Trackunit ME500-X, Technical Manual v.1.1, January

 

2016 

 Page 11 

Power supply  

The unit 

must

 be connected to 12V, +24V, +36V or +48V battery voltage through a 

1 amp. fuse. The use of a fused supply wire is important for not damaging the wires 
related to the unit in case of a short circuit etc. 

Digital inputs  

The activation of a digital input requires a minimum high level voltage of 8V.  

Digital output 

The digital output has the type indication ”LO-side switch”, that connects the output to 0V 
“ground”, when the output is active. This output can be used to control a relay powered 
from an external DC supply voltage. The maximum current drawn from the output is 
200mA and the voltage from the external supply voltage must not exceed 52V DC. 
 
The output is protected against short circuits, overload and is also protected against over 
voltage. For further information about connection possibilities of the digital output, see 
chapters about installation later in this manual.  

Motion/acceleration sensor 

The unit has a built-in 3 axis acceleration sensor that is able to activate the unit if it, as a 
consequence of disconnected supply voltage, is in stand-by mode.  

1-Wire input 

The 1-wire (Green wire) is designed to communicate with Dallas iButton Key or Trackunit 
RFID/PIN reader for access control. 
 
The 1-wire input is only operational when supply voltage (12V / 24V / 48V) is present. 
It cannot operate on internal battery alone. 
 

Installing the ME500-X as to surpass the main switch on the machine: 

 
In case the main switch on the machine will break the negative wire (Ground wire), the 
inputs may register a voltage level and start counting operating hours. To avoid this 
situation the digital input 4 (Pink wire) should be connected to the chassis/ground on the 
machine. Then send the following SMS to the unit (phone number) to activate the filtering:  
 

Function 

Send SMS 

Return-SMS from the unit 

Activate filter function on inputs. 

MT INFILT ON

 

MTC ACK (SERIAL No.) INFILT ON

 

 

NOTE:

 

Enabling the filtering function will disable the use of the digital input 4 as a 
normal input. 

 

NOTE:

 

It is recommended always to connect digital input 2 to the ignition signal of the 
vehicle or machine. 

 

NOTE:

 

For the “Send SMS” it is of no importance if small or capital letters are used in 
the command string, or a mixture hereof. 

Содержание ME500-X

Страница 1: ...ME500 X Trackunit ME500 X Technical Manual v 1 1 January 2016 Page 1 ME500 X Technical Manual Version 1 1 January 2016...

Страница 2: ...Digital inputs 11 Digital output 11 Motion acceleration sensor 11 1 Wire input 11 Functionality check 12 LED 12 Status SMS Commands 13 Installation of the digital output 15 SMS commands for output con...

Страница 3: ...n material authorization procedures or as otherwise instructed by Trackunit Warranty Exclusions and Disclaimers The foregoing Product Limited Warranty shall only apply in the event and to the extent t...

Страница 4: ...nstructions may cause harmful interference to radio communication However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful inter...

Страница 5: ...ackunit assumes that you are familiar with Microsoft Windows Related Information The Trackunit web site is found at www trackunit com This site links to the fleet management system from M Tec Trackuni...

Страница 6: ...acts are shorted Do not exceed the temperature ranges or other environmental conditions specified by the battery manufacturer Dispose of used batteries according to the instructions provided with the...

Страница 7: ...r installation so any vehicle moving machinery construction machinery installed with the ME500 X etc must not operate near health care facilities when any regulations posted in these areas prohibit th...

Страница 8: ...d and the air bag inflates serious injury could result Specific Human Absorption Rates SAR THE ME500 X UNIT IS NOT DESIGNED TO BE WORN ON A PERSON S BODY AS SUCH BODY WORN TEST POSITIONS FOR THE ME500...

Страница 9: ...d and start transmitting if an authorized GSM network is available While a basic understanding of the different ME500 X operational states is helpful configuring the ME500 X unit does not require a hi...

Страница 10: ...not beneath metal parts To reduce hum and noise in the FM radio it is recommended to place the unit at a minimum distance of 20 inches 50 cm from the radio or the loudspeakers Connections The connecti...

Страница 11: ...n sensor that is able to activate the unit if it as a consequence of disconnected supply voltage is in stand by mode 1 Wire input The 1 wire Green wire is designed to communicate with Dallas iButton K...

Страница 12: ...nd constant green light in LED GSM network is OK and GPS has valid satellite position No light in LED No power supply Constant red light and no green light in LED Power supply is OK but NO GSM network...

Страница 13: ...garage would reduce signal quality MT SIGNAL MTC ACK SERIAL No SIGNAL GSM 22 SAT 8 SN 44 GSM is a measure for the quality of the GSM coverage The value should be at least 10 Maximum value for GSM and...

Страница 14: ...the unit is off thus no power on the unit Check if the installation is performed correctly according to the guidelines of this manual F3 The LED is constant red thus the unit is not attached to the GS...

Страница 15: ...upply voltage etc The current consumption of the relay must not exceed 200 mA DC current and the relay contacts must be specified to withstand the load that needs to be controlled NOTE The output can...

Страница 16: ...command the output is deactivated NOTE For the Send SMS it is of no importance if small or capital letters are used in the command string or a mixture hereof Safety precautions The use of the digital...

Страница 17: ...have a problem and cannot find the information you need in the product documentation please contact Trackunit A S Trackunit A S Industrivej 10 9490 Pandrup Tel 45 9973 0020 E mail support trackunit c...

Страница 18: ...uiry will be processed by our support team and a support ticket number will be created in our system You will receive your ticket number by email 2 In case your hardware needs to be sent to us you wil...

Страница 19: ...A 10 mA average at 12V 24V Consumption during charging on an empty battery 225 mA 115 mA max at 12V 24V Standby time on the backup battery TBD Charging time for an empty backup battery 3 hours at 25 C...

Страница 20: ...ME500 X 1 9 Trackunit ME500 X Technical Manual v 1 1 January 2016 Page 20...

Страница 21: ...quirements Notice statements according to CFR 47 Part 15 19 RSS GEN The ME500 X product complies with Part 15 of the FCC rules and with Industry Canada license exempt standard s Operation is subject t...

Страница 22: ...et fonctionner une distance minimale de 20 cm entre l appareil irradiant et votre corps Cet metteur ne doit pas tre install ou utilis en conjonction avec d autres antennes ou d autres metteurs EEC Int...

Страница 23: ...1 2007 Cold EN IEC 60068 2 2 2007 Dry Heat EN IEC 60068 2 27 2008 Shock SAEJ1455 EN IEC 60068 2 32 Drop SAEJ1455 EN IEC 60068 2 64 2008 Random vibration EN IEC 60068 2 78 2001 Damp heat steady state...

Страница 24: ...X product complies with the essential requirements of the R TTE Directive 1999 5 EC as stated by the EC Declaration of Conformity Certificates and Declaration of conformity DOC statements can be down...

Отзывы: