background image

 

Installation Instructions                        Revised 10/13/2015                 Copyright (C) 2008                    Proverbs 22:29                     Page 9                         
 

 

 

Duct Pipe and Fitting Sizes 

(Continued)

 

Duct Runs – Length 

a.

 

Configure the ventilation duct run to be as short and as direct to the outside as possible.  Minimize 
the number of elbows and transition fittings used.  Complex or long runs should be reviewed by a 
qualified installer. 

 

b.

 

No portion of the ducting should be run so that the exhaust air flows downward.  Since exhaust heat 
rises, forcing the air to flow downward will cause increased static pressure.  As previously mentioned, 
improperly installed duct pipe will cause excessive static pressure (air resistance), that may result in 
rattling, vibration and air buffeting noises, as well as inadequate ventilation. 

 

c.

 

Duct runs for 390CFM ventilator models should not exceed 20 linear feet with two 90-degree elbows 
(or four 45-degree elbows), a damper and a roof or wall cap.  Longer runs or additional elbows will 
result in decreased ventilation performance.   Each 90-degree elbow is the equivalent of 8 linear feet 
of duct pipe; each 45-degree elbow is equivalent to 4 linear feet of duct pipe. 

 

d.

 

Always run ventilator ducts to the outdoors.  DO NOT terminate a duct into an attic, basement, 
garage, crawl space under a house, a chimney, other ducting or an enclosed room. 

4.

 

Dampers 

IMPORTANT:

  DO NOT USE SCREWS TO ATTACH ANY TYPE OF DAMPER AS THE SCREWS MAY BLOCK THE 

DAMPER BLADES. 
 

IMPORTANT:

  DO NOT USE MORE THAN ONE DAMPER IN THE VENTILATION SYSTEM.  

NOTE

:  Many styles of 

roof caps and wall caps have built-in dampers.  See 

Roof Caps and Wall Caps

 section for more detail. 

 

Always use carefully crafted, tightly wrapped Aluminum Foil Metal Duct Tape on all connections and physically 
view and test the damper blades to make certain they are opening and closing correctly.  Make sure that the 
damper blades do not touch the duct walls and that there is no debris blocking the free movement of the 
damper mechanism.  Common things to look for include screws protruding into the blade’s path, overspray of 
paint, plaster and insulation.  If using rectangular duct, be sure that all four sides of the duct are on the 
outside of the damper’s start collar or frame. 

 

390CFM Models 

390CFM models have a 7" round Ducting and Damper.   
DO NOT USE SCREWS TO ATTACH THE DUCT TO THE DAMPER FRAME AS THE SCREWS MAY BLOCK 
THE DAMPER BLADE.  ALWAYS use Aluminum Foil Metal Duct Tape on all connections and physically 
view the damper blade to make certain it is operating correctly.  On ventilator installations designed 
to recirculate the exhaust air back into the kitchen, be sure to remove the aluminum damper blade 
before attaching the duct to the damper frame. 

 

Damper in Roof Cap or Wall Cap 

In ventilation systems utilizing a roof cap or wall cap 

with

 a built-in damper, do not install an 

additional in-line damper. Two dampers are unnecessary and will cause increased static pressure (air 
resistance), that may result in rattling, vibration and air buffeting noises, as well as inadequate 
ventilation. 

 
In-line Damper

 (for ventilation systems utilizing a roof cap or wall cap 

without

 a built-in damper)

 

In cold weather areas, installing an “in-line” damper may be the preferred type of installation.  This is 
because in-line dampers installed just above the perimeter of the heated space (the ceiling) will 
reduce the amount of cold air traveling down the duct into the heated space and into the kitchen 
through the ventilator. 
 
 

Содержание PMB02

Страница 1: ...age or incorrect installation TIPS Contain helpful information to facilitate installation READ AND SAVE THESE INSTRUCTIONS WARNING TO REDUCE THE RISK OF FIRE ELECTRICAL SHOCK OR INJURY TO PERSONS OBSERVE THE FOLLOWING a Use this unit only in the manner intended by the manufacturer If you have any questions please contact the manufacturer at the address or telephone number listed in the warranty b ...

Страница 2: ...ible 2 Ducts must be of adequate size and duct runs should be as short as possible Where turns are necessary keep turning radius as large and as smooth as possible 3 The ducting must be air tight Use a minimum of 2 sheet metal screws at every duct joint Then seal the duct joints with high quality duct tape 4 Do not use this unit with any solid state speed control device 5 This unit must be grounde...

Страница 3: ...your custom canopy Failure to do so could distort and damage the liner and void the warranty Given that most installations are different a back draft damper is not provided with this unit Always install ventilation products with an approved wall or roof cap Duct performance is improved by using round smooth metal duct work instead of rectangular If multiple elbows must be used ensure that there is...

Страница 4: ...LABEL Because the Trade Wind Standard Series Liner was designed for various wood hood applications no mounting holes have been pre drilled This allows the liner to be attached in most any area of the canopy that has a wood frame support e g the back sides or top We recommend at least six equally spaced screws per liner three screws along the back top or back side panel and three screws on the fron...

Страница 5: ...liner while pressing the front side upwards into place The filters may be cleaned by hand washing in hot water using a mild detergent solution or by placing in an automatic dishwasher Dry the filters before reusing CAUTION Most common scrubber type pads will scratch the liner If a commercially available stainless steel cleaner is used it is important to read the labels for chlorine compounds Chlor...

Страница 6: ... rather than amps divide the watts by 120 and this will give you the amperage rating CAUTION The neutral wire usually white for the ventilator must connect to the same neutral wire that comes from the electrical panel to the liner It is recommended to run a white neutral wire from the liner s white neutral wire along the same path as the red wire from the liner s variable speed control to the vent...

Страница 7: ...ucting or restrictive roof caps is not covered and will by default be charged back to the Homeowner Trade Wind disclaims and excludes any liability for implied warranties or for incidental or consequential damages wherever permitted by law There are no implied warranties of merchantability or fitness for a particular use or purpose This warranty gives you specific legal rights and you may also hav...

Страница 8: ... DO NOT use butt joints c For best air flow elbows and pipe size transition fittings should not be directly connected to one another Where possible always include at least 15 inches of straight pipe between fittings 3 Duct Pipe and Fitting Sizes See Duct Sizing Chart and Area Calculations Section for more detail IMPORTANT DO NOT use either of the following duct pipe sizes or fitting sizes for any ...

Страница 9: ...refully crafted tightly wrapped Aluminum Foil Metal Duct Tape on all connections and physically view and test the damper blades to make certain they are opening and closing correctly Make sure that the damper blades do not touch the duct walls and that there is no debris blocking the free movement of the damper mechanism Common things to look for include screws protruding into the blade s path ove...

Страница 10: ...zed portion of a roof cap or wall cap will cause excessive static pressure that may result in rattling vibration and air buffeting noises as well as inadequate ventilation Roof caps and wall caps must have an integral bird screen 6 Attaching Duct to House Framework The ventilation system should be attached to the framework in such a manner that the weight of the duct and fittings is supported with...

Страница 11: ...7 Round Metal Duct 38 5 38 5 8 Diameter Round 50 25 8 Round Metal Duct or 6 x 9 Rectangular Metal Duct 50 25 54 50 25 54 10 Diameter Round 78 5 10 Round Metal Duct 78 5 78 5 3 25 x 10 Rectangular 32 5 3 25 x 10 Rectangular Metal Duct 32 5 32 5 Calculating Square Inches of Various Duct Sizes Types ROUND DUCT RECTANGULAR DUCT Radius x Radius x 3 1416 Area Sq Inches Width x Depth Area Sq Inches x x x...

Отзывы: