background image

 

Page 19

Installer’s Guide

Air Filter Installation

The packaged unit requires an air filter.  The unit does not come 
with a factory installed filter rack in it, however, two filter frame ac-
cessories are offered that will allow the installation of a filter within 
the unit, BAYFLTR101 & BAYFLTR201. Otherwise a field supplied 
filter rack must be installed by the installer in the return  duct work. 
Refer to Table 5 to determine filter sizes for field supplied filter racks. 

*Filters must be installed in the return air system. The above square 

footages are based on 300 F.P.M. face velocity.  If permanent filters are 

used, size per mfg. Recommendation with clear resistance of 0.05" W.C.

High Altitude Installation

Unit nameplate ratings are based on equipment operation from 
sea level to 2000 feet elevation above sea level. 

No orifice changes 

required for high altitude installation, please refer to below chart for 
rating information.

 

Table 4. High Altitude Derate Chart

Table 5. Filter Sizes (field supplied filter rack)

Electrical Connections

Electrical wiring and grounding must be installed in accordance 
with local codes or, in the absence of local codes, with the National 
Electrical Code ANSI/NFPA 70, Latest Revision.

Electrical Wiring

NOTE:

 This unit is factory wired for 230V. See wiring dia-

gram in SERVICE FACTS for 208V conversion.

Figure 19. Power Wiring

NOTE:

 

For branch circuit wiring (main power supply to unit 

disconnect), determine wire size for the length of run using the 

circuit ampacity found on the unit nameplate and the N.E.C.

For  more than 3 conductors in a raceway or cable, see the 

N.E.C. for derating the ampacity of each conductor.

Run power supply 

Lines through 

weather-tight 

conduit and secure 

to unit with strain 

relief

Unit Input

115k

2001

3000

4000 5000 6000 7000 8000

High stage

112100 104100 96200 88100 86900 85600 85100

Low stage

84000 78100 72100 66100 65100 64200 63800

90k

High stage

87700 81500 75200 69000 68000 67000 66500

Low stage

65700 61100 56400 51700 51000 50200 49900

70k

High stage

68200 63300 58500 53600 52900 52100 51800

Low stage

51100 47600 43900 40200 39600 39100 38800

60k

High stage

58500 54300 50100 46000 45300 44700 44300

Low stage

43800 40700 37600 34500 34000 33400 33200

For LP installations. Models that require #49 orifices, for 

altitudes from 7000 - 8000' orifices must be changed to #50. 

HIGH ALTITUDE DERATE CHART NAT.

Altitude (In Feet)

Inputs shown are with factory orifices @ 3.5"WC (High Fire) 

1.8"WC (Low Fire)

Natural Gas heating value of 950 btu/cuft.

Electrical Power

It is important that proper electrical power be available for the unit.  
Voltage variation should remain within the limits found on the unit 
nameplate.

Disconnect Switch

Provide an approved weatherproof disconnect within close proxim-
ity and 

within sight of the unit. 

If disconnect must be mounted to the 

cabinet, the location shown in Figure 21 should be the only one 
considered.

Over Current Protection

The branch circuit feeding the unit must be protected as shown on 
the unit nameplate.

Power Wiring

The power supply lines must be run in weather-tight conduit to the 
disconnect and into the side of the unit control box.  Provide strain 
relief for all conduit with suitable connectors. 
Provide flexible conduit supports whenever vibration transmission 
may cause a noise problem within the building structure.
1.  Remove the CONTROL/HEAT access panel. Pass the power  
  wires  through the Power Entry hole in the end of the unit.  
  See Figure 19.
2. Connect the high voltage wires to the appropriate contactor lug 

terminals. Single phase units use a two (2) pole contactor  
and three phase units use two (2) pole contactor and a Blue 
lead wire. Connect the ground to the ground lug on the chas-
sis. See Figure 20. Be sure all connections are tight. 

GROUNDING:  THE UNIT MUST BE ELECTRICALLY 

GROUNDED IN ACCORDANCE WITH LOCAL CODES OR 

THE NATIONAL ELECTRIC CODE.

NOTE: 

Unit must be grounded for ignitor to operate properly. 

Gas pipe to unit is not an adequate ground. Ground the unit 

internally as provided. 

HAZARDOUS VOLTAGE, MOVING PARTS, AND GAS

Bodily injury can result from high voltage electrical components, fast 

moving fans, and combustible gas. For protection from these inherent 

hazards during installation and service, the electrical supply must be 

disconnected and the main gas valve must be turned off. If operating 

checks must be performed with the unit operating, it is the technician's 

responsibility to recognize these hazards and proceed safely.

WARNING

!

NOMINAL

FILTER

CFM

SIZE(Sq Ft)

4

D

C

L

4024

800

2.67

0.08

4

D

C

L

4030

1000

3.33

0.08

4

D

C

L

4036

1200

4

0.08

4

D

C

L

4042

1400

4.67

0.08

4

D

C

L

4048

1600

5.33

0.08

4

D

C

L

4060

2000

6.67

0.08

UNIT

FILTER

RESISTANCE ("W.C.)

IMPORTANT: 

Air filters and media wheels or plates shall meet the test 

requirements in UL 900.

RELEASED 10/Aug/2020 16:34:00 GMT

Содержание 4DCL4024

Страница 1: ...ards during installation and service the electrical supply must be disconnected and the main gas valve must be turned off If operating checks must be performed with the unit operating it is the technician s responsibility to recognize these hazards and proceed safely WARNING SAFETY HAZARD Do not operate the unit without the evaporator fan or coil access pan els in place Reinstall the access panels...

Страница 2: ...erate fiber concentrations requiring additional respiratory pro tection Use the appropriate NIOSH approved respirator in these situations FIRST AID MEASURES Eye Contact Flush eyes with water to remove dust If symptoms persist seek medical attention Skin Contact Wash affected area gently with soap and warm water after handling This product contains fiberglass wool insulation Fiberglass dust and cer...

Страница 3: ...ctory this unit is for use with natural gas only It is listed by Underwriters Laboratory An LP Gas conver sion kit is available Extreme mounting kits for slab and curbs are also available Packaged units are designed for outdoor mounting with a vertical condenser discharge They can be located either at ground level or on a roof in accordance with local codes or National Fuel Gas Code ANSI Z223 1A L...

Страница 4: ...Unit Clearances Figure 1 4DCL4024 through 4DCL4036 1 of 3 Figures 1 through 6 show the unit critical dimensions NOTE The view labed Bottom Side represents the base as viewed looking up from underneath the unit RELEASED 10 Aug 2020 16 34 00 GMT ...

Страница 5: ...Page 5 Installer s Guide Figure 2 4DCL4024 through 4DCL4036 2 of 3 RELEASED 10 Aug 2020 16 34 00 GMT ...

Страница 6: ...Page 6 Installer s Guide Figure 3 4DCL4024 through 4DCL4036 3 of 3 4DCL4024 060 4DCL4030 070 4DCL4036 4DCL6036 070 RELEASED 10 Aug 2020 16 34 00 GMT ...

Страница 7: ...Page 7 Installer s Guide Figure 4 4DCL4042 through 4DCL 4060 1 of 3 NOTE The view labed Bottom Side represents the base as viewed looking up from underneath the unit RELEASED 10 Aug 2020 16 34 00 GMT ...

Страница 8: ...Page 8 Installer s Guide Figure 5 4DCL4042 through 4DCL4060 2 of 3 RELEASED 10 Aug 2020 16 34 00 GMT ...

Страница 9: ...Page 9 Installer s Guide Figure 6 4DCL4042 through 4DCL4060 3 of 3 4DCL4042 090 4DCL4048 090 4DCL4060 115 RELEASED 10 Aug 2020 16 34 00 GMT ...

Страница 10: ...tion section for instruction on converting the supply and return airflow covers to down airflow 3 The field assembled Roof Mounting Curb BAYCURB050A or BAYCURB051A or a field fabricated curb should be in place before the unit is hoisted to the roof top The Roof Mounting Curb frame must be installed on a flat level section of the roof maximum of 1 4 per foot pitch and provide a level mounting surfa...

Страница 11: ... mate rial shall be maintained on air outlet duct Rooftop Installation Curb Mounting Convert Horizontal Airflow to Down Airflow The factory ships the unit for horizontal airflow Perform this procedure to convert the unit to down airflow 1 Remove the three 3 sheet metal screws securing the supply air cover and the four 4 sheet metal screws securing the return air cover from the base of the unit Rem...

Страница 12: ... clevis hooks pins or bolts to the unit casing casing hardware corner lugs angles tabs or flanges Failure to observe these warnings may result in equipment damage 1 Before preparing the unit for lifting check the unit dimension draw ings for center of gravity for lifting safety Figures 1 to 6 page 4 9 Because of placement of internal components the unit s weight may be unevenly distributed Approxi...

Страница 13: ...cations using field fabricated ducts and sleeper rails rather than a curb or frame use the following procedure 1 Locate and secure the sleeper rails to the roof Three 3 sleeper rails are required One on each end to support the edges of the unit and one across the center of the unit The center rail must run inside both drip lips Vibration isolators should be installed as indicated on Figure 9 adjus...

Страница 14: ...facturer is not responsible for the unauthorized use of this drawing and expressly disclaims any liability for damages resulting from such unauthorized use Gasket Seal Spreader Bars Base of unit rest on top of curb rails Drip lip on perimeter of unit IMPORTANT To prevent damage to the sides and top of the unit when hoisting use spreader bars as shown in these illustrations Figure 11 Curb Dimension...

Страница 15: ... Application with Frame Supply Air Return Air Roof Flashing Channel Iron Center Support Center Support required on all Frame Applications Angle Iron Frame Roof Flashing Return Air Angle Iron Frame Roof Flashing Supply Air Channel Iron Center Support Center Support required on all Frame Applica tions RELEASED 10 Aug 2020 16 34 00 GMT ...

Страница 16: ...ation transmission Elbows with turning vanes or splitters are recommended to minimize air noise and resistance The first elbow in the ductwork leaving the unit should be no closer than two 2 feet from the unit to minimize noise and resistance To prevent leaking do not attach the ductwork to the bottom of the unit base refer to the bottom example in Figure 14 A 3 4 inch female NPT condensate drain ...

Страница 17: ... pipe connection give serious consideration to providing the clearance necessary to remove the accesspanelsontheunit e g economizerandfilteraccesspanels NOTE In the absence of local codes the installation must conform with American National Standard Z223 1 National Fuel Gas Code Latest Revision The available gas supply must agree with the required gas supply marked on the unit nameplate Minimum pe...

Страница 18: ...nletboss connect the gas piping to the unit Check the completed piping for leaks using a soap and water solution or the equivalent 6 After installation of the gas pipe in the unit the pipe opening should be closed with the filler barrier plug provided Manifold Pressure Check the manifold pressure at the unit gas valve Do not exceed the recommended pressure shown on the unit nameplate Input Check a...

Страница 19: ...om 7000 8000 orifices must be changed to 50 HIGH ALTITUDE DERATE CHART NAT Altitude In Feet Inputs shown are with factory orifices 3 5 WC High Fire 1 8 WC Low Fire Natural Gas heating value of 950 btu cuft Electrical Power It is important that proper electrical power be available for the unit Voltage variation should remain within the limits found on the unit nameplate Disconnect Switch Provide an...

Страница 20: ...heat will operate with the heat pump when the unit requires a defrost cycle The gas heat is used to offset the effect of the unit going into the cooling mode during defrost For the CONT402 the unit will be commanded to transition to gas heat even when the outdoor temperature is abobve the selected outdoor temperature changeover oint if the heat pump capacity is not enough to maintain the indoor te...

Страница 21: ...Page 21 Installer s Guide Figure 22 4DCL4 Field Wiring Diagram CONSTANT CIRCULATION 4DCL4 FIELD WIRING DIAGRAM RELEASED 10 Aug 2020 16 34 00 GMT ...

Страница 22: ... to the normal operating pressures provided in the unit s SERVICE FACTS NOTE Do not use the PRESSURE CURVES from the unit s SERVICE FACTS to determine the unit refrigerant charge The correct charge is shown on the unit nameplate To charge the system accurately weigh in the charge according to the unit nameplate and check subcooling against the Subcooling Charging Table in the SERIVCE FACTS Voltage...

Страница 23: ... a manometer Do not exceed recommended pressures 4 Adjust the unit to obtain an air temperature rise with that specified on the unit nameplate NOTE For manifold pressures and orifice sizes for gas with other BTU ratings contact the local gas utility Manifold pressure should be 1 8 low to 3 5 high inches water column 0 1 Input must not exceed the value shown on the nameplate 5 Set the comfort contr...

Страница 24: ...ratures above 40 degrees heating is provided by Heat Pump operation only For temperatures 40 and below heating may be provided by both gas or Heat Pump operation TWO MODES OF OPERATION The unit can be installed and configured to operate in one of two different heating modes restricted and non restricted A brief explanation of each mode follows RESTRICTED In the restricted mode of operation an outd...

Страница 25: ...on 1st stage heat When the thermostat cycles the heat pump off power is removed from Y Y1 and G If the indoor blower delay is defeated in the unit it is an installer option for the thermostat to control the delay of the indoor blower by using G If there is a thermostat controlled indoor blower delay the thermostat will turn G off after the delay time set within the thermostat has elapsed Call for ...

Страница 26: ...o OFF for approximately three seconds then back ON CONT802 and CONT803 Operational Differences from the above sequence NOTE Unlike the CONT402 these two controls will not call for the furnace to operate when the outdoor temperature is above the selected outdoor temperature changeover point even if the heat pump capacity is not enough to maintain the indoor temperature at the desired heating setpoi...

Страница 27: ...a general unit inspection on a regular basis Filters When the system is in constant operation inspect the filters at least once each month If you have disposable type filters replace them with new filters of the same type and size Donotattempttocleandisposablefilters Permanent type filters can be cleaned by washing them with a milddetergentandwater Makesurethatthefiltersarethoroughly dry before re...

Страница 28: ... 7 Flashes Thermostat miswired W1 W2 Fast Flash Rate The LED will flash on for 1 4 second and off for 1 4 second Slow Flash Rate The LED will flash on for 3 4 second then off for 1 4 second The pause between groups of fast flashes is 3 seconds Status LED Liteport LED IGN Diagnostic Indicators Flash Codes CFM SELECTION LIGHT DIP SWITCHES CFM FAN R W3 W2 W1 Y Y LO J 21C800796P01 CNT03600 Figure 23 E...

Отзывы: