for damages resulting from such unauthorized use Gasket Seal Spreader Bars Base of unit rest on top of curb rails Drip lip on perimeter of unit IMPORTANT To prevent damage to the sides and top of the unit when hoisting use spreader bars as shown in these illustrations Figure 11 Curb Dimension...

Страница 15: ... Application with Frame Supply Air Return Air Roof Flashing Channel Iron Center Support Center Support required on all Frame Applications Angle Iron Frame Roof Flashing Return Air Angle Iron Frame Roof Flashing Supply Air Channel Iron Center Support Center Support required on all Frame Applica tions RELEASED 10 Aug 2020 16 34 00 GMT ...

Страница 16: ...ation transmission Elbows with turning vanes or splitters are recommended to minimize air noise and resistance The first elbow in the ductwork leaving the unit should be no closer than two 2 feet from the unit to minimize noise and resistance To prevent leaking do not attach the ductwork to the bottom of the unit base refer to the bottom example in Figure 14 A 3 4 inch female NPT condensate drain ...

Страница 17: ... pipe connection give serious consideration to providing the clearance necessary to remove the accesspanelsontheunit e g economizerandfilteraccesspanels NOTE In the absence of local codes the installation must conform with American National Standard Z223 1 National Fuel Gas Code Latest Revision The available gas supply must agree with the required gas supply marked on the unit nameplate Minimum pe...

Страница 18: ...nletboss connect the gas piping to the unit Check the completed piping for leaks using a soap and water solution or the equivalent 6 After installation of the gas pipe in the unit the pipe opening should be closed with the filler barrier plug provided Manifold Pressure Check the manifold pressure at the unit gas valve Do not exceed the recommended pressure shown on the unit nameplate Input Check a...

Страница 19: ...om 7000 8000 orifices must be changed to 50 HIGH ALTITUDE DERATE CHART NAT Altitude In Feet Inputs shown are with factory orifices 3 5 WC High Fire 1 8 WC Low Fire Natural Gas heating value of 950 btu cuft Electrical Power It is important that proper electrical power be available for the unit Voltage variation should remain within the limits found on the unit nameplate Disconnect Switch Provide an...

Страница 20: ...heat will operate with the heat pump when the unit requires a defrost cycle The gas heat is used to offset the effect of the unit going into the cooling mode during defrost For the CONT402 the unit will be commanded to transition to gas heat even when the outdoor temperature is abobve the selected outdoor temperature changeover oint if the heat pump capacity is not enough to maintain the indoor te...

Страница 21: ...Page 21 Installer s Guide Figure 22 4DCL4 Field Wiring Diagram CONSTANT CIRCULATION 4DCL4 FIELD WIRING DIAGRAM RELEASED 10 Aug 2020 16 34 00 GMT ...

Страница 22: ... to the normal operating pressures provided in the unit s SERVICE FACTS NOTE Do not use the PRESSURE CURVES from the unit s SERVICE FACTS to determine the unit refrigerant charge The correct charge is shown on the unit nameplate To charge the system accurately weigh in the charge according to the unit nameplate and check subcooling against the Subcooling Charging Table in the SERIVCE FACTS Voltage...

Страница 23: ... a manometer Do not exceed recommended pressures 4 Adjust the unit to obtain an air temperature rise with that specified on the unit nameplate NOTE For manifold pressures and orifice sizes for gas with other BTU ratings contact the local gas utility Manifold pressure should be 1 8 low to 3 5 high inches water column 0 1 Input must not exceed the value shown on the nameplate 5 Set the comfort contr...

Страница 24: ...ratures above 40 degrees heating is provided by Heat Pump operation only For temperatures 40 and below heating may be provided by both gas or Heat Pump operation TWO MODES OF OPERATION The unit can be installed and configured to operate in one of two different heating modes restricted and non restricted A brief explanation of each mode follows RESTRICTED In the restricted mode of operation an outd...

Страница 25: ...on 1st stage heat When the thermostat cycles the heat pump off power is removed from Y Y1 and G If the indoor blower delay is defeated in the unit it is an installer option for the thermostat to control the delay of the indoor blower by using G If there is a thermostat controlled indoor blower delay the thermostat will turn G off after the delay time set within the thermostat has elapsed Call for ...

Страница 26: ...o OFF for approximately three seconds then back ON CONT802 and CONT803 Operational Differences from the above sequence NOTE Unlike the CONT402 these two controls will not call for the furnace to operate when the outdoor temperature is above the selected outdoor temperature changeover point even if the heat pump capacity is not enough to maintain the indoor temperature at the desired heating setpoi...

Страница 27: ...a general unit inspection on a regular basis Filters When the system is in constant operation inspect the filters at least once each month If you have disposable type filters replace them with new filters of the same type and size Donotattempttocleandisposablefilters Permanent type filters can be cleaned by washing them with a milddetergentandwater Makesurethatthefiltersarethoroughly dry before re...

Страница 28: ... 7 Flashes Thermostat miswired W1 W2 Fast Flash Rate The LED will flash on for 1 4 second and off for 1 4 second Slow Flash Rate The LED will flash on for 3 4 second then off for 1 4 second The pause between groups of fast flashes is 3 seconds Status LED Liteport LED IGN Diagnostic Indicators Flash Codes CFM SELECTION LIGHT DIP SWITCHES CFM FAN R W3 W2 W1 Y Y LO J 21C800796P01 CNT03600 Figure 23 E...

Отзывы: