www.trafag.com
Operating menu
Description
Value range
Switch point SP1 (Hysteresis) or Window high FH1
SP1 > rP1, FH1 > FL1
Hysteresis ≥ 1 % FS
Reset point rP1 (Hysteresis) or Window low FL1
rP1 < SP1, FL1 < FH1
Hysteresis ≥ 1 % FS
Switch point SP2 (Hysteresis) or Window high FH2
SP2 > rP2, FH2 > FL2
Hysteresis ≥ 1 % FS
Reset point rP2 (Hysteresis) or Window low FL2
rP2< SP2, FL2 < FH2
Hysteresis ≥ 1 % FS
Reset to factory settings
Switching delay time for SP1/FH1
0.01 ... 99.99s
Switching delay time for rP1/FL1
0.01 ... 99.99s
Switching delay time for SP2/FH2
0.01 ... 99.99s
Switching delay time for rP2/FL2
0.01 ... 99.99s
Function switching output 1
Hysteresis NO (Hno), Hysteresis NC (Hnc)
Window NO (Fno), Window NC (Fnc)
Function switching output 2
Hysteresis NO (Hno), Hysteresis NC (Hnc)
Window NO (Fno), Window NC (Fnc)
Pressure unit
bar/MPa/kPa/psi/m WC/mm WC
Lowest measured pressure
Highest measured pressure
Reset highest and lowest pressure value
Analogue output type
I, U, off
Pressure zero point
Pressure end point
50 % ... 100 % FS
Analogue output zero point
Analogue output end point
Damping analogue output
rise time 10 ... 90 % nominal pressure
0.01 ... 3.00 s
Display rotate
no, yes (180°)
Display mode
actual, highest, lowest, off,
act. – 1 decimal, act. – 2 dec., act. – 3 dec.
Display update rate
1, 2, 5, 20 Hz
Diagnostic mode
Sampling time for logger
0.1 ... 999.9 s, off (0)
Access code
4-digit code
Factory use
By pressing
▲
+
▼
simultaneously
the menu will return to the base dis-
play or automatically after ca. 60 s
without operation.
pw* When performing a parameter change by pressing
▲
or
▼
and if
an access code has been defined, it has to be entered digit by digit.
W
e r
eserve the right to mak
e alternations as technical pr
ogr
es
s may warr
ant.
H73320f
Tr
afag
AG 01/2018
After confirming the new parameter value, the menu item of the
changed parameter will be displayed.
Base Display
unit indication
actual value
SP1
value
rP1
value
SP2
value
rP2
value
EF
rES
function
dS1
value
dr1
value
dS2
value
dr2
value
ou1
list
ou2
list
uni
list
Lo
display only
Hi
display only
HLrE
function
oAnA
list
P_nP
display only
P_EP
value
o_nP
display only
o_EP
display only
dAA
value
diSr
list
diS
list
DuPd
list
diA
function
StiN
value
CodE
value
CAL
function
Base Display
SP1
parameter
EF
rES
parameter
parameter
parameter
list or value
pw
+
+
+