Installation Instructions Revised 10/13/2015 Copyright (C) 2008 Proverbs 22:29 Page 6
6
INSTRUCTIONS:
A 15 to 20 amp electrical service is recommended for proper electrical supply. Before
determining, calculate amp ratings based on the product label found on the PMB series module. Always observe
local building codes. Always use a dedicated circuit. Line load is calculated by adding the amperage of the
halogen lights to the rated amperage of the ventilator.. If the ventilator is rated in watts rather than amps, divide the
watts by 120 and this will give you the amperage rating.
CAUTION:
The neutral wire (usually white) for the ventilator must connect to the same neutral wire that
comes from the electrical panel to the liner. It is recommended to run a white neutral wire from the liner’s white
neutral wire along the same path as the red wire from the liner’s variable speed control to the ventilator.
Factory Installed Variable-Speed Wiring Details
Black
120 volt AC from electrical panel (usually black)
White
Neutral from electrical panel (white)
Green
Ground from electrical panel (usually green)
Wiring Diagram
PMB Series Models
Liner
House Electrical
Panel
Green
White (N)
120V Black (L)