18-HD64D1-4
Menu
Setting
Available Options
5.2.5 ADVANCED
AIRFLOW
VS Blower On Delay - Cooling .........................................................
No Delay
1 Minute @ 50%, 7.5 Minutes @ 80%
1 Minute @ 50%, 4 Minutes @ 80%
7.5 Minutes @ 80%
4 Minutes @ 80%
1 Minute @ 50%
30 Seconds @ 35%
VS Blower Off Delay - Cooling ......................................................... No Delay
1.5 Minutes @ 100%
45 Seconds @ 100%
30 Seconds @ 50%
1.5 Minutes @ 50%
3 Minutes @ 50%
30 seconds @ 35%
VS Blower On Delay - Compressor Heating .................................... No Delay
1 Minute @ 50%, 7.5 Minutes @ 80%
1 Minute @ 50%, 4 Minutes @ 80%
7.5 Minutes @ 80%
4 Minutes @ 80%
1 Minute @ 50%
30 Seconds @ 35%
VS Blower Off Delay - Compressor Heating .................................... No Delay
1.5 Minutes @ 100%
45 Seconds @ 100%
30 Seconds @ 50%
1.5 Minutes @ 50%
3 Minutes @ 50%
30 seconds @ 35%
Non VS Blower On Delay - Cooling ................................................. No Delay
15 Seconds
30 Seconds
90 Seconds
Non VS Blower Off Delay - Cooling ................................................. No Delay
30 Seconds
60 Seconds
90 Seconds
Non VS Blower On Delay - Compressor Heating ............................. No Delay
15 Seconds
30 Seconds
Non VS Blower Off Delay - Compressor Heating ............................. No Delay
30 Seconds
60 Seconds
90 Seconds
Hydronic Heat Blower On Delay ...................................................... No Delay
30 Seconds
60 Seconds
Hydronic Heat Blower Off Delay ...................................................... No Delay
30 Seconds
60 Seconds
90 Seconds
Compressor Low Stage Air Flow % - Cooling .................................. 35% - 60%
55% - 80%
Compressor Low Stage Air Flow % - Compressor Heating ............. 35% - 60%
55% - 80%
Installer Setup Menus and Options (continued)